1. If Makeup Screen House (MUSH) battery room exhaust fan (0VH02CA) tripped due to an overload condition, what would be the status of the room ventilation?
Answer: The battery room exhaust fan would auto start to prevent buildup of hydrogen in the room.
2. List three conditions that would prevent ESW room supply from starting.
Answer: Low room temperature, fan motor control power fuses are "blown," or fan motor thermal overloads are tripped.
1. Area Temperature Monitoring ensures ESW Pump House temperature is maintained =119(F. Why is this necessary?
Answer: Ensures safety-related equipment is not subjected to conditions greater than their environmental qualification temperatures, to prevent degradation and loss of operability.
1. What is the main function of the Site Ventilation Systems?
Ans.: To maintain a suitable atmosphere for personnel and equipment.
2. What auto starts the ESW Pump Room supply Fan?
Ans.: Start of the associated ESW pump.
3. What will prevent the ESW Pump Room Supply Fan from starting?
Ans.: Low room temperature Fan motor control power fuses are "blown" Fan motor thermal overloads are tripped.
4. It is wintertime and a SI has occurred. Is there anything that must be done concerning the ESW pump room ventilation?
Ans.: Yes. The heaters are load shed in a SI and not reloaded. Thus operator actions must reinstate heating.