Manifold pressure of gas flowing up to gas orfice

3.5” wc

What does venturi design of burner mean? And why is it used?

1.Becomes larger as gas air mixture heads to burner ports 2. velocity is reduced increasing pressure, is called static regain, gives it adequate pressure to burn at burner ports

What is the purpose of secondary air?

Complete combustion process, only 30-50% of air needed for combustion is supplied in primary air.

What controls amount of primary air? How is it set?

1. Primary air shutter.


2. To the btuh rating of the burner, if lessened velocity is lowered in gas orfice lowering pressure

What is partial pre-mixing?

Some of air is premixed prior to combustion process

What is a Bunsen flame?

Blue flame, due to pre mixing

What is a perfect flame? What are 2 imperfect flames?

Blue but not too blue. Too blue is an oxidizing flame. Carbonizing flame is orange and means too much fuel

What is flame lifting? And flashback?

1. Too much velocity on flame front


2. Not enough velocity

What can be caused by lifting flame?

Aldehydes and carbon monoxide

How to stop lifting flame?

Usually you can just reduce primary air.

What is cause of yellow tipping? And what can it result in?

1.Not enough primary air


2. Carbon manoxide

2 purposes of orfice

1. Regulates flow rate through burner, set to btuh or kw input rate


2. Sends flow down center line of burner mixing tube.

What should be used to clean orfice?

Broom straw, wire brush bristle

What is adjustable orfice?

Needle inside adjusts to change opening of orfice. Used on gas ranges and adjustable burners

Formula for orfice sizing.

Flow rate (cfh) = btuh input /


(1000 btuh/cf)

How much to de-rate appliance in Calgary?

4%, it is 4% for every 1000 ft above 2000ft, Calgary is at 3400ft

How far should thermocouple be into pilot flame?

3/8-1/2”

What is a pilot stat?

Also known as safety shut off valve, screws into gas valve and is connected to thermocouple it is responsible for shutting off gas if burner goes out.

What is open circuit test thermocouple?


And what is expected result

1. Det voltage output of thermocouple (20-30mV)

What is open circuit test thermocouple?

1. Det voltage output of thermocouple (20-30mV)


P. 178

What is a closed circuit test for thermocouple?


And what is expected range?

Tests that voltage is enough to hold valve in open position


10-15 mV


P.179

What is drop out test?


And expected range?

Same as closed circuit but flame turned off and allowed to de-energize 2-4 mV

What is drop out test?

Same as closed circuit but flame turned off and allowed to de-energize 2-4 mV


P.181

Flame failure response test?

Timing pilotstat to drop out placing unit in safety shut down condition. 1-1.5 min


P. 181

What is Aprox voltage of thermopile?

750 mV

In a closed circuit test. What happens if the value is really low or really high?

1. If low thermocouple needs to change, since it has high internal resistance


2. If high check pilot stat coil or power unit. Because it has high operating resistance

What is a drop out test?

Done same way as closed circuit test. Turn off pilot. Should drop at 2-4 mV

What is flame failure response test? Time?

1.Time it takes for power unit to shut down.


2. Should be about 1 minute to a max of 1.5 mins

Pilot turndown test. How long after gas valve clicks on should main burner light at max?

4 seconds

How is heating anticipator set?

By amperage drawn by the coil of the gas valve

What protects the valve coil from shorting out?

Since heating anticipator is wired in series with valve coil, it would burn out the anticipator 1st

Diaphragm gas control valves which are mostly used on residential equipment are mainly opened and closed by?

Gas pressure.

Flame failure response time for systems under 400,000 BTUs

Between 60 and 90 seconds

For ignition control module. What could create a false flame condition?

Short to ground

For a flame sensor. How much should be immersed in the burner flame?

About 1”

How does intermittent pilot system differ from DSI and HSI?

Spark ignited pilot is used to ignite flame upon each burner start up

How does intermittent pilot system differ from DSI and HSI?

Spark ignited pilot is used to ignite flame upon each burner start up

What is flame failure response time for intermittent pilot system?

0.8 seconds

How to retrofit a conventional furnace.

Automatic vent damper and automatic ignition system. This makes it a mid efficient furnace.

seasonal Efficiency of conventional furnace and water heater?

1. 45-58%


2. 30-45%

Seasonal efficiency of mid efficient furnace.

65-75%

Seasonal efficiency of non condensing high efficiency furnace.

75-85%

Why does high-efficiency condensing furnace have multiple heat exchangers?

First heat exchanger is for sensible heat. Second heat exchanger is for latent heat, when air changes to a liquid.

Because condensate from the flue gases is slightly acidic, What is the second stage heat exchanger made of.

Stainless steel

With high efficiency condensing furnaces. What can happen if vent length is exceeded?

Erratic operation and shutdown due to pressure switch tripping out.

When 636 passes through an unheated space it must be?

Insulated

636 vent termination must be 4 ft from? 2 things

Building soffit, inside corner from 2 exterior walls.

636 vent termination must be 4 ft from? 2 things

Building soffit, inside corner from 2 exterior walls.

How far must 636 vent termination be from a mechanical air supply inlet to a building?

6 ft

What side of building should vent termination be?

One that isn’t prone to prevailing winds.

How far should 636 vent termination be from building opening or supply inlet of another appliance? 2

1. 12” for furnaces 100 000 btuh or less


2. 36” for over that

How far must a 636 vent termination be from a gas meter or service regulator? A regulator vent?

1. Not directly above a gas meter or service regulator


2. At least 6 ft from a regulator vent

Spillage in a venting system is a result of what two things?

Venting system overloaded or appliance is overloaded

What 4 things can cause a venting system to be overloaded?

The appliance is overfiring, appliance venting system restricted or blocked, Venting system to small, venting system poorly designed

What two things can cause a Downdraft in a venting system?

Lack of make up air or chimney or vet location