All indirect waste piping that requires an airgap shall discharge into the building drainage system through _______________.
|
a drainage airgap of 1 inch maximum
|
|
Except for refrigeration coils and ice-making machines, the minimum size of the indirect waste pipe shall not be smaller than the drain on the unit and not smaller than ___________ inch(es).
|
1
|
|
Floor drains in walk-in coolers shall discharge _______________.
|
to a separate drainage line discharging into an outside receptor through an airgap or airbreak
|
|
Drains, overflows, or relief pipes from a water distribution system shall be connected to the building drain by ________________.
|
indirect waste by means of an airgap
|
|
Stills, sterilizers, and similar equipment that produce waste shall be _________________.
|
indirectly connected by means of an airgap
|
|
Devices that are not regularly classified as plumbing fixtures, but which have drip or drainage outlets, shall be drained by _____________________.
|
indirect waste pipes discharging into an open receptor through an airgap or airbreak
|
|
No plumbing fixture that is receiving discharge from indirect waste pipes shall be installed until first approved by __________________.
|
Authority Having Jurisdiction
|
|
The developed length from the fixture outlet of a bar sink to the receptor shall not exceed ______________ feet.
|
5
|
|
All receptors receiving the discharge from indirect waste piping shall be _________________.
|
approved, shaped and sized to prevent splashing, and accessibly located
|
|
A standpipe for a clothes washer shall have a minimum and maximum length of ___________inches and _____________inches.
|
18, 30
|
|
An indirect waste receptor shall not be installed in a _________________.
|
toilet room
|
|
No drain, overflow, or relief vent from a water supply system, or any other discharges under pressure shall be discharged to the drainage system ______________.
|
by direct connection
|
|
A domestic dishwashing machine shall be connected to the drainage system by using ________________.
|
an approved airgap fitting
|
|
Drinking fountains may be installed with _______________.
|
indirect waste
|
|
Water shall not be discharged under pressure directly into the wasted system if it has a temperature of _______________ or more.
|
140°
|
|
Every indirect waste interceptor receiving discharge containing particles that would clog the receptor drain shall _______________.
|
have a readily removable beehive strainer
|
|
_______________ tube shall not be used for chemical or industrial waste, as defined in Section 811.1
|
PVC
|
|
Lead waste pipe that may receive discharge containing acid or corrosive chemicals, and each vent pipe connected to it, shall not be less than ____________ inch wall thickness.
|
3/32
|
|
Whenever practicable, all piping receiving chemical waste shall be ________________.
|
readily accessible
|
|
The owner shall make and keep a _______________.
|
permanent record of all piping and venting carrying chemical waste
|
|
No chemical waste vent shall _____________.
|
intersect vents for other service
|
|
No chemical waste shall be discharged without _________________.
|
approval of the Authority Having Jurisdiction
|
|
Water lifts, expansion tanks, cooling jackets, sprinkler systems, drip or overflow pans, and other similar devices that discharge clear wastewater into the building drainage system shall _____________________.
|
discharge into an indirect waste receptor
|
|
Pipes carrying wastewater from swimming or wading pools, including pool drainage, backwash from filters, and discharge from pumps, shall be ___________________.
|
installed as an indirect waste
|
|
Condensate waste shall discharge to the drainage system by means of a(n) ____________.
|
indirect waste pipe
|
|
Condensate or wastewater shall not drain over ______________.
|
a public way
|
|
Condensate from fuel-burning condensing appliances shall be collected and discharged ________________.
|
to an approved plumbing fixture or disposal area
|
|
If the trap from a sink located in a bar cannot be vented, _____________.
|
the drain shall discharge through an airgap or airbreak into an approved receptor that is vented
|
|
The minimum size condensate waste pipe from a 12-ton refrigeration unit is ___________inch(es).
|
3/4
|