Mercury Reduction
Injecting power activated carbon (PAC) into gas stream.
Carbon attaches itself to the mercury and reaction products collected in fabric filter
What is Lime
is slaked with water and the resulting slurry is directed to a lime slurry storage tank.
Spray Dryer Absorber (SDA)
The Spray Dryer Absorber provides the system with the means for effectively removing sulfur dioxide (SO2) from the flue gas stream by mixing a lime slurry solution with the flue gas. The reacted particulate byproduct is removed in the downstream fabric filter.
SH2 outlet temp trip
greater than 1000 F
SH2 inlet temperature trip
greater than 765 F
Drum pressure trip greater than
1500 psig
- Drum level less than
-15 inches
- Flue gas inlet temperature (on HRSG, not Crossover duct) Trip
greater than 2400 F
-Flue Gas evaporator 1 temperature trip
greater than 2200 F
Baghouse Bypass:
-Inlet gas temperature
385 F
Baghouse Bypass
Inlet gas temperature
370F for 10 minutes
-Low outlet temperature for Baghouse Trip
235F for 30 minutes
Baghouse Bypass:
Trip
Less than 5 compartments in service
Baghouse trip
Differential pressure across baghouse greater than
15” wc
Atomizers trip:
Cooling water loss for 10 minutes
What is the trip point for high cooling water temp? Randy incated a temp of 90 was a trip. Is this accurate?
-Air/lube pressure > 10 psi for 10 minutes
-Position sensor not in place at start for 1 second
Vibrations exceeds 1.5”/second
-Upper bearing temperature exceeds 210F
-Lower bearing temperature exceeds 210F
-Cooling water temperature below 60F
-Baghouse low temperature of 235F atomizers stop spraying slurry and dilution water
ID Fans: trip
- Low oil pressure of 0.5 psi
- Front & Rear motor bearings trip at 212 F.
Front & Rear fan bearings trip at 188 F.
- Fan vibration > 9 mm/sec
Mechanical Exhauster: Trip
Motor amp greater than 50.
Lime Slurry: Trip
Lime slurry storage tank low low level of 11% stops slurry flow.