What are the four protected zones in a substance?

-Line Fault, Overcurrent


-Transformer Overcurrent


-Bus Diff


-Feeder Over current

What are your zone of protections Ansi #

50 Line fault Overcurrent


51 Transformer Overcurrent


87 Transformer Differentials


63 Sudden Pressure


87 Bus Differential


50/51 Feeder Overcurrent

Line fault/Overcurrent zone

High side of Transformer to other side of line.

Transformer Overcurrent Zone

Low side of Transformer to distribution, excluding BT

XFMR Differential/Sudden pressure

Transformer HS LS

Bus differential zone

LS XFMR To distribution side of BKR, includes BT

Feeder Overcurrent Zone

Trans side of BKR to Distribution