• Shuffle
    Toggle On
    Toggle Off
  • Alphabetize
    Toggle On
    Toggle Off
  • Front First
    Toggle On
    Toggle Off
  • Both Sides
    Toggle On
    Toggle Off
  • Read
    Toggle On
    Toggle Off
Reading...
Front

Card Range To Study

through

image

Play button

image

Play button

image

Progress

1/75

Click to flip

Use LEFT and RIGHT arrow keys to navigate between flashcards;

Use UP and DOWN arrow keys to flip the card;

H to show hint;

A reads text to speech;

75 Cards in this Set

  • Front
  • Back

As water is heated in a boiler, the water molecules ________

Speed up

As water molecules change to steam, they ______

Expand approximately 1500-1700 times

_______Is generated in the water, flows up through the water, and disengages at the waterline

Steam

When water is heated beyond the boiling point, the water molecules ______

Change from a liquid to a gas

Internal water flow within a Weil-McLain boiler is through the _______, providing for better thermal circulation and heat transfer

Lower ports and lower portion of the upper ports

A "Wet nipple" boiler refers to the fact that water can flow _____

HAHA WET NIPPLE... classic.

Through the upper and lower port openings

As steam is generated and released from the water, it collects in the ________

Steam chest

The generation and release of steam in a boiler created a very ______ boiler waterline

Turbulent

A radiator air vent ______ when the steam contacts its heat actuated float valve

Closes

Steam ______ its heat energy as it changes to condensate

releases

When steam cools in the radiator, it ______

changes from a gas to a liquid.

As the steam cools and turns to condensate, it returns to the boiler through the ______

Return piping system

Visual aid of steam boilers and their parts

Visual aid of steam boilers and their parts

Only one f*cking side

The ___ controls the cycling of a steam boiler.

Pressure control

The pressure control is piped into the boiler through _____

the pigtail system

A pressure control with an additive differential has the following two settings.

Low and differential



If on a subtractive boiler pressure control, you set the differential at 1.5 PSI and the high setting at 2.0 PSI what would be the low (or burner on) setting?

0.5 PSI 2-1.5 = 0.5

The ____ acts just like a trap in a plumbing application and protects the pressure control from coming into direct contact with the steam.

Pigtail Syphon

The ____ gives readings of the pressure within the boiler

pressure gauge

The ____ is provided for visual inspection of the boilers operating water level.

water-column gauge glass AKA the sight glass

On or near the top of the boiler you will find a _____, used to protect the boiler from excessive pressure

Pressure relief valve

For residential cast iron steam boilers, the steam pressure relief valve is set to discharge at a maximum of ____ psi

15

The safety device that automatically shuts the boiler-burners off when the boiler water level drops below the water level control setting, is called a ______ ?

low-water cutoff

All ____ boilers are required by code to have a low-water cutoff

Steam

The ____ type low-water cutoff requires frequent "blow-down" (or flushing) to rid its sediment that can collect in its chamber

float

The piping directly around the boiler is known as near boiler piping and should ______ be replaced when installing a replacement steam boiler.

Always

The supply piping risers coming out of the boiler should be ______

sized per manufacturers instructions

All supply tappings coming out of the boiler are found ______

on or near the top of the boiler.

When piping multiple risers from a boiler into a common header, swing joints are used to _____

accommodate the expansion and contraction of the piping and the boiler

In sizing the header, the pipe must be sized _____

Specifically per manufacturers instructions

When installing the boilers header, you must allow a minimum of ____ between the boiler waterline and the header centerline.

24 inches

Always ____ the vertical drop into the equalizer pipe

reduce the header after

The ______ allows condensate to return immediately to the boiler and keeps the water from being pushed back through the return piping as the steam pressure increases.

Equalizer line

When installing a Hartford Loop on a residential steam boiler, the short nipple should be installed in the Tee in the equalizer line.....




And for commercial?

2 inches below the waterline for rezzy




4 inches below the waterline for commercial

In piping multiple system take-off risers, it is recommended that they are piped out of the header ____

between the equalizer and the closest boiler riser to the equalizer

Installing a bullhead tee in the piping is an excellent way of eliminating water hammer.




True or false.

It is by far the absolute most retarded way to eliminate water hammer... It only causes it.




