List the parameters used by the SGWLC Program to generate a signal in the Feedwater Pump Speed Control System.
|
Feed Header Pressure, Steam Header Pressure, Total Steam Flow, and No-load setpoint.
|
|
What parameters are the Main Feedwater Pump Speed Control System programmed to maintain a differential pressure between?
|
Steam Header and Main Feedwater Header.
|
|
During normal operation at power, what would a sudden steam flow/feed flow mismatch on one steam generator most likely be an indication of?
|
A failure of a single Main Feedwater Regulating Valve controller.
|
|
During normal operation at power, what would a sudden steam flow/feed flow mismatch on all steam generators most likely be an indication of?
|
A load rejection or a MFP Master Controller failure.
|