The low-pressure side of the system must not be pressurized to more than 150 psig because of
. the low-side test pressure
True or False: The high-pressure side working pressure for most systems is 700 psig.
False
The ________ is both the greatest asset and the greatest liability of an electronic leak detector.
Sensitivity
Why should oxygen or compressed air never be used to pressurize a system?
Oxy and oil will become unstable and may explode under pressure
List some of the foreign matter that may enter a refrigeration system.
Moisture, dirt, oil, nitrogen
or False: A vacuum pump can remove any type of foreign matter that enters a refrigeration system.
False
Air in a refrigeration system causes which of the following problems?
Acid buildup
Moisture
Copper plating
The only two products that should be circulating in a refrigeration system are
Refrigerant and Oil
For a technician to remove moisture from a refrigeration system using a vacuum pump, it must be in a ______ state.
Vapor
Are the best vacuum pumps one stage or two stage?
Two Stage
Name the two types of vacuum procedures used by technicians.
Deep Vacuum and triple evacuations
What can be done to get water out from under the oil level in a compressor?
Heat the compressor
When evacuating a refrigeration system that has solenoid valves, what special procedure must be followed?
The valves should be either opened manually or electrically
Name two common vacuum gages.
. Mercury manomemeter and micron gage
how many microns are in 1 mm Hg.
1000
What gas is commonly used to sweep a refrigeration system to push out any air in the system?
Nitrogen
What is the advantage of using large gage lines for evacuation?
It speeds the process
At _____ in. Hg, water boils at 60°F.
.522
When a vacuum is pulled on the water in question 18, the water vapor created for each pound of water
removed is ____ cubic feet.
1206