It takes _____cuFt of Air for every cuFt of Natural Gas Burned

10

It takes _____cuft of Air for every 1 cuFt of Propane Burned

24

What is the minimum height of a air supply inlet above grade level?

12 inches (300mm)

What is the minimum size ( dimension) of an opening on a screen , louvre or grill used for air supply?

1/4 inch 6mm

What is the maximum developed length of an air supply duct allowed without increasing the size?

20 feet

What is the minimum size area for a square or rectangular duct used for air supply?

9in2 (58cm2)

What type of damper is allowable for installation on air supply duct in a dwelling unit?

Certified automatic damper

Where should an air supply duct terminate?

Next to the burner of the largest input appliance

What is required when a mechanical air supply is used ?

Must be interlocked

Using a NO.600 grille, what size grille is required to provide 69!square inches of free area?

10”X10”

An air supply grille installed in a wall between a mechanical room and the building must be what height above the floor?

Between 6” and 18”

Category I natural draft appliances ( draft good) require _______ than a Category I fan assist appliance

More

Today’s Code requirements state the air required for combustion and flu gas dilution must be ________________

Piped in through a dedicated air intake or mechanical duct system .

Which table is used for air supply requirements when all appliances have draft hoods?

8.1

Which table is used when all appliances are Fan assist?

8.2

Which table is used for a combination of draft hood appliances and fan assist appliances ?

Both.


Draft hood in 8.1


Fan Assist + Draft hood 8.2


Select largest

Clause 8.2.6.(a)!states that the air supply opening shall have a free area of not less than _______ for every _______BTU of appliance input.

1inch sq


1000

Less than ______sq” of leakage is considered tightly constructed

76

Where a water heater is installed with an input not exceeding _______ and it is the only gas appliance in the room or building, there is no need to _____________.

50


Supply air from outdoors

Combustion air openings should be located between

6” and 18” from floor level.

Where must the supply air duct from outside terminate in the mechanical room?

Within 1 foot above and 2 feet horizontally of the appliance.