• Shuffle
    Toggle On
    Toggle Off
  • Alphabetize
    Toggle On
    Toggle Off
  • Front First
    Toggle On
    Toggle Off
  • Both Sides
    Toggle On
    Toggle Off
  • Read
    Toggle On
    Toggle Off
Reading...
Front

Card Range To Study

through

image

Play button

image

Play button

image

Progress

1/99

Click to flip

Use LEFT and RIGHT arrow keys to navigate between flashcards;

Use UP and DOWN arrow keys to flip the card;

H to show hint;

A reads text to speech;

99 Cards in this Set

  • Front
  • Back
The plant is operating at 100% power, with all systems and controls in normal alignment. A Small Break LOCA occurs.What is the Reactor trip setpoint and coincidence as RCS pressure decreases? A. 1940 psig on three of four instruments, get one protection train, and one reactor trip breaker.B. 1970 psig on two of four instruments, get both protection trains, and both reactor trip breakers.C. 1940 psig on two of four instruments, get both protection trains, and both reactor trip breakers.D. 1970 psig on three of four instruments, get one protection train, and one reactor trip breaker.
C
What is the C-9 setpoint and logic coincidence? A. <4.0" HgA on 2/2 pressure switchesB. <5.0" HgA on 2/2 pressure switchesC. <5.0 "HgA on 1/2 pressure switchesD. <4.0" HgA on 1/2 pressure switches
B
The plant is at 100% power when a Tavg circuit fails low (after the Th/Tc averaging). Procedure guidance places the Tavg circuit in "DEFEAT" for the affected loop.What is the adverse consequence if this action is NOT performed? A. Steam dump P-12 interlock prematurely secures steam dumps.B. C-16 prevents using the "Load Decrease Rate circuit".C. Cold overpressure protection circuit sets the pressure setpoint too low.D. Feedwater isolation occurs prematurely with a P-4.
B
The following conditions exist:A plant startup is in progress, the RCS is currently at 4500F and 1800 psig. The reactor operator raises Reactor Coolant System (RCS) pressure to 2235 psig to perform post-maintenance testing on a Pressurizer Power Operated relief valve.Which one of the following explains the response of the Engineered Safety Features (ESF) for this event? A. SIS and MSLIS actuate on low pressurizer pressure when P-11 energizes.B. SIS actuates on low pressurizer pressure and MSLIS will not actuate.C. SIS will not actuate, but MSLIS actuates on low steam line pressure.D. SIS and MSLIS actuate on low steam line pressure when P-11 de-energizes.
D
Which one of the following signals resets only by depressing the FWIS RESET switch? A. Low Tavg with P-4B. AFASC. Low-Low steam generator levelD. P-14, High-High steam generator level
A
Which one of the following uses P-4 as an input to actuate Engineered Safety Features Actuation (ESFAS)? A. Feedwater IsolationB. Steamline IsolationC. Containment Spray ActuationD. Auxiliary Feedwater Actuation
A
What trip is directly associated with the P-8 permissive? A. Turbine tripB. Pressurizer high pressureC. RCP undervoltageD. Loss of flow on Two loops
D
At 100% power, NIS channel N41 failed high. All required bistables were tripped as required by Technical Specifications. An ECCS pump failure now requires a T/S shutdown. During this reduction the RO reports readings on the NI channels are:N42 - 7% N43 - 14% N44 - 6%What actions should be taken? A. Trip the reactor and have I & C place the P-10 permissive in a non-tripped (Light Off) condition.B. Have I & C place the P-10 permissive in the tripped (Light On) condition then trip the reactor.C. Bypass N41 and continue power reduction.D. Remove control power fuses from the N43 power range drawer and have I & C trip associated bistables.
A
Assume S/G level has been restored to 50% narrow range with Auxiliary Feed Water flow. What manipulations would be required to reopen the FWIVs following a P-14 turbine/reactor trip? A. Recharge hydraulic accumulators.B. Close reactor trip breakers.C. Reset SI.D. At both MSFIS Cabinets reset each FWIV (using Operate Switches).
D
The plant is at 100% power when the controlling channel for "A" Steam Generator (S/G) level control fails to 0%.With no operator action, what is the plant response? A. Reactor trip on S/G Lo-Lo Level.B. Feedwater flow to S/G "A" will initially increase, then decrease causing S/G level to stabilize at a level higher than program.C. Reactor trip on P-14 turbine trip.D. Feedwater flow to S/G "A" will initially decrease, then increase causing S/G level to stabilize at a level lower than program.
