In an installation where appearance is the most important consideration, the most likely choice of a wiring system will be
|
Mineral insulated cable
|
|
When calculations show that the voltage drop between the supply terminals and a load will exceed 5% of the supply voltage the action to be taken is to
|
Increase the size of the cable supplying the load
|
|
To comply with I.E.E. Wiring Regulations the voltage drop on a three phase 400v motor circuit should not exceed
|
16V
|
|
Copper cored data communication cables are made up of pairs of conductors twisted along their length in order to
|
Reduce electrical interference
|
|
A component designed to disconnect a supply under full load conditions is
|
A switch
|
|
In situations where there is a risk of an explosion due to the presence of fumes and gases electrical switches and control equipment must be
|
Mounted in flameproof enclosures
|
|
Supplementary equipotential bonding is likely to be required in all
|
Bathrooms
|
|
The T.T. system of earthing is usually used in
|
Rural areas
|
|
An earthing system that can only be used in special circumstances and uses a combined neutral and earth conductor in the supply and the installation is the
|
T N-C system
|
|
Isolators used to isolate electrical supplies are designed to operate under
|
No-load conditions
|