Use LEFT and RIGHT arrow keys to navigate between flashcards;
Use UP and DOWN arrow keys to flip the card;
H to show hint;
A reads text to speech;
48 Cards in this Set
- Front
- Back
Should the P28 oil failure control be mounted vertically? |
The P28 is not position sensitive |
|
Should the P28 be mounted with the dust cover off if it away from the compressor in an electrical box? |
No, keep the dust cover on |
|
Is there a P28 that is Ammonia Specific? What are some of the mounting concerns with ammonia? |
Yes. • A P28AN or P28DN control used for ammonia service must be mounted separately from the electrical cabinet. An ammonia leak could damage the electrical circuitry. • Do not use Johnson Controls/Penn Ecosafe® hose tubing in applications with ammonia or other corrosive refrigerants. Corrosion could cause tube breakage and refrigerant leakage. |
|
Describe the operation of the P28 |
When the compressor starts, the timer is energized because the net oil pressure of the system is zero. During normal operation, the net oil pressure should build up to the pressure switch's cut-out setting (scale setting) plus the switch differential (3 to 5 psi [21 to 34 kPa]) within the required time delay, causing the time delay relay to de-energize. If the net oil pressure does not rise to the cut-out pressure setting plus the switch differential within the required time delay, the time delay relay trips and stops the compressor. If the net oil pressure drops below the cut-out pressure setting during the compressor's run cycle, the time delay relay energizes. If the net oil pressure returns within the time delay, the time delay relay de-energizes and the compressor continues to operate normally. If the net oil pressure does not return within the time delay, the control shuts down and locks out the compressor. |
|
What are some basic installation warnings with the P28? |
CAUTION: Equipment damage hazard. Avoid sharp bends or kinks in the capillary or tubing to avoid damage to the capillary. • Coil and secure excess capillary or tubing. Because harmonic vibration can break the capillary or tubing, some slack must be provided. • Do not allow the capillary or tubing to rub against metal surfaces where friction can cause damage. • When using a control with 1/4 in. / 6.4 mm tubing, a pulsation damper must be used. Pulsation can cause excessive wear and damage the control. |
|
On the test how will they tell you to test the oil failure control? |
Remove compressor from the load side of the contactor and then energize the circuit. This will turn on the contactor and eventually trip the P28. |
|
What does the P28 measure? |
The P28 and P128 controls measure the net oil pressure available to circulate oil throughout a pressure-lubricated refrigeration system. The net oil pressure is the difference between the oil pressure at the pump discharge and the refrigerant pressure in the compressor crankcase.(suction) Example: If the oil pressure pump discharge reading is 90 psi (621 kPa) and the crankcase pressure is 70 psi (483 kPa), the net oil pressure is 20 psi (138 kPa). |
|
What are the contacts between 1-2 and L-M normally open or normally closed? |
Both are N/C |
|
How should you set the oil differential is the manufacturers specification is not known? |
Back (Definition) |
|
Which contacts do you jumper to test the oil failure control (according to the P28 manual)? |
Contacts 1-2 |
|
What does the wiring diagram look like? What is the opening force on the differential pressure switch? |
Back (Definition) |
|
What would happen if the heater inside the P28 failed? |
If the pump fails, the oil pressure control wouldnt work. |
|
How do you size fuse sizes?
Transformer VA: 100VA Low side voltage: 24V
P=IV (100VA)/(24V)= 4.16A Max fuse size = 4.16A x 1.25 = 5.2A (choose smaller -> 5A) |
Transformer VA: 100VA Low side voltage: 24V
|
|
How do you size fuse sizes?
