All indirect waste piping that requires an airgap shall discharge into the building drainage system through _______________.
a drainage airgap of 1 inch maximum
Except for refrigeration coils and ice-making machines, the minimum size of the indirect waste pipe shall not be smaller than the drain on the unit and not smaller than ___________ inch(es).
1
Floor drains in walk-in coolers shall discharge _______________.
to a separate drainage line discharging into an outside receptor through an airgap or airbreak
Drains, overflows, or relief pipes from a water distribution system shall be connected to the building drain by ________________.
indirect waste by means of an airgap
Stills, sterilizers, and similar equipment that produce waste shall be _________________.
indirectly connected by means of an airgap
Devices that are not regularly classified as plumbing fixtures, but which have drip or drainage outlets, shall be drained by _____________________.
indirect waste pipes discharging into an open receptor through an airgap or airbreak
No plumbing fixture that is receiving discharge from indirect waste pipes shall be installed until first approved by __________________.
Authority Having Jurisdiction
The developed length from the fixture outlet of a bar sink to the receptor shall not exceed ______________ feet.
5
All receptors receiving the discharge from indirect waste piping shall be _________________.
approved, shaped and sized to prevent splashing, and accessibly located
A standpipe for a clothes washer shall have a minimum and maximum length of ___________inches and _____________inches.
18, 30
An indirect waste receptor shall not be installed in a _________________.
toilet room
No drain, overflow, or relief vent from a water supply system, or any other discharges under pressure shall be discharged to the drainage system ______________.
by direct connection
A domestic dishwashing machine shall be connected to the drainage system by using ________________.
an approved airgap fitting
Drinking fountains may be installed with _______________.
indirect waste
Water shall not be discharged under pressure directly into the wasted system if it has a temperature of _______________ or more.
140°
Every indirect waste interceptor receiving discharge containing particles that would clog the receptor drain shall _______________.
have a readily removable beehive strainer
_______________ tube shall not be used for chemical or industrial waste, as defined in Section 811.1
PVC
Lead waste pipe that may receive discharge containing acid or corrosive chemicals, and each vent pipe connected to it, shall not be less than ____________ inch wall thickness.
3/32
Whenever practicable, all piping receiving chemical waste shall be ________________.
readily accessible
The owner shall make and keep a _______________.
permanent record of all piping and venting carrying chemical waste
No chemical waste vent shall _____________.
intersect vents for other service
No chemical waste shall be discharged without _________________.
approval of the Authority Having Jurisdiction
Water lifts, expansion tanks, cooling jackets, sprinkler systems, drip or overflow pans, and other similar devices that discharge clear wastewater into the building drainage system shall _____________________.
discharge into an indirect waste receptor
Pipes carrying wastewater from swimming or wading pools, including pool drainage, backwash from filters, and discharge from pumps, shall be ___________________.
installed as an indirect waste
Condensate waste shall discharge to the drainage system by means of a(n) ____________.
indirect waste pipe
Condensate or wastewater shall not drain over ______________.
a public way
Condensate from fuel-burning condensing appliances shall be collected and discharged ________________.
to an approved plumbing fixture or disposal area
If the trap from a sink located in a bar cannot be vented, _____________.
the drain shall discharge through an airgap or airbreak into an approved receptor that is vented
The minimum size condensate waste pipe from a 12-ton refrigeration unit is ___________inch(es).
3/4