C
At 100% power the controlling S/G level channel on S/G "A" fails to 100%.With no operator action, what is the plant response? A. Feedwater flow to S/G "A" will initially increase, then decrease causing S/G level to stabilize at a level higher than program.B. Reactor trip on P-14 turbine trip.C. Reactor trip on S/G Lo-Lo Level.D. Feedwater flow to S/G "A" will initially decrease, than increase causing S/G level to stabilize at a level lower than program.
C
What protective function is NOT common between PZR Pressure Channels PT-455 and PT-458? A. P-11B. OTdeltaTC. Low pressure reactor tripD. High pressure reactor trip
A
Main Steam Line Isolation will occur if: A. 1/3 pressures < 615 psig in 2/4 main steam linesB. 2/3 High Containment pressures > 3.5 psigC. 2/3 pressure rates > setpoint in 1/4 main steam lines if low steam line pressure isolation has been blocked below P-11D. 1/3 pressure rates > setpoint in 2/4 main steam lines if low steam line pressure isolation has been blocked below P-11
C
Wolf Creek is operating at 95% RTP when the Feedwater Regulating Valve, AE FCV-530, fails to the full open position and the BOP operator is unable to close the valve.Which of the following statements accurately describes the signal which actually generates the Reactor Trip? A. The trip of the Main Feedwater Pumps on S/G #3 high level generates a reactor trip.B. The Main Turbine trip from the high level in S/G #3 generates the reactor trip.C. 78% level in S/G #3 generates the reactor trip.D. The FWIS generated on the high level in S/G #3 causes a low level in the other S/G's to generate a reactor trip.
B
What reactor trip CANNOT be blocked by an interlock or permissive? A. Pressurizer Low PressureB. Power Range Hi Neutron Flux RateC. Pressurizer High LevelD. Turbine Trip
B
At 100% power the controlling S/G level channel on S/G "A" fails to 100%.With no operator action, what is the plant response? A. Reactor trip on P-14 turbine trip.B. Feedwater flow to S/G "A" will initially decrease, than increase causing S/G level to stabilize at a level lower than program.C. Reactor trip on S/G Lo-Lo Level.D. Feedwater flow to S/G "A" will initially increase, then decrease causing S/G level to stabilize at a level higher than program.
C
The plant is at 4% RTP performing a startup. Intermediate range channel N-36 fails high.How does this failure affect the startup? A. Startup may continue if the channel is bypassed within 6 hours.B. Power must be reduced <6% or increased >10% within 24 hours.C. Power must be reduced <P-6 within 24 hours.D. The reactor will trip.
D
How are the Reactor Trip Breaker trip coils affected by a MANUAL Reactor trip switch? A. Shunt coils are energized directly from NK, the UV coils remain energizedB. UV coils are de-energized, the shunt coils are energized from NNC. Under-voltage coils are de-energized; the shunt coils are energized from NKD. UV coils and shunt coils all de-energize
C
Plant parameters are sensed by various process instruments which provide an output to the Reactor Protection System. What component is between the analog signal and the RPS? A. Slave RelayB. BistableC. Master RelayD. Digital Controller
B
The plant is operating at 100% power, with all systems and controls in normal alignment. A Small Break LOCA occurs.What is the Reactor trip setpoint and coincidence as RCS pressure decreases? A. 1940 psig on two of four instruments, get both protection trains, and both reactor trip breakers.B. 1970 psig on three of four instruments, get one protection train, and one reactor trip breaker.C. 1970 psig on two of four instruments, get both protection trains, and both reactor trip breakers.D. 1940 psig on three of four instruments, get one protection train, and one reactor trip breaker.
A
Which term is an input in the calculations of BOTH the OT?T and OP?T calculations? A. RCS Lead-Lag TavgB. RCS Temperature rateC. Pressurizer PressureD. Delta I
D
Which accident is the Intermediate Range High Flux Trip designed to protect the plant against? A. Startup AccidentB. Single Rod Drop AccidentC. Over-power AccidentD. Multiple Rod Ejection Accident
A
Which Reactor Protection System trip is designed to prevent the effects of a Rod Ejection Accident? A. Power Range, Neutron Flux Low SetpointB. Overpower ?T TripC. Power Range, Neutron Flux, High Positive RateD. Overtemperature ?T Trip