Transformer VA: 100VA Low side voltage: 24V
P=IV (100VA)/(24V)= 4.16A Max fuse size = 4.16A x 1.25 = 5.2A (choose smaller -> 5A) |
Transformer VA: 100VA Low side voltage: 24V
|
|
What is a proportional signal? |
The control signal is not on/off. The signal will ask for a percentage of demand. Think of a gas pedal. |
|
What is the difference between opposed and parallel blades? |
Opposed blades work for proportional control: 50% open means 50% airflow (linear control)
Parallel don’t work for proportional control: 50% open means 90% airflow |
|
What are the two types of blade design? What are their fpm design speeds? |
Back (Definition) |
|
What installation specifications must be followed when installing a flow switch? |
TQ: Flow switch must me installed on a threaded tee or welded fitting (half coupling). |
|
Do the overloads on a motor control open contacts on the control circuit or the line voltage circuit? |
It opens the control circuit. |
|
What is a manual motor starter? |
It is used on fractional hp motor that is not internally thermally protected. Looks like a light switch but it has an overload integrated into the switch. |
|
What is direct acting, reverse acting, close on rise, open on rise, and calculate the cut-in and cut-out using a differential pressure switch |
Know it. |
|
What is the setting for O/L on a motor given no 1.15 service factor and 1.0 service factor? |
sf less than 1.15 will be 1.15 FLA (or sf is not shown) sf 1.15 equal to or greater will be 1.25 FLA |
|
TQ: what is the first thing you do when you show up on a job site? |
Listen to the customer. |
|
What happens if you burn out a heat anticipator on a thermostat? |
You will not get any heat. Heat anticipator is a “timed two position control” because the heater is a timer. Prevents overshoot
|
|
What position do economizer actuators fail to? Open or closed? |
Closed |
|
With a hot water zone valve is it close-on-rise or open-on-rise?
(The zone valve is fail open, normally open.) |
Closes-on-rise (24V applied) so the VALVE is reverse acting! Volts (up) -> temp (down) However, the thermostat for a zone valve is direct acting. As the temperature goes up the switch closes! Temp (up) -> volts (up)
Furnace is the direct acting Volts (up) -> temp (up) Furnace thermostat is reverse acting Temp (up) -> volts (down) |
|
TQ: Thermocouple open
What effect is it? |
25mV -30 mV open circuit voltage Seebeck effect |
|
What is “the hop-scotch method” to trouble shooting? |
Start at power and work your way down, past the fuse, to the damper motor, then the end switch, then the fan interlocks… etc. |
|
What do you set up first on a low pressure switch? What do you set up first on a high pressure switch? |
Low pressure switch: Cut-in (high event) and then the differential High pressure switch: Cut-out (high event) then the differential (High event) - (differential) = (low event)
|
|
When does the fan limit switch close? |
Closes at 120-140F |
|
Is the heat anticipator in series or parallel for an cooling thermostat? |
Parallel for cooling, so the heat anticipators heat up the thermostat and will turn on slightly before the room reaches the 20C. Series for heating, so the heat anticipators heat up the thermostat and will turn off slightly before the room reaches the 20C. |
|
Is a condenser fan cycling switch on the high pressure line direct acting or reverse acting? |
Pressure (up) -> voltage (up) Direct acting |
|
3% voltage unbalance? How do you calculate it? |
(Votage (furthest away from average) - Voltage(avg.) ) / voltage average |
|
How does a time-guard work? |
Call -> 15 second delay Remove call-> 4 min 45 sec delay Total 5 min |
|
Any safety devices are wired before or after the PLC? |
The safeties are wired directly into the field wiring and not into the PLC program. |
|
What does a start top station wiring diagram look like? Pump out? pump down? |
Blah
|
|
What does a pump down ladder logic diagram look like? |
Blah |
|
How many times does a pump out circuit? What does the wiring diagram look like? |
Once |
|
What does the first quiz cover? |
About 30 Questions Oil Pressure TimeGuard Anti Short Cycle Schematics Lockout relays Wiring Diagrams Electromechanical Controls Terminology Transformers Dampers Actuators Flow Switches Pressure Switches Thermostats (with and without anticipators) Humidity Control Motor Starters Overloads Relays G Contactors Design Gas Fired Equipment Heatpumps Maintenance |
|
Pump down, pump out, or solenoid drop? |
Solenoid drop Thermostat is in front of compressor on a solenoid drop |
|
Front (Term) |
Pump down Because it pumps down more than once |
|
Pump out, pump down, solenoid drop? |
Pump out |
|
A schematic diagram can be refered to as a….. |
Ladder diagram |
|
Pump out, pump down, solenoid drop? |
Pump out |
|
What is the seebeck effect? |
It is when dissimilar metals produce a voltage. Ala a thermocouple. |
|
What is the setting for a low temp cut out on an absorber? |
34F |
|
What kinda questions are on the test? |
Mostly wiring diagram, or short cycling timer, or pressure control |
|
If the lights flash and its 6pm what happens next? |
The lights will turn off in 10 minutes If you turn the lights on and off they will stay on for another 2 hours |