Inline shut off valves shall be permitted to be installed to isolate or shut off piping for servicing of individual rooms or areas
T/F |
T |
|
New or replacements shut off valve shall have the operator showing when the valve is open or closed T/F |
T |
|
The shut off valve shall be accessible to other than authorized personnel to facilitate periodic testing
T/F |
F |
|
Each riser supplied from the main line shall be provided with a shut off valve in the riser adjacent to the main line TT/F |
T |
|
Regard lus of how many zone valve boxes are installed on a lateral branch off a razor, only one service vow but shall be required for each branch T/F |
T |
|
The zone valve shall not be located in a Room with station outlets/inlets that it controls, such that a wall intervenes between the valve and outlets. T/F |
T |
|
All valves accept valves zone valve Box assemblies shall be secured by any of the following means
any of the above
located in secure areas
locked or latched in their operating positions
located above ceiling, but remaining accessible and not obstructed |
Any of the above |
|
With the approval of the authority having jurisdiction, and which areas shall the shut off valve as be permitted to be secured to prevent inappropriate access? Maternity anesthetizing critical care psychiatric or pediatric |
Psychiatric or pediatric |
|
New or replacement shut off valves for medical gas pressure piping systems shall be permitted to be any type as long as they meet the following they have a minimum CV factor constructed of material suitable quarter turn to off all of the above |
All of the above |
|
Shut up valves for positive pressure gasses shall be cleaned for oxygen service by the manufacture permit in line serviceability provided with copper tube extensions for brazing all of the above |
All of the above |
|
A shut off valve shall be placed at the immediate connection of each ____ system to the distribution piping system. What is the name given to the valve? Main isolation source supply |
Source |
|
A shut off valve shall be provided in the ____ supply line when the source valve is not accessible from within the building being served. What is the name given to this valve? Zone service supply main |
Main |
|
What is the name given to the shut off valve installed on all lateral branch piping from a main or riser? Riser zone main service |
Service |
|
What valve shall be readily operable from a standing position in the corridor on the same floor they serve? Zone main service riser |
Zone |
|
Immediately outside each vital life support, critical care and anesthetizing location of moderate sedation, deep sedation, or general anesthesia there shall be located a ____ in each medical gas, or vacuum line or both. Zone valve relief valve area fire extinguisher |
Area alarm |
|
There shall be a zone valve immediately outside of anesthetizing location of ____? moderate sedation general anesthesia all or any of the above deep sedation |
All or any of the above |
|
Inline check valve shall not have threaded connections but shall have ____? in line serviceability threaded purge port brazed extensions all of the above |
All of the above |
|
Service valve shall be placed in the branch piping prior to any ____ on that branch zone valves valves for future inline valve source valve |
Zone valve |
|
What valve is permitted to be installed to isolate or shut off piping for servicing of individual rooms or areas? riser valve service valve future valve inline valve |
Inline valve |
|
The main line valve shall be located on which side of the source valve, when the main line valve enters the building upstream of the source valve facility side of the source Valve main line valve upstream of the service valve downstream of the source valve |
Facility side of the source valve |
|
A positive pressure gas valve, 1/2 inch in size minimum CV is what? 21 17 31 60 |
17 |
|
A positive pressure gas valve, 1" is size minimum CV is what? 110 31 60 58 |
60 |