C
> A. Pressurizer Low Pressure TripB. RCP Undervoltage TripC. Overtemperature deltaT TripD. Intermediate Range High Flux Trip
D
At what value does P-6 change states during a reactor startup? A. 5X105 cpsB. 5X10-10 AmpsC. 105 cpsD. 10-10 Amps
D
Which describes the setpoint and coincidence for a change in state of P-9? A. 50% Reactor Power; 2/4 Power Range ChannelsB. 48% Reactor Power; 2/4 Power Range ChannelsC. 50% Turbine Power; 1/2 Impulse PressureD. 48% Turbine Power; 2/2 Impulse Pressure
A
Which of the following describes the setpoint and coincidence for the state change of P-10 during plant startup? A. 10% current equivalent on 1/2 Intermediate Range ChannelsB. 10% Power on 3/4 Power Range ChannelsC. 10% Power on 2/4 Power Range ChannelsD. 25% current equivalent on 1/2 Intermediate Range Channels
C
Which of the following is NOT associated with P-10? A. De-energizes Source Range high voltageB. Allows blocking of the Power Range high flux low setpoint Reactor TripC. Allows blocking of IR hi flux Reactor Trip and Rod Stop (C-1)D. Provides an input to P-13
D
Reactor Protection System interlocks are separated into two basic groups or categories. What are they? A. Protective and ControlB. Protective and ProcessC. Permissive and ControlD. Process and Control
D
When a P-4 permissive is generated signals are provided to ESFAS components.When is a P-4 permissive considered complete? A. Either bypass breaker open and any reactor trip breaker closedB. Both reactor trip breakers openC. All reactor trip and bypass breakers openD. Any reactor trip breaker or bypass breaker open
C
What is the plant response once a P-4 permissive is received? A. Arms Steam Dumps in the PLANT TRIP Mode.B. Causes a Reactor trip when the Turbine trips.C. Allows the operator to Block an automatic SIS immediately after a Reactor Trip.D. Generates a CISA if Low TAVG is present.
A
What is the purpose of the P-6 permissive? A. Allows bypassing Source Range high flux trips during reactor startup.B. Causes a Turbine trip when the reactor trips.C. Automatically enables Pressurizer Pressure - Low Reactor Trip.D. Prevents a Reactor Trip below 48% due to a single Reactor Coolant Loop Loss of Flow.
A
What signal will initiate the P-6 permissive? A. 2/4 Power Range channels > 48%B. Source Range channel > 105 cpsC. 2/4 Power Range channels > 10%D. Intermediate Range channel > 10-10 amps
D
The P-7 permissive is actuated by input from which other permissive? A. P-11B. P-10C. P-12D. P-9
B
What function does the P-8 permissive accomplish? A. Arms the Steam Dump upon a Load Rejection.B. Prevents a single loop RCS Low Flow Reactor Trip at <48% Reactor Power.C. Enables a Reactor Trip on Turbine Trip at > 50% Reactor Power.D. Generates a FWIS if TAVG is < 564 degrees.
B
What function does the P-9 permissive accomplish? A. Arms the Steam Dump upon a Load Rejection.B. Generates a FWIS if TAVG is < 564 degrees.C. Prevents a single loop RCS Low Flow Reactor Trip at < 48% Reactor Power.D. Enables a Reactor Trip on a Turbine Trip at >50% Reactor power.
D
The P-10 permissive provides key functions within the Reactor Protection system. What other permissive does P-10 provide input to? A. P-13B. P-11C. P-6D. P-7
D
What is the function of the P-11 permissive? A. Allows manual block of the low Pzr Press Reactor Trip.B. Allows manual block of the low Pzr Press Safety Injection Actuation.C. Replaces the low steam-line pressure steam line isolation with a high steam pressure Reactor Trip.D. Replaces the high steam pressure rate steam-line isolation with a low steam-line pressure steam line isolation.
B
What logic and setpoint actuates the P-12 permissive? A. 2/3 Pressurizer Pressure Bistables < 1970 psigB. 1/2 Intermediate Range Channels > 1E-10 ampsC. 2/4 TAVG instruments > 550 ?FD. 2/4 NIS Power channels > 10%
C
What actions occur following the receipt of a P-14 permissive? A. Turbine Trip, MSLIS, CISAB. Turbine Trip, Trip of both Main Feed Pumps, FWISC. Trip of both Main Feed Pumps, FWIS, MSLISD. Reactor Trip, Turbine Trip, SGBSIS
B
What is the function of the C-7 interlock? A. Blocks automatic and manual control rod withdrawal.B. Prevents automatic rod withdrawal with power < 15%.C. Blocks automatic withdrawal of control bank "D".D. Arms the steam dump upon a load rejection.
