Sprinkler systems can be defined as? 3

Sprinkler systems, residential sprinklers and automatic sprinklers

Define automatic sprinkler

Discharges water over specific area when heat actuated element is heated to above a preset temperature

Define residential sprinklers

Sprinklers specifically listed in residential occupancies

What are the three different styles of automatic sprinkler systems?

Dry, wet, preaction

Define dry system

Piping normally contains air under pressure

Define pre-action system

Piping normally dry, fire alarm sends a signal to solenoid valve which lets water into system

It is a device that opens automatically and directs water on to fire called a sprinkler or a head?

Sprinkler

NFPA stands for?

National fire protection Association

After how many stories kind of building not be residential anymore?

Five or more stories

What are the temperature ratings for residential sprinklers?

135 F to 170 F ordinary


175 F to 225 F intermediate

What are three predominant styles of sprinklers?

Pendant, sidewall, upright

What is most important aspect of sprinkler system?

Location

Maximum square footage coverage of sprinkler

144 ft.²

Maximum distance to wall for sprinkler

6 feet

Maximum distance between sprinklers

8 feet or 12 ft?

Maximum distance from the ceiling to sprinkler deflector if not positioned

4 to 6 inches

All pipe and fittings used for residential sprinkler systems must be able to withstand pressure and temperature of what?

175 PSI and 120°F

What types of copper can you use for residential sprinkler systems?

KL and M

Copper joints for what systems Shall be?

Brazed or 95/5

Why can't 50-50 solder be used on sprinkler systems

Will blow apart

What types of plastic pipe are acceptable for sprinkler systems?


3

Schedule 80 C PVC threaded or socket type, schedule 40 C PVC socket type and pex

When are you allowed to use half-inch to supply sprinkler?

If it is pex and it has three separate paths

What gallons per minute is one sprinkler design for

18 gallons per minute

What's gallons per minute is two sprinklers designed for?

26 gallons per minute

What are four approved sources of water for a sprinkler system?

1. Water service


2. Elevated tank


3. Pressure tank


4. Stored water with pump

What are the four elements of a sprinkler piping arrangement?

Main control valve, pressure gauge, waterflow alarm, drain.

What is required if building exceeds 2000 ft.² or is more than one story?

At least one fire department connection, connection should be at least one and a half inches

What is the minimum size of a drain pipe on the sprinkler system?

1 inch

What is maximum temperature of water permitted to sprinkler system?

120°F or 49°C

Sprinkler systems need test gauges for what?

Supply pressure, system pressure, if there is backflow preventer or two gauges are required

What are four stages of fire?

Incipient stage, smoke stage, flame stage, high heat stage

Air normally contains what percentage of oxygen?

21%

At what percentage of oxygen does thinking and coordination become difficult?

Below 17%

What percentage of oxygen is breathing becomes impossible?

6%

What are three different types of fire detectors?

Smoke detectors, thermal or heat detectors, flame detectors

Which is more expensive smoke detectors or heat detectors?

Smoke detectors

What are two basic types of smoke detectors?

Ionization and photo electric

What are two types of water flow alarms? And how do they operate?

1. Water alarm alarm signal devices have a title or Dane that moves to signal flow of water


2. Pressure operated electric switches sense the change in pressure to indicate water flow

How long before should hydrostatic test be prepared?

24 hours

What is hydrostatic test?

Water test pressurized with all air out of system

What are the test pressure requirements of a hydrostatic test?

200 psi or 50 psi more than working pressure

Siamese connection is require what kind of connectors?

Threaded

Siamese connections are fastened using what size connections?

2 1/2 inches

Is drip valve installed upstream or downstream of Siamese connection?

Downstream

Water storage reservoir us must be capable of holding how many minutes of water supply?

30 minutes

Most common valves used for fire protection systems?

OS and Y

Stamp pipes that contain glycol require what?

Backflow protection device

Firehose cabinet that has two valves installed is classified as?

Class III

Ball drips are installed between?

Check valve and Siamese

Standpipe systems are used for what class of fire?

Class A

Class 3 hose cabinets have?

2 1/2" connections with an adapter for one 2 1/2" connection and one 1 1/2" connection

Class one standpipe system will be used by?

Trained site personnel or fire department

Type B fires are caused by?

Flammable liquids

Class 2 cabinets have one valve and are intended for use by?

Building occupants

What is class a fire

Ordinary combustible's Like wood and pipe

What is class a fire

Ordinary combustible's Like wood and pipe

What is class B fire?

Liquids, oils, gasoline

What is class C fire?

Electrical

What is a class D fire?

Flammable metals

What is class K fire?

Kitchen, kitchen fire

The device that opens automatically and directs water onto the fire is called?

A sprinkler

What is a dry system?

Normally contains air so no standing water

How is initial operation of a pre-action system controlled?

Sprinkler pipe is dry, solenoid valve directs water into sprinkler line when automatic detection device senses fire

What is AFC an abbreviation for?

Alberta Fire Code

What are 3 possible remedies for the installation of residential fire sprinklers exposed to freezing.

Glycol, antifreeze, dry system

What types of sprinkler must you inform owner not to paint over or conceal?

Concealed sprinklers and pendant type sprinklers with special finishes

What types of sprinkler must you inform owner not to paint over or conceal?

Concealed sprinklers and pendant type sprinklers with special finishes

What types of sprinklers would be best suited for a daycare? 2

Pendant with guard or concealed

If an elevated tank is utilized on a residential fire sprinkler system, what is the min water supply duration?

30 min

The main control elements of a sprinkler piping arrangement include which of the following? 4

Main control valve, pressure gauge, water flow alarm, drain

Sprinkler systems over 100 psi, what must be installed?

A prv

In relation to fire code, nfpa 13 R, R represents

Residential