Use LEFT and RIGHT arrow keys to navigate between flashcards;
Use UP and DOWN arrow keys to flip the card;
H to show hint;
A reads text to speech;
105 Cards in this Set
- Front
- Back
National Electrical Code |
NFPA 70 Pg 447 |
|
National Fire Alarm Code |
NFPA 72 Pg 447 |
|
FACP |
Fire Alarm Control Panel pg447 |
|
Responsible for processing signal detection devices and transmitting to alarms audible, visual alarms or alarm company |
Fire Alarm Control Panel Pg 447 |
|
Alarm control units are designed for both security & fire protection which takes higher priority. |
Fire Protection pg 448 |
|
Usually the building's main public electrical connection, connected at a fire detection alarm system dedicated branch circuit. |
Primary electrical Power Supply. pg 448 |
|
Engine-driven generators may be permitted as what? |
Alternative Primary Power Supply pg 448 |
|
If a generator is used what must applied? |
24 Hour Trained Operator or Engine-driven generators |
|
If the primary operating engine fails what must happen? |
Secondary generator must be designed to start automatically |
|
The secondary system must operate fire detection and alarm system once the main power supply fails. |
The secondary system must be operational within 30 seconds. |
|
Secondary Power source Option 1
|
Storage Battery and Charger |
|
Secondary Power source Option 2 |
Engine-driven generators and 4 hour capacity storage battery. |
|
Secondary Power source Option 3 |
Multiple Engine-driven generators, one must be automatic starting Pg 448 |
|
How must the trouble signal indicator be supplied power within a system? |
Trouble signal indicator must have a source of power different from the primary power source pg 448 |
|
Fire detection systems consists of what? |
Manual and Automatic Initiating devices that are activated by fire, smoke, flame, heat. Pg449 |
|
Two methods devices send signals to the FACP |
Hard wired systems & Radio wave over a special frequency to a radio receiver in the panel. Pg 449 |
|
When the alarm initiating devices activate and send signals to the FACP. The FACP does what? |
Takes appropriate action including activating audible/visual local alarms, and transmits a signal to a central station, FD telecom. Pg 450 |
|
What else may a audible & visual notification or signal indicate? |
May be used to indicate a trouble conditions in the alarm system as well as providing status of fire systems. Pg 450 |
|
What is the most common types of alarm signaling systems used for structure. |
Audible notification signaling Pg. 450 |
|
Continuously monitor the atmosphere of a building, compartment, or area. |
Automatic Alarm-Initiating devices (Detectors) Pg 451 |
|
Two important factors that inspector should know affect the performance of the audible signaling system? |
Its ability to alert & its ability to convey information. Pg 450 |
|
What happens when changes in atmosphere detect rapid rises in heat or presence smoke or flame signature |
Signal is sent to the FACP Pg 451 |
|
List the four types of automatic alarm-initiating devices? |
Heat Smoke Flame Fire Gases Pg 452 |
|
What are the two categories of heat detectors? |
Fixed Temperature Rate of Rise Pg 452 |
|
Which devices are considered the oldest still in service? |
Heat Detection Devices Pg 452 |
|
What are the heat detection devices prone not to do? |
Give False activations Pg 452 |
|
What is one drawback to heat detection devices? |
Typically the slowest type of system to activate under fire conditions Pg 452 |
|
Where must heat detectors be placed to most effective? |
Ceilings, Atriums and architecturally designed areas where is expected to accumulate. Pg 452 |
|
Uses one of the primary principles of physics can detect the presence of heat? |
-Heat Cause expansion of various material -Heat causes melting of certain material -Heated material have a thermoelectric properties that are detecable. Pg 453 |
|
What does a fusible link do within a detector/device? |
Hold detector in the open position.Pg 453 |
|
What happen once the fusible link reaches its melting point. |
It drops away releasing the spring that touches an electrical contact that completes a circuit and sounds an alarm. Pg 453 |
|
What does a frangible bulb do within a detection device? |
Hold two electrical contacts aparts. Once reaching temperature fractures contacts close competing a circuit sending an alarm. Pg 453 |
|
What uses two types of metal that have different heat expansion ratios. |
Bimetallic Heat Detector Pg 454 |
|
What type of position do Bimetallic strip come in? |
One End, Both End secured. Design of the device metal will bow completing the circuit sending alarm Pg 454 |
|
Detects conditions only at the spot where they are located. |
Pneumatic Rate of Rise Spot Pg 456 |
|
Brains of the system. Processes the devices and transmit them to local or other alarm system altering devices. |
FACP |
|
Prevalent Monitoring system, located outside the protected premises. monitored by contracted service |
Central Station Pg 472 |
|
Warns building occupants that action is needed and tells them what action to take. |
One way System Pg 473 |
|
Allows people at buildings to communicate with person at main control station with intercom or special telephone |
Two Way System Pg 473 |
|
Not required until 15 years after installed. 2 percent of detector tested. Failure additional detector must be removed and lab tested. |
Non-restorable fixed temperature system test. pg 479 |
|
What must you not use as a primary or secondary power supply? |
Dry cell Batteries. Pg 448 |
|
Pull/ one motion to activate device. |
Single Action Pull station |
|
Performs two steps lift cover and then pull to activate. |
Double Action pg 466 |
|
Visually inspect and actively test monthly to ensure all parts are working. |
Auxiliary Fire Alarm System Pg 480 |
|
Test Non-coded manual fire alarm boxes semiannually. |
Auxiliary Fire Alarm system Pg 480 |
|
Protects large commercial, industrial buildings, high rise structures, groups of commonly owned facilities. |
Proprietary Pg 471 |
|
Each building or area has its own system that is wired into a common receiving point in the facility. |
Proprietary Pg 471 |
|
Separate structure or a part of the structure is remote from any hazardous operations. |
Proprietary Pg 471 |
|
Simplest type of local alarm. Alarm signaling devices operate simultaneously. Not capable of identifying device triggered. |
Non-Coded Local Alarm Pg 468 |
|
Know the distance to respond for an infrared detector. |
1 square foot of fire from a distance of 50 feet. |
|
Heat detector that consist of one or more thermistors. |
Electronic spot type detector Pg 457 |
|
Rate at which thermistor are heated determines the amount of current generated, more heat equals alarm activation |
Electronic spot type detector |
|
Sensitivity testing should be preformed after the detector first year of service and |
Every 2 years after.
|
|
Red and white lettering |
Appearance of Manual Pull station. |
|
Principle that fire rapidly increase the temperature in a given area? |
Rate of Rise Detector
|
|
Designed to send signal when the rise in temperature exceeds 12 to 15 degrees fahrenheit. |
Rate of Rise Detector |
|
When should is a fusible link checked & replaced? |
Replace every 5 years Checked Semiannually |
|
How far should test records go back? |
5 years |
|
Dedicated telephone line between Alarm boxes, protected property, FD telecomm. |
Parallel Telephone |
|
Plays a big factor in flame detector placement. |
Environment |
|
Responds quicker to smoldering |
Photoelectric |
|
Respond quicker to flames? |
Ionization |
|
Public electricity connection that must be connected at fire detection alarm system dedicated branch circuit. |
Primary Power Supply |
|
Has its own source of power and does not depend on the municipal power. |
Local Energy system |
|
Electrically connected to an integral part of the municipal fire system and municipal power. |
Shunt System |
|
Two types of metal with different heat expansion ratios. |
bimetallic |
|
One metal expands faster than the other and causes the combined strip to arch when heated. |
Bimetallic |
|
Areas that are subject to regular temp changes at slower than those of fire. |
Rate Compensation Detector |
|
Inspection must be witnessed by the fire department. True or False |
False |
|
Who test all parts of a smoke detector? |
UL |
|
Activates a gong of bell when water begins to flow through sprinkler systems |
Water Flow Devices |
|
Notify the FACP of a change in the status of the water in the system. |
Water flow devices |
|
Fixed rate/Rate of Rise Detector |
Combination Detector |
|
heat/smoke detector |
Combination Detector |
|
Smoke/Fire gas detector |
Combination Detector |
|
Who designs fire alarm system? |
Fire Protection engineer or technical personnel |
|
Can work for a city and a private firm |
Fire Protection engineer |
|
Detects UV and Infrared Lights |
Flame Detector |
|
Auxiliary fire alarm systems are connected to what? |
A municipal city fire alarm system |
|
Receiving device such as photodiode |
Projected beam application |
|
Movement and vibration can cause the light to misalign |
Projected Beam application |
|
Light emitting diode that passes through a small chamber |
Refractory application. |
|
Multiply story building most have at least one of these? |
Manual Pull station |
|
identify the general location of a fire more quickly and accurately than noncode local alarms |
Zone annunciated alarm |
|
How fast must a secondary power supply come on line once there is power failure |
30 Seconds |
|
Alternative method to cleaning detectors other than wiping |
Vacuum cleaner |
|
Pinpoints what device caused the alarm? |
Addressable |
|
Used to supervise automatic sprinkler systems |
Tamper switch |
|
Monitor main water shutoff valve that supplies sprinkler system |
Tamper switch |
|
Monitors air pressure in dry pipe sprinkler systems |
Tamper switch |
|
What is reported if the main water shutoff valve is closed |
Trouble indication is displayed on the FACP |
|
Another name for pull stations |
Manual pull stations |
|
max total travel distance of a manual pull station |
200ft
|
|
A leased telephone line |
Remote receiving communication |
|
List detectors from fastest to slowest |
Smoke Detector Fire gas detector heat detector
|
|
Purpose of a fire alarm system. |
to alert of fire NFPA 72 |
|
on semiannual testing how many restorable heat device should be tested |
One |
|
Conductive metal inner core cable, allow small amounts of current to pass |
Tubing Type |
|
Insulated and bundled within an outer covering melts to make contact. |
Wire Type |
|
Get power locally |
Local energy Auxiliary alarm system |
|
Wall a smoke detector activate due to excessive moisture? True or false |
True |
|
manual fire alarms are tested? |
semiannually |
|
Are fixed heat detectors expensive? true of false |
False |
|
Are fixed heat detectors prone to false activation? True of False |
False |
|
Fixed Temperature heat detectors characteristics? |
Oldest in service Inexpensive Slowest to react Reliable |