Inline shut off valves shall be permitted to be installed to isolate or shut off piping for servicing of individual rooms or



True or False

True

New or replacement shut off valve shall have the operator showing when the valve is open or closed



true or false

True

The zone valve shall not be located in a Room with station outlets/inlets that it controls, such that a wall intervenes between the valve and outlets


True or false

True

All valves except valves zone valve Box assemblies shall be secured by any of the following means


A. Located in secure areas


B. Locked or latched in their operating positions


C. Located above the ceiling, but remaining accessible and not obstructed


D. Any of the above


D

With the approval of the authority having jurisdiction, in what areas shall the shut off valves be permitted to be secured to prevent inappropriate access?


A. Maternity


B.anesthesia


C. Critical care


D. Psychiatric or pediatric

D

New or replacement shut off valves for medical gas pressure piping systems shall be permitted to be any type as long as they meet the following



B. Constructed of material suitable


A. They have a minimum CV factorB. Constructed of material suitableC. Quarter turn to OffD. All of the above


B. Constructed of material suitableC. Quarter turn to OffD. All of the above


C. Quarter turn to Off


D. All of the above


D. All of the above

D

Shut off valves for positive pressure gasses Shall


A. Be clean for oxidant service by the manufacturer


B. Permit in line serviceability


C. Quarter torn top off


D. All of the above



D

A shut off valve shall be placed at the immediate connection of each _____ system to the distribution piping system. What is the name given to the valve?


A. Main


B. Isolation


C. Source


D. Supply

C