Maximum water closets wet vented |
2 |
|
Requirements for wet venting two water closets |
They must be connected at the same level by means of a double sanitary T fitting if the pipe is vertical and by means of a Double Y if the vent pipe is horizontal |
|
When wet venting where must water closets be installed |
Downstream of all other fixtures |
|
Trap arms and fixture drains connected to a wet vent shall not exceed what size except for connections for emergency floor drains |
2 inches |
|
Do you take into consideration the hydraulic load of separately vented fixtures that drain into a wet vent when sizing a continuous vent |
No |
|
When it wet vent extends through more than one story the total discharge from anyone story above the first story shall not exceed how many fixture units |
4 |
|
Maximum nominally horizontal offset in a wet vent 2 inch or less in size |
1.2 m |
|
Maximum nominally horizontal offset in a wet vent larger than 2 in |
2.5 m |
|
Where must all fixture served by Circuit vent be located |
In the same story |
|
can a soil or waste stack be connected Upstream of a circuit vented fixture |
No |
|
When circuit venting fixtures with Outlet pipes less than 2 in in size shall |
Be separately vented or separately circuit vented |
|
Where is a relief vent connected |
To the branch that forms part of a circuit vented system and downstream of the most Downstream circuit vented fixture |
|
If a soil or waste pipe having a hydraulic load of not greater than how many fixture units is permitted to act as a relief vent for a circuit vented branch |
6 fixture units |
|
When is a symmetrically connected relief vent permitted to serve as a combined relief vent for a maximum of two branches |
When there are not more than eight circuit vented fixtures connected between the combined relief vent and each circuit vent |
|
When shell additional circuit vent be required |
Each cumulative horizontal change a 45° in a circuit vented branch or when more than eight circuit vented fixtures are connected to a branch |
|
When can a soil or waste pipe be permitted to serve as an additional circuit vent |
As long as it is sized as a wet vent and is minimum 2 in in size |
|
A circuit vented Branch shall be minimum what size wear traps less than 2 in in size are vented |
2 inch |
|
What is the minimum size a circuit vented Branch can be where it has traps 2 inch or larger butter connected to the Circuit vent |
3 in |
|
What is the minimum size of an additional circuit vent or relief vent |
One size smaller than the required size of the circuit vent but need to not be larger than 2 in |
|
When determining the size of a wet vent the hydraulic load from which fixture connected shall not be included |
The most Downstream fixture |
|
Is a continuous vent considered to be dry or wet |
Dry |
|
maximum number of fixtures that are allowed to be connected to a circuit vent or additional circuit |
Two symmetrically connected maximum six fixture units |
|
Yolk events must be installed in buildings that receive discharge from fixtures located on more than how many stories |
11 |
|
At what length, and other requirements does an offset required to offset relief vents? |
The offsets must be greater than 1.5 M long and the upper vertical portion of the stack passes through more than two stories and receives a hydraulic load of more than 100 fixture units |
|
Where are offset relief vents required to be connected |
At the highest and lowest points off the offset |
|
Minimum size of an offset relief vent |
Maybe one size smaller than the stack vent |
|
Where are yoke vents located |
Each section of five stories or parked there of counting from the top down |
|
At what height are yoke vents connected |
Not less than 1 meter above the floor of the lowest story of the section in question |
|
How shall the Yoke vent be connected to the soil or waste stack |
By means of a drainage fitting at or mediately below the lowest soil or waste pipe from the lowest story |
|
The upper end of every soil or waste stack shall terminate in a |
Stack vent |
|
Every soil or waste stack draining fixtures for more than four stories that contain Plumbing fixtures shall have a |
Vent stack |
|
A soil or waste stack that serves as a wet vent does not require a |
Vent stack |
|
Where is a vent stack connected to the vertical section of soil or waste stack |
At or immediately below the lowest soil or waste pipe connected to the soil or waste stack |
|
Fixtures are permitted to be connected to a vent stack provided that they |
Fixture unit does not exceed 8, at least one fixtures connected to a vertical portion of the vent stack and Upstream of any other fixtures, no fixtures connected to Downstream of a water closet, all fixtures are located in the lowest story served by the vent stack and the section of the vent pipe that acts as a wet vent conforms to the requirement regarding what vents |