How to make maxitrol go to high fire (probably not on test)

Remove 4 for high fire


Remove 7 (or 8) for low fire

Direct fired is 100% efficient?

True

When are they designed to turn on PPM?

1000 ppm will turn it on

In the winter time?

Take your filters off

Indirect differences between it and direct?

Has: Heat exchanger, roll out switch


Doesnt have: profile plate


Isolation dampers are usually parallel?

True

What is the purpose of a V-Bank filter configuration?

Allows for more filter surface area.


Magnehelic gauge measures static pressure across the filters to know how plugged the filters are.

Rate of flow across the burner?



How does variable airflow MUA work with variable airflow?

2500-3200 fpm


Low pressure proves above 2500 fpm


High pressure trips if above 3200 fpm



Variable airflow uses a modulating profile plate

Dont need to know

Back (Definition)

What is a common temperature rise?

Direct Fired Burner


• Most direct gas-fired MUAs have a supply-air temperature between 50°F and 100°F (10°C and 38°C)


• Temperature rise ranges from 0°F to 100°F

If you open the profile plates then open both? T/F

True, if you open them then the velocity will increase

Service call: Blower Not Running


Name some causes..

Blower Not Running


• If the blower is not running:


• Check power supply to the unit and motor


Verify that freeze protection has not activated


• Make sure dampers are operational


• Make sure end switch is working properly.


Normally the switch closes when the damper is open


• Check Exhaust fan is on


• Check air Filters.


•motor running backwards

Where are the ports located to measure low velocity or high velocity

Low port is after the profile plate



High port is before the profile plate

The pressure switches sense static pressure, when should you test your switches? Heat on or off?

Heat must be on

What is the maximum allowable voltage drop across the contactor?

No more that 3% voltage drop across the contactor

Name three types of MUA heat exchangers?

3 Types of Heat Exchangers


-Clam Shell


-Tubular


-Drum and Tube

What is a reverse interlock?

A reverse interlock is when the MUA will shut down the EF if the MUA fails.

What are the 2 types of burners for MUA?

Burners


• The two main types of burners used in indirect fired MUA units are upshot and in-shot


• Depending on the age of the MUA, most have in-shot burners.


• When diagnosing an ignition issue, be aware that few things can go wrong with the burner itself other than becoming misaligned or dirty.

What is the temperature of a HSI?

Hot Surface Ignition


Direct Spark Ignition


• Ceramic materials with an electric heating element


• When 120 V is applied to the igniter, current flows through the element causing it to glow red.


• The surface temp may exceed 980°F


• An HSI is only energized for a few seconds.

What is the voltage of an ignition transformer?

Its in the thousands.



1/8 inch away from surface. Hold it with insulated wire

flame sense question and diaphragm question on TQ?

Not sure what they are.



Bleed tube goes from diaphram to the pilot flame (standing flame)


Removes excess gas from diaphragm.


You need a bleed line so the solenoid can open.


How to make maxitrol go to high fire (probably not on test)

Remove 4 for high fire


Remove 7 (or 8) for low fire

How many fins on a cooling coil for a MUA?

6-12 fins per inch

If the unit is a direct fire the DX coil is down stream of the burner? T/F

True, If it was upstream and there is a refrigerant leak then you are going to have issues

Dont need to know the acronyms for the BMS systems

Blah

Direct fired MUA btu/hr?

94,000-18 million

Mua temp rise?

50-100F

What are the three types of heat exchangers?

Drum and tube


Tubular


Clam shell

When should the burner on off set point?

10-20F below discharge setpoint

What is the temperature range in Celsius?

55C max temp rise

What is the discharge head of a MUA?

The outlet

Where is the evaporator on a MUA?

After the fan

2500-3200 units?

Feet Per Minute!!

High pressure is before profile plate?

Yes!

F = (C x 1.8) + 32?

Yep


Fpm = 4005 * (root (vp))