D
What will actuate the C-1 Interlock? A. Low auctioneered TAVG < 553?FB. 3% less than the variable OPDT setpointC. 1/2 Intermediate channels > 20% powerD. 1/4 Power Range channels > 103% power
C
Given the following: Reactor Power is 13% SG A level is 77% SG B level is 82% SG C level is 76% SG D level is 75%Which one of the following lists AUTOMATIC actions that should directly result from the above situation? A. No auto action should occurB. Turbine trip, Feedwater isolation, Feed Pumps tripC. Turbine trip, Reactor trip, Feed Pumps tripD. Reactor trip, Feedwater isolation, Feed Pumps trip
B
> A. steam dump logicB. safety injection logicC. control rod drive logicD. feedwater isolation logic
C
The plant was operating at 51% power when a reactor trip occurred due to a loss of "B" RCP. The plant responded in the following manner:* Tavg decreased to 560?F* The Main Turbine did not automatically trip* Feedwater isolation did not immediately occurThe above mentioned plant response to the reactor trip suggests that a failure occurred in which permissive circuit? A. P-8B. P-9C. P-14D. P-4
D
The following plant conditions exist:* Beginning of life (BOL)* Reactor Power is at 100% with rod control in AUTOMATIC* Control Bank "D" is at 218 steps* A failure in rod control causes rods to step OUT Which rod control interlock is the FIRST to stop outward rod movement assuming NO Operator action? A. Power Range Rod Stop (C-2)B. Overtemperature ?T Rod Stop (C-3)C. Overpower ?T Rod Stop (C-4)D. Control Bank "D" Position Rod Stop (C-11)
D
A plant shutdown from 50% power is in progress when Intermediate Range Channel SENI36 fails HIGH.Power Range NIs currently indicate:* SENI41 9%* SENI42 10%* SENI43 11%* SENI44 11%What is the plant response to this failure? A. The reactor will NOT immediately trip, but will trip when the Intermediate Range Trip is reinstated when power decreases below the P-10 setpoint.B. The reactor will immediately trip on IR High Flux and Source Range Trip will NOT reinstate automatically when SENI35 decreases below the P-6 setpoint.C. The reactor will immediately trip on IR High Flux and Source Range Trip will reinstate automatically when SENI35 decreases below the P-6 setpoint.D. The reactor will NOT immediately trip, but will trip when the Source Range Trip is reinstated when power decreases below the P-6 setpoint.
A
The reactor is operating at 100% with all systems in a normal lineup with control rods in manual.What is the effect on the OT?T setpoint for channel II if Power Range Channel 42 lower detector fails to zero? A. Becomes InvalidB. DecreasesC. IncreasesD. No Change
B
Reactor Power has been reduced to 8% from 50% due to problems with the main turbine and feedwater systems.Which Reactor Protection System function has now been automatically re-enabled? A. All Reactor Trips associated with P-7.B. Source Range High Flux Reactor Trip.C. Intermediate Range High Flux Reactor Trip.D. Overpower Differential Temperature Trip (OP?T).
C
With the plant in Mode 3, the Main Control Board Handswitch for the Reactor Trip Breakers is rotated to the CLOSE position.Which of the following conditions would prevent the Reactor Trip Breakers from closing? A. Pressurizer Level at 17%B. Pressurizer Pressure at 1870 psigC. Pressurizer Level at 95%D. Pressurizer Pressure at 2400 psig
D
The reactor is operating at 100% with all systems in a normal lineup with control rods in manual.What is the effect on the OT?T setpoints if Reactor Power is decreased to 50% with normal pressure and temperature? A. IncreasesB. DecreasesC. No ChangeD. Increases, then decreases
A
With the plant at full power, Reactor Trip Breaker "B" is mechanically inoperable at 0800 on Monday. Reactor Trip Breaker "A" was determined to be operable.At what time would the plant be required to be in Mode 3? A. 1500 WednesdayB. 1500 MondayC. 1600 MondayD. 1400 Wednesday
B
The unit is operating at 100% RTP following a refueling outage.After several months operation in Mode 1, the following was determined:* STS IC-726B, 7300 PROCESS RESPONSE TIME TEST (2/3 LOGIC) CYCLE B, was last performed 41 months ago.* STS IC-726C, 7300 PROCESS RESPONSE TIME TEST (2/3 LOGIC) CYCLE C, was last performed 23 months ago* STS IC-726A, 7300 PROCESS RESPONSE TIME TEST (2/3 LOGIC) CYCLE A, was last performed 5 months agoAssuming each of these procedures satisfy only SR 3.3.1.16, for Function 10, Reactor Coolant Flow - Low, then what actions must be taken? A. Perform STS IC-726B within the next 18 months.B. Immediately enter LCO 3.0.3 because Technical Specifications have been violated.C. Perform STS IC-726B within the next 13 months.D. Enter SR 3.0.3 and perform STS IC-726B within the next 24 hours.
