• Shuffle
    Toggle On
    Toggle Off
  • Alphabetize
    Toggle On
    Toggle Off
  • Front First
    Toggle On
    Toggle Off
  • Both Sides
    Toggle On
    Toggle Off
  • Read
    Toggle On
    Toggle Off
Reading...
Front

Card Range To Study

through

image

Play button

image

Play button

image

Progress

1/105

Click to flip

Use LEFT and RIGHT arrow keys to navigate between flashcards;

Use UP and DOWN arrow keys to flip the card;

H to show hint;

A reads text to speech;

105 Cards in this Set

  • Front
  • Back

National Electrical Code

NFPA 70 Pg 447

National Fire Alarm Code

NFPA 72 Pg 447

FACP

Fire Alarm Control Panel pg447

Responsible for processing signal detection devices and transmitting to alarms audible, visual alarms or alarm company

Fire Alarm Control Panel Pg 447

Alarm control units are designed for both security & fire protection which takes higher priority.

Fire Protection pg 448

Usually the building's main public electrical connection, connected at a fire detection alarm system dedicated branch circuit.

Primary electrical Power Supply. pg 448

Engine-driven generators may be permitted as what?

Alternative Primary Power Supply pg 448

If a generator is used what must applied?

24 Hour Trained Operator


or


Engine-driven generators

If the primary operating engine fails what must happen?

Secondary generator must be designed to start automatically

The secondary system must operate fire detection and alarm system once the main power supply fails.

The secondary system must be operational within 30 seconds.

Secondary Power source Option 1


Storage Battery and Charger

Secondary Power source Option 2

Engine-driven generators and 4 hour capacity storage battery.

Secondary Power source Option 3

Multiple Engine-driven generators, one must be automatic starting Pg 448

How must the trouble signal indicator be supplied power within a system?

Trouble signal indicator must have a source of power different from the primary power source pg 448

Fire detection systems consists of what?

Manual and Automatic Initiating devices that are activated by fire, smoke, flame, heat. Pg449

Two methods devices send signals to the FACP

Hard wired systems


&


Radio wave over a special frequency to a radio receiver in the panel. Pg 449

When the alarm initiating devices activate and send signals to the FACP. The FACP does what?

Takes appropriate action including activating audible/visual local alarms, and transmits a signal to a central station, FD telecom. Pg 450

What else may a audible & visual notification or signal indicate?

May be used to indicate a trouble conditions in the alarm system as well as providing status of fire systems. Pg 450

What is the most common types of alarm signaling systems used for structure.

Audible notification signaling Pg. 450

Continuously monitor the atmosphere of a building, compartment, or area.

Automatic Alarm-Initiating devices (Detectors) Pg 451

Two important factors that inspector should know affect the performance of the audible signaling system?

Its ability to alert & its ability to convey information. Pg 450

What happens when changes in atmosphere detect rapid rises in heat or presence smoke or flame signature

Signal is sent to the FACP Pg 451

List the four types of automatic alarm-initiating devices?

Heat


Smoke


Flame


Fire Gases Pg 452

What are the two categories of heat detectors?

Fixed Temperature


Rate of Rise Pg 452

Which devices are considered the oldest still in service?

Heat Detection Devices Pg 452

What are the heat detection devices prone not to do?

Give False activations Pg 452

What is one drawback to heat detection devices?

Typically the slowest type of system to activate under fire conditions Pg 452

Where must heat detectors be placed to most effective?

Ceilings, Atriums and architecturally designed areas where is expected to accumulate. Pg 452

Uses one of the primary principles of physics can detect the presence of heat?

-Heat Cause expansion of various material


-Heat causes melting of certain material


-Heated material have a thermoelectric properties that are detecable. Pg 453

What does a fusible link do within a detector/device?

Hold detector in the open position.Pg 453

What happen once the fusible link reaches its melting point.

It drops away releasing the spring that touches an electrical contact that completes a circuit and sounds an alarm. Pg 453

What does a frangible bulb do within a detection device?

Hold two electrical contacts aparts. Once reaching temperature fractures contacts close competing a circuit sending an alarm. Pg 453

What uses two types of metal that have different heat expansion ratios.

Bimetallic Heat Detector Pg 454

What type of position do Bimetallic strip come in?

One End, Both End secured.


Design of the device metal will bow completing the circuit sending alarm Pg 454

Detects conditions only at the spot where they are located.

Pneumatic Rate of Rise Spot Pg 456

Brains of the system. Processes the devices and transmit them to local or other alarm system altering devices.

FACP

Prevalent Monitoring system, located outside the protected premises. monitored by contracted service

Central Station Pg 472

Warns building occupants that action is needed and tells them what action to take.

One way System Pg 473

Allows people at buildings to communicate with person at main control station with intercom or special telephone

Two Way System Pg 473

Not required until 15 years after installed. 2 percent of detector tested. Failure additional detector must be removed and lab tested.

