Can a metallic gas hose extend from one room to another or passed through any wall partition or ceiling or floor

No

When a metallic gas hose is used to connect an appliance to Ridgid Supply piping where is a shut off valve necessary

In the piping immediately Upstream of the metallic gas hose

When a gas hose is used for transferring liquid propane from one container to another what shall it be protected by

Hydrostatic relief valve located between the shutoff valves

The gas connector shall

Be protected from damage, not passed through a wall floor ceiling or partition, be connected to rigid piping or tubing located in the same area as the Appliance

Max length for a corrugated metal gas connector to connect a range fridge or clothes dryer

6 feet

Maximum length of a corrugated metal gas connector used to connect a suspended Appliance

Two feet

Maximum length of a corrugated metal gas connector when hooking up decorative Appliance, a room heater, or a direct vent wall furnace except when the appliance is installed as a free-standing unit

Two feet

Minimum diameter of pressure test gauge used when testing gas lines

3 in

By how much does the maximum range of a pressure gauge used while testing your gas piping system have to exceed the test pressure by

15% but not more than 300%

Pressure test requirement for low pressure gas lines 200 feet or less

15 psi for 15 minutes

Pressure test requirements for low pressure gas lines longer than 200 ft

15 psi for 60 minutes

Pressure test requirements for all welded pipe

The greater of 50 psi or 1.5 times the maximum operating pressure for 180 minutes

If the piping is 4 inch or larger than air has been used for testing what must happened before turning the gas on

The piping shall first be purged with carbon dioxide or nitrogen, or a mixture of these then Purge with gas

What a piping or tubing system is to be purged to the outdoors the purging line shall not terminate closer than how many feet from either a building or air intake

10 ft

How is rooftop gas piping supported

With treated wood blocks or material having at least equivalent characteristics as wood blocks and protection against outdoor exposure

Maximum support spacing for piping one in in greater on a rooftop

Same as of hanging pipe but also at every threaded fitting

Maximum support distance for piping less than one in on a rooftop

Every 4 ft

How is gas tubing supported on a rooftop

Continuously