C
The unit is in Mode 3. S/G "A" Narrow Range Water Level - Low Low instrument (Channel 4) is declared inoperable at 0400. At 0600, the inoperable channel is placed in trip.Is entry into Mode 2 permitted with the inoperable S/G "A" Narrow Range Water Level - Low Low instrument? A. No. There are no exceptions to LCO 3.0.4 noted in the applicable Technical Specifications.B. Yes. Once the unit is in Mode 2 the only Action is to continue efforts to restore compliance with TS 3.3.2 LCO statement.C. Yes. Once the unit is in Mode 2 the Actions of TS 3.3.1 must also be entered.D. No. LCO 3.0.4 requires all channels be OPERABLE prior to entering the Mode of Applicability.
C
With bypass breaker A (BYA) in the closed position, and both normal reactor trip breakers (RTA and RTB) in the closed position, which one of the following will generate a reactor trip? A. RTA opens up (by itself)B. RTB opens up (by itself)C. BYA opens up (by itself)D. None of the above, a reactor trip requires at least two breakers open to generate a reactor trip
B
Which of the following Control Rod Stops requires only one channel to exceed its setpoint to stop all control rod withdrawl? A. Power Range High FluxB. Overpower delta TC. Overtemperature delta TD. Both A and B
A
Wolf Creek is operating at 95% RTP when the Feedwater Regulating Valve, AE FCV-530, fails to the full open position and the BOP operator is unable to close the valve.Which of the following statements accurately describes the signal which actually generates the Reactor Trip? A. The FWIS generated on the high level in S/G #3 causes a low level in the other S/G's to generate a reactor trip.B. 78% level in S/G #3 generates the reactor trip.C. The Main Turbine trip from the high level in S/G #3 generates the reactor trip.D. The trip of the Main Feedwater Pumps on S/G #3 high level generates a reactor trip.
C
The plant experienced a refueling outage and is ready to return to service. The P-8 permissive has been satisfied.Which one of the following would be the expected color of the window seen on the reactor partial trip status permissive/block indicating panel for the permissive? A. GreenB. WhiteC. YellowD. Red
A
Which of the following correctly describes the C-7 interlock and its relationship to the Steam Dump System? A. It arms the steam dump valves on a turbine load rejection.B. Receives inputs from P-10 and P-13 protective circuits.C. Stops further turbine loading by closing the control valves.D. Enabled by 2 RCS loop Tavg channels <550 degrees F.
A
The following conditions exist:A plant startup is in progress, the RCS is currently at 4500F and 1800 psig. The reactor operator raises Reactor Coolant System (RCS) pressure to 2235 psig to perform post-maintenance testing on a Pressurizer Power Operated relief valve.Which one of the following explains the response of the Engineered Safety Features (ESF) for this event? A. SIS actuates on low pressurizer pressure and MSLIS will not actuate.B. SIS and MSLIS actuate on low steam line pressure when P-11 de-energizes.C. SIS and MSLIS actuate on low pressurizer pressure when P-11 energizes.D. SIS will not actuate, but MSLIS actuates on low steam line pressure.
B
Which indication would alert the operator to the "under compensation" of one intermediate range channel? A. P-6 does not energize following a reactor trip.B. P-6 does not energize following a reactor startup.C. P-6 energizes much sooner than expected following a reactor startup.D. P-6 energizes much sooner than expected following a reactor trip.
C
What is the C-9 setpoint and logic coincidence? A. <4.0" HgA on 2/2 pressure switchesB. <5.0" HgA on 2/2 pressure switchesC. <5.0 "HgA on 1/2 pressure switchesD. <4.0" HgA on 1/2 pressure switches
B
Power Range Neutron Flux High Setpoint
109% power with a 2/4 coincidence) provides protection against an over-power condition.
Power Range Neutron Flux Low Setpoint
25% power with a 2/4 conincidence protects against a startup accident
Power Range Neutron Flux High Positive Rate
