33 Cards in this Set

  • Front
  • Back

What are Class 0 gloves voltage limit?

1000 Volts
What is third step in meter on?
Ground jumper test
What are the 3 potentials of a wire?
Voltage, Ground, 0

What are the reasons for a 120 volt load test to fail?

1. Capacitance


2. 120 load ready to come on (breaker on)


3. 120 load in front of the main breaker


4. Phase to ground short

What are the reasons for a 240 volt load test to fail?

1. 240 volt load ready to come on


2. Phase to Phase short


3. 240 volt load wired ahead of main breaker

What are the 4 steps for Meter On testing?

* Test your tester


1. Backfeed


2. 120 volt load


3. Ground Jumper


4. 240 volt load

What do barriers seperate?

A Phase to Phase or A Phase and Ground

What is a circuit with no resistance to current flow?

A Dead Short

What is OHM's Law?

I=E/R



I=Current


E=Voltage


R=Resistance

What is the minimum volts for a read on an Elwood Tester?

80-90 volts is minimum needed to register

When must a rep. wear a face shield?

When connecting or disconnecting


1. All 4 wire services


2. All services greater than 250 volts


3. All URD services (underground)

When must a rep wear a 20 Kal jumpsuit?

When voltage is above 250 volts

On 120v nominal voltage services, readings below 110v or above 130v require what?

Immediate Disconnection of the customer's service

What is a Green fusetron fuse rated for?

30 amps

A GFI or AFCI breakers are the only breakers that would have a __________ going to them?


1. bare copper wire


2. Green bonding wire


3. Circuit neutral wire


4. Auto reset

3. A Circuit neutral wire

What would the following voltage readings indicate?


With a normal load on 120/75/195

Poor connection on low side

Your elwood tester will light across a bad cartridge fuse only if?

There is a completed circuit

When programming a sentinal meter what program is used for a TOU meter?


1. 093-demand


2. 193-demand


3. 10-TOU

10-TOU

You find backfeed while turning on an electric meter. If you cannot eliminate the backfeed what do you do?

Remove meter


Glass off channel


Notify dispatch


Contact CSS

What are the 120 volt nominal voltage limits?

114/123

With a normal load on, What would the following voltage readings indicate?


100/140/240

A poor neutral connection

A conductor at ground potential would be?

The Neutral

What is the purpose of the bare copper wire in a circuit?

To protect against a shock

A reading of 240v at the top of two cartridge fuses and a reading of zero on the bottom of the same fuses indicates?

A Blown Fuse

What would the following readings require you to do?
135/137/272
Shut customer OFF
Call Line
Check neighbors

On a meter set test you get a light on test 5. What are two possible causes?

A Phase to Phase short


A 240 volt load ready to come on


A 240 volt load wired ahead of main breaker

Name 3 causes for a light on your elwood tester during step 2 of an on test.

Phase to ground short


120 load


120 load ahead of main breaker


Capacitance

How many wires does a HQ5 have?

3 wires

How many wires does a HQ7 have?

4 wires

What is backfeed?

Voltage from another source

What size breaker should be attached to #10 wires?

30 amp

To help a customer find a short you could install a light bulb in the fuse holder. When the short is cleared what happens to the bulb?

It goes out or dims

What is the most common backfeed in apartments?

Running an extension cord from one apartment to another with 2 male ends plugged into outlets.