Sprinkler systems can be defined as? 3 |
Sprinkler systems, residential sprinklers and automatic sprinklers |
|
Define automatic sprinkler |
Discharges water over specific area when heat actuated element is heated to above a preset temperature |
|
Define residential sprinklers |
Sprinklers specifically listed in residential occupancies |
|
What are the three different styles of automatic sprinkler systems? |
Dry, wet, preaction |
|
Define dry system |
Piping normally contains air under pressure |
|
Define pre-action system |
Piping normally dry, fire alarm sends a signal to solenoid valve which lets water into system |
|
It is a device that opens automatically and directs water on to fire called a sprinkler or a head? |
Sprinkler |
|
NFPA stands for? |
National fire protection Association |
|
After how many stories kind of building not be residential anymore? |
Five or more stories |
|
What are the temperature ratings for residential sprinklers? |
135 F to 170 F ordinary 175 F to 225 F intermediate |
|
What are three predominant styles of sprinklers? |
Pendant, sidewall, upright |
|
What is most important aspect of sprinkler system? |
Location |
|
Maximum square footage coverage of sprinkler |
144 ft.² |
|
Maximum distance to wall for sprinkler |
6 feet |
|
Maximum distance between sprinklers |
8 feet or 12 ft? |
|
Maximum distance from the ceiling to sprinkler deflector if not positioned |
4 to 6 inches |
|
All pipe and fittings used for residential sprinkler systems must be able to withstand pressure and temperature of what? |
175 PSI and 120°F |
|
What types of copper can you use for residential sprinkler systems? |
KL and M |
|
Copper joints for what systems Shall be? |
Brazed or 95/5 |
|
Why can't 50-50 solder be used on sprinkler systems |
Will blow apart |
|
What types of plastic pipe are acceptable for sprinkler systems? 3 |
Schedule 80 C PVC threaded or socket type, schedule 40 C PVC socket type and pex |
|
When are you allowed to use half-inch to supply sprinkler? |
If it is pex and it has three separate paths |
|
What gallons per minute is one sprinkler design for |
18 gallons per minute |
|
What's gallons per minute is two sprinklers designed for? |
26 gallons per minute |
|
What are four approved sources of water for a sprinkler system? |
1. Water service 2. Elevated tank 3. Pressure tank 4. Stored water with pump |
|
What are the four elements of a sprinkler piping arrangement? |
Main control valve, pressure gauge, waterflow alarm, drain. |
|
What is required if building exceeds 2000 ft.² or is more than one story? |
At least one fire department connection, connection should be at least one and a half inches |
|
What is the minimum size of a drain pipe on the sprinkler system? |
1 inch |
|
What is maximum temperature of water permitted to sprinkler system? |
120°F or 49°C |
|
Sprinkler systems need test gauges for what? |
Supply pressure, system pressure, if there is backflow preventer or two gauges are required |
|
What are four stages of fire? |
Incipient stage, smoke stage, flame stage, high heat stage |
|
Air normally contains what percentage of oxygen? |
21% |
|
At what percentage of oxygen does thinking and coordination become difficult? |
Below 17% |
|
What percentage of oxygen is breathing becomes impossible? |
6% |
|
What are three different types of fire detectors? |
Smoke detectors, thermal or heat detectors, flame detectors |
|
Which is more expensive smoke detectors or heat detectors? |
Smoke detectors |
|
What are two basic types of smoke detectors? |
Ionization and photo electric |
|
What are two types of water flow alarms? And how do they operate? |
1. Water alarm alarm signal devices have a title or Dane that moves to signal flow of water 2. Pressure operated electric switches sense the change in pressure to indicate water flow |
|
How long before should hydrostatic test be prepared? |
24 hours |
|
What is hydrostatic test? |
Water test pressurized with all air out of system |
|
What are the test pressure requirements of a hydrostatic test? |
200 psi or 50 psi more than working pressure |
|
Siamese connection is require what kind of connectors? |
Threaded |
|
Siamese connections are fastened using what size connections? |
2 1/2 inches |
|
Is drip valve installed upstream or downstream of Siamese connection? |
Downstream |
|
Water storage reservoir us must be capable of holding how many minutes of water supply? |
30 minutes |
|
Most common valves used for fire protection systems? |
OS and Y |
|
Stamp pipes that contain glycol require what? |
Backflow protection device |
|
Firehose cabinet that has two valves installed is classified as? |
Class III |
|
Ball drips are installed between? |
Check valve and Siamese |
|
Standpipe systems are used for what class of fire? |
Class A |
|
Class 3 hose cabinets have? |
2 1/2" connections with an adapter for one 2 1/2" connection and one 1 1/2" connection |
|
Class one standpipe system will be used by? |
Trained site personnel or fire department |
|
Type B fires are caused by? |
Flammable liquids |
|
Class 2 cabinets have one valve and are intended for use by? |
Building occupants |
|
What is class a fire |
Ordinary combustible's Like wood and pipe |
|
What is class a fire |
Ordinary combustible's Like wood and pipe |
|
What is class B fire? |
Liquids, oils, gasoline |
|
What is class C fire? |
Electrical |
|
What is a class D fire? |
Flammable metals |
|
What is class K fire? |
Kitchen, kitchen fire |
|
The device that opens automatically and directs water onto the fire is called? |
A sprinkler |
|
What is a dry system? |
Normally contains air so no standing water |
|
How is initial operation of a pre-action system controlled? |
Sprinkler pipe is dry, solenoid valve directs water into sprinkler line when automatic detection device senses fire |
|
What is AFC an abbreviation for? |
Alberta Fire Code |
|
What are 3 possible remedies for the installation of residential fire sprinklers exposed to freezing. |
Glycol, antifreeze, dry system |
|
What types of sprinkler must you inform owner not to paint over or conceal? |
Concealed sprinklers and pendant type sprinklers with special finishes |
|
What types of sprinkler must you inform owner not to paint over or conceal? |
Concealed sprinklers and pendant type sprinklers with special finishes |
|
What types of sprinklers would be best suited for a daycare? 2 |
Pendant with guard or concealed |
|
If an elevated tank is utilized on a residential fire sprinkler system, what is the min water supply duration? |
30 min |
|
The main control elements of a sprinkler piping arrangement include which of the following? 4 |
Main control valve, pressure gauge, water flow alarm, drain |
|
Sprinkler systems over 100 psi, what must be installed? |
A prv |
|
In relation to fire code, nfpa 13 R, R represents |
Residential |