What is PAB Ventilation credited for post accident?

PAB ventilation is credited for heat removal only, augmented quality for releases to the vent stack.


What is the power supply to W-23, SSB Supply Fan?


-


What interlocks are associated with W-23?


-


What protective devices are provided for W-23?


W-23 powered from PP-35, controlled from 1C04R.


-


Starting W-23 SSB Supply Fan, starts W-22 (B21) exhaust fan.


-


W-23 has a freeze stat if pre-heater temp drops to <35F.

What is the power supply to W-29 SSB A/C Fan?


-


What interlocks are associated with W-29?


-


What protective devices are provided for W-29?


W-29 is powered from B-21, controlled from 1C04R.


-


To start W-29, must have W-27 Exhaust Fan running.


Starting W-29 auto starts W-26 and W-24 Exhaust Fans


-


Trips on freeze stat if preheater temp <35F.

What is the power supply to W-27A/B, HP Exhaust Fans?


-


What interlocks are associated with W-27?


W-27A/B HP Exhaust Fans powered from B-21.


-


W-21 PAB Exhaust Stack Fan must be running to start W-27A/B.

What is the power supply to W-35 PAB Supply Fan?


-


What interlocks are associated with W-35?


-


What protective devices are provided for W-35?


W-35 PAB Supply Fan is powered from 1B-31, controlled from 1C04R. Maintains temperature via thermostat near the PAB Zurn.


-W-32 PAB Exhaust Fan and W-30A/B PAB Filter Fans must be running to start W-35.


-


W-35 has a freeze stat if pre-heater temp drops to <35F, and will trip if heating steam condensate return temp drops to <200F.

What is the power supply to W-30A/B PAB Filter Fans?


-


What interlocks are associated with W-30A/B?


-


What protective devices are provided for W-30A/B?


W-30A and B are powered form 1B-42 and 2B-32, controlled from 1C04R.


-


Interlocked with W-21A/B PAB Exhaust Stack Fans, respective W-21 must be running to start W30.


-


Normal flow is through a F-29 with a roughing and a HEAPA filter. Hi Rad on RE-214 will auto swap the filters F-23, with a roughing, HEPA, and a charcoal filter.


What is the power supply to W-32 PAB Exhaust Fan?


-


What interlocks are associated with W-32?


W-32 PAB Exhaust Fan is powered from B-33


-


W-32 is interlocked with W-21A/B Exhaust Stack Fans, W-32 will not start unless a W-21 fan is running.


Interlocked with W-35, W-32 must be running to start W-35.


What is the power supply for W-21A/B PAB Exhaust Stack Fans?


-


What fans will be lost if the operating W-21 fan trips?


W-21A/B PAB Exhaust Stack Fans are powered from 1B-42 and 2B-32, controlled from 1C04R.


-


If W-21A/B trips, the following will trip:


- W-30A/B PAB Exhaust Filter Fans


- W-35 PAB Supply Fan


- W-27A/B HP Exhaust Fans


- W-32 PAB Exhaust Fan


- W-23 SSB Supply Fan


- W-29 SSB A/C Fan


What is the power supply to W-67, RHR area cooling unit?


-


How is W-67 started?

W-67 - B-43 - Local Off-Auto-On switch.


-


W-67 starts based on low duct pressure in the supply ducting for the area.


What is the power supply for W-68, SI and Spray Pump Area Cooler?


-


What auto starts this unit?


W-68 Spray and Si Cooler is powered from B-43, local Off-Auto-On control switch.


-


Runs based on SI and Spray Pump room temperature.

What will cause a Aux Building Stack or Filter Flow Low alarm on C01?

Low flow on a running W-30A/B will cause the Aux Building Stack or Filter Flow Low alarm on C01.

What is the power supply to W-47 Drumming Area Supply Fan?


-


What interlocks are associated with W-47?


-


What protective devices are provided for W-47?


W-47 Drumming Area Supply Fan - B-33


-


W-47 shares a control switch and is interlocked with W-36A/B, all start at the same time, W-36A/B trip will trip W-47.


-


Freeze stat will trip W-47 if preheater temp is <35F, and will trip if heating steam condensate return temp is <200F.

What interlock is associated with W-33A/B SFP Surface Fans?

W-33A/B will not start unless drumming area ventilation is ruinning (W-47 & W-36A/B).


What is the power supply to W-88 LDGS Bldg Vent Fan?


-


What is the flow path for BDE Bldg Ventilation?


-


What protective functions are provided for W-88?


W-88 BDE Ventilation Fan is powered from B-45.


-


Draws a suction from the PAB, and returns to the PAB.


-


Trips on freeze stat if preheater temp is <35F


What is the power supply for LDGS Building ventilation?


-


How are the LDGS Building Ventilation Fans Started?


LDGS Ventilation is powered from and controlled on B-46.


-


Start the LDGS Bldg exhaust Fan, and the Supply fan will start.


What alarms are associated with LDGS Building Ventilation?


-


What actions are required for these alarms?


LDGS Ventilation has a low flow alarm and a High D/P alarm on the LDGS Pane.


RE-224 monitors LDGS Building Ventilation and will alarm on PPCS / SS.


-


If a high alarm is received on RE-224 LDGS Building Ventilation Monitor, the ARB directs shifting the building exhaust to the Unit 2 Purge Exhaust Filters.


What is the power supply to W-85.86 PAB Battery and Inverter Room fans?


-


What is the normal flow path for PAB Battery and Inverter Room Ventilation, and what is the cooling medium?


W-85 powered form 2B-32


W-86 powered from 2B-42


-


Suction is from Unit 2 TH and the rooms exhaust to U-2TH. Cooling units are cooled by SW.


How are the PAB Battery and Inverter Room Fans normally operated?


-


What temperature are we trying to maintain in the PAB Battery and Inverter Rooms?


Normally W-85 or W-86 are operated with one in slow, the other in Auto. In high lake temperature conditions, both fans may be run in slow.


-


Maintaining the Battery Pilot Cell temperatures between 69F and 85F.


What will happen to W-85 and 86 PAB Battery and Inverter Room Fans on a low flow condition?


-


On an SI?


The fan selected to Auto will start in the speed selected if a low flow condition exists.


-


W-85 and 86 will shift to slow speed if there is a Safety Injection and the Normal 4160V feeder to their respective bus is open for diesel loading concerns, reset locally.

What time dependent operator action is associated with PAB Ventilation?

PAB ventilation must be restored within 