Therefore the answer is FALSE

Check valves are _____ an acceptable replacement to Hartford Loop piping

Never an acceptable method

The cold water fill pipe should be connected _____ (There are 3 blanks)

1) Below the waterline


2) Into the condensate return piping


3) As far from the boiler as possible.

For a basic one-pipe steam system, the proper pitch for the system main should be a minimum of ____, from where the main begins to where it drops into the wet return.

1 inch per 20 feet

The _____ rapidly expels air out of the system main

Quick vent

The proper placement of a quick vent is ____

15 inches from the end of the main

The length of the radiator riser, from the main to the radiator should be at least _____

3 feet



The radiator riser is connected to the radiator through _____ which is fully opened to control the flow of steam into the radiator.

a supply valve

The radiator air vent _____ when steam enters it, thus keeping the steam in the radiator.

closes

_____ air vents allow you to adjust the speed at which the air escapes from the radiator.

Adjustable

Balancing the system means that _____

by using adjustable air vents you can control the speed of steam arriving at individual radiators.

The system main can carry both steam and condensate in the same direction at the same time. True or false.

True.

The _____ is that portion of the return main located above the boiler water level.

Dry return.

The _____ is always completely filled with water.

Wet return.

"Dimension A" refers to _____ (There are three blanks)

1) The pressure drop of the system.


2) The static head of the system.


3) A safety factor in the system.

For a steam system under 100,000 BTUs there should be a minimum dimension of _____ from the vertical drop of the dry return to the boiler waterline.




And what is it for over 100,000 BTUs

18 Inches for under 100M BTU


28 inches for over 100M BTU

Steam and condensate flow in the same direction in _____ steam piping systems

One-pipe parallel flow

In _____ steam piping systems the condensate and steam flow in opposite directions

One-pipe counter flow

A one pipe counter-flow steam piping system requires the system main to be pitched _____

1 inch per 10 feet

A _____ steam piping system carries steam and condensate in separate pipes

Two-way

The _____ located at the end of the radiator in a two-pipe steam system discharges air and condensate from the radiator.

Thermostatic trap

Two-pipe steam systems use _____ on the radiators rather than air vents.

Traps

A _____ allows both air and condensate to be quickly discharged directly out of the system main.

Float and thermostatic trap

Newer steam boilers are designed to steam at full capacity _____ before the low-water cutoff shuts off the boiler.

For ten to fifteen minutes.

If a water feeder is used to increase steaming time, it may cause _____ of the boiler.

Flooding

The _____ can be used to provide additional water fro the boiler to help increase steaming time.

Reservoir pipe

If the condensate is too slow in returning to the boiler causing the low-water cutoff to cycle off too quickly, this may indicate that _____

There is an obstruction in the piping system.

All steam piping systems include at least a _____ (3 blanks)

1) System riser and system main


2) Radiator riser with swing joints


3) Condensate return piping system.

Every _____ steam boiler should be skimmed. (3 blanks)

1) New


2) Existing


3) Replacement

If a steam boiler is not cleaned, _____ may occur. (3 blanks)

1) Loss of efficiency


2) Erratic operation


3)Surging

Oil, grease, or other foreign matter floating on the boiler water surface _____ the proper operation and steaming of the boiler.

Can severely affect

When skimming the boiler, you should raise the water to _____ of the skim tapping

The center

One good method that you can use to observe the water level when skimming a boiler is to _____

Install a tee in the skim piping.

During the skimming process the boiler water temperature should be _____

Just below steaming

A typical skimming of a steam boiler may take _____ to complete

Several hours

After skimming, the boiler should be filled with fresh water and steamed for _____ to eliminate dissolved gases from the make-up water.

15 minutes



Boiler chemicals should _____ in a steam boiler.

Only be used if necessary

If skimming doesn't clean the boiler, it is acceptable to use _____ , soaking for 20-30 minutes in the boiler until its water has a pH of 7.0 to 8.5 (3 blanks)

1) Trisodium phosphate


2) Sodium hydroxide


3) Sodium carbonate

When using one of the recommended boiler chemical cleaners, it is a good practice to steam the boiler so that the chemicals will clean the whole piping system. True or false?

False.

Many steam boiler service calls can be solved by simple _____ the boiler.

Skimming and flushing.