power range detectors experience a power increase equivalent to 4% in 2 seconds.
Power Range, Neutron Flux, High Negative Rate
power decrease of 4% in 2 seconds. This protects against multiple rod drop accidents, DNB, and localized peaking
Intermediate Range High Flux Trip
initiates at an ion current value equivalent to 25% full power. Protects against startup accident. The IR trips may be bypassed when the P-10 permissive at 10 percent.
Source Range High Flux Trip
Trip occurs at 10^5 cps. This trip is bypassed when the P-6 permissive at 10^-10 amps, derived from the IR channels is met.
OTDT
prevents DNB. Primary Coolant Temperature, pressurizer pressure, and axial flux are used to determine a DT that corresponds to reactor power and compared to the COLR
OPDT
protects against overpower conditions. Not credited in SA
Pressurizer Pressure Low
Initiates at 1940 psig protects against DNB. It is automatically bypassed below 10 percent power by the P-7 interlock.
Pressurizer Pressure High Trip
2385 psig protects against overpressure.
Pressurizer Water Level High Trip
Initiates at 92% level. This signal is blockwd when power is less than the P-7 setpoint.
Reactor Coolant Low Flow Trips
Protect against DNB following a loss of flow, senses RCP bus undervoltage. RCP bus underfrequency, or Measured Flow in the Reactor Coolant Piping. Blocked by P-7 less than 10% power.
UnderVoltage RCP
10578 Volts AC is the trip setpoint and is blocked below P-7
Under-frequency RCP trip
Setpoint of 57.2 Hz. Blocked below P-7
RCS flow low Trip
Setpoint is flow less than 90 percent of normal flow. Trips the reactor if flow is greater than P-8 (48 percent) and flow is lost in any loop.
SG water level low trip
Trip setpoint is 23.5% NR
Turbine Trip on Reactor Trip
trip as a result of a mismatch between turbine and reactor power. This trip will only initiate if above P-9 (50% power).
SI Reactor Trip
A reactor trip with SI occurs either by manual initiation, Containment High pressure (3.5 psig), Pressurizer Low pressure (1940 psig), or Low Steam Line Pressure (615 psig)
P-4
occurs when reactor trip breaker and bypass breaker are open. Causes a turbine trip, MFWIS if Tavg is low (564F), Allows blocking SIS for 60 seconds, and arms steam dumps.
P-6
bypasses the source Range High flux trip at 10^-10 amps
P-7
Upon increasing power, enables trips for Pressurizer pressure low trip, Pressurizer Water level High trip, reactor coolant flow low trip, undervoltage RCPs trip, or underfrequency RCPs. (Reactor trip and Turbine load must be less than 10% power.), It blocks the two loop flow, RCP Bus Undervoltage, RCP Bus Under-frequency, High Pressurizer Water Level, Low Pressurizer Pressure when below P-7
P-8
prevents a reactor trip from occuring below 48% power with a loss of flow in one loop.
P-9
enables reactor trip on turbine trip when power is greater than 50% reactor power.
P-10
allows manual block/automatic reinstatement of IR High flux trip, C-1 rod step, low setpoint power range trip and backup to P-6 SR cutout
P-11
blocks low pressurizer pressure safety injection SI and allows blocking the low steam. P greater than 1970 psig
P-12
automatically blocks steam dump system Tavg less than 550F
P-13
when turbine pressure is greater than 10 percent power, all the reactor trips associated with P-7 are automatically unblocked.
P-14
protects turbine from moisture carryover. Setpoint is >78% NR high high level. When it occurs turbine trip and FWIS.
C-1
High Neutron Flux Rod Stop blocks automatic and manual rod withdrawal. When IR channels > 20% power.
C-2
Overpower Rod Stop blocks automatic and manual control rod withdrawal when channels exceed 103% power.
C-3
decreases turbine load at an average rate of 10%/min when the OTDT setpoint is 3 percent below the variable OTDT reactor trip setpoint
C-4
Same as C-3 except the variable is OPDT
C-5
prevents automatic rod withdrawal when power is less than 15 percent power
C-7
arms steam dumps on a load rejection when turbine load is reduced by greater than 10 percent step or 5 percent per minute ramp
C-9
arms the steam dumps to the condenser
C-11
Prevents misalignment of rod position counters by blocking automatic withdrawal of control bank D when control bank D position is at 232 steps
C-16
stop turbine loading and defeat remote dispatching. Setpoint Tavg < 553F or Tavg 20F lower than Tref.