Non-restorable fixed temperature system test. pg 479

What must you not use as a primary or secondary power supply?

Dry cell Batteries. Pg 448

Pull/ one motion to activate device.

Single Action Pull station

Performs two steps lift cover and then pull to activate.

Double Action pg 466

Visually inspect and actively test monthly to ensure all parts are working.

Auxiliary Fire Alarm System Pg 480

Test Non-coded manual fire alarm boxes semiannually.

Auxiliary Fire Alarm system Pg 480

Protects large commercial, industrial buildings, high rise structures, groups of commonly owned facilities.

Proprietary Pg 471

Each building or area has its own system that is wired into a common receiving point in the facility.

Proprietary Pg 471

Separate structure or a part of the structure is remote from any hazardous operations.

Proprietary Pg 471

Simplest type of local alarm. Alarm signaling devices operate simultaneously. Not capable of identifying device triggered.

Non-Coded Local Alarm Pg 468

Know the distance to respond for an infrared detector.

1 square foot of fire from a distance of 50 feet.

Heat detector that consist of one or more thermistors.

Electronic spot type detector Pg 457

Rate at which thermistor are heated determines the amount of current generated, more heat equals alarm activation

Electronic spot type detector

Sensitivity testing should be preformed after the detector first year of service and

Every 2 years after.


Red and white lettering

Appearance of Manual Pull station.

Principle that fire rapidly increase the temperature in a given area?

Rate of Rise Detector


Designed to send signal when the rise in temperature exceeds 12 to 15 degrees fahrenheit.

Rate of Rise Detector

When should is a fusible link checked & replaced?

Replace every 5 years


Checked Semiannually

How far should test records go back?

5 years

Dedicated telephone line between Alarm boxes, protected property, FD telecomm.

Parallel Telephone

Plays a big factor in flame detector placement.

Environment

Responds quicker to smoldering

Photoelectric

Respond quicker to flames?

Ionization

Public electricity connection that must be connected at fire detection alarm system dedicated branch circuit.

Primary Power Supply

Has its own source of power and does not depend on the municipal power.

Local Energy system

Electrically connected to an integral part of the municipal fire system and municipal power.

Shunt System

Two types of metal with different heat expansion ratios.

bimetallic

One metal expands faster than the other and causes the combined strip to arch when heated.

Bimetallic

Areas that are subject to regular temp changes at slower than those of fire.

Rate Compensation Detector

Inspection must be witnessed by the fire department. True or False

False

Who test all parts of a smoke detector?

UL

Activates a gong of bell when water begins to flow through sprinkler systems

Water Flow Devices

Notify the FACP of a change in the status of the water in the system.

Water flow devices

Fixed rate/Rate of Rise Detector

Combination Detector

heat/smoke detector

Combination Detector

Smoke/Fire gas detector

Combination Detector

Who designs fire alarm system?

Fire Protection engineer or technical personnel

Can work for a city and a private firm

Fire Protection engineer

Detects UV and Infrared Lights

Flame Detector

Auxiliary fire alarm systems are connected to what?

A municipal city fire alarm system

Receiving device such as photodiode

Projected beam application

Movement and vibration can cause the light to misalign

Projected Beam application

Light emitting diode that passes through a small chamber

Refractory application.

Multiply story building most have at least one of these?

Manual Pull station

identify the general location of a fire more quickly and accurately than noncode local alarms

Zone annunciated alarm

How fast must a secondary power supply come on line once there is power failure

30 Seconds

Alternative method to cleaning detectors other than wiping

Vacuum cleaner

Pinpoints what device caused the alarm?

Addressable

Used to supervise automatic sprinkler systems

Tamper switch

Monitor main water shutoff valve that supplies sprinkler system

Tamper switch

Monitors air pressure in dry pipe sprinkler systems

Tamper switch

What is reported if the main water shutoff valve is closed

Trouble indication is displayed on the FACP

Another name for pull stations

Manual pull stations

max total travel distance of a manual pull station

200ft


A leased telephone line

Remote receiving communication

List detectors from fastest to slowest

Smoke Detector


Fire gas detector


heat detector


Purpose of a fire alarm system.

to alert of fire NFPA 72

on semiannual testing how many restorable heat device should be tested

One

Conductive metal inner core cable, allow small amounts of current to pass

Tubing Type

Insulated and bundled within an outer covering melts to make contact.

Wire Type

Get power locally

Local energy Auxiliary alarm system

Wall a smoke detector activate due to excessive moisture? True or false

True

manual fire alarms are tested?

semiannually

Are fixed heat detectors expensive? true of false

False

Are fixed heat detectors prone to false activation? True of False

False

Fixed Temperature heat detectors characteristics?

Oldest in service


Inexpensive


Slowest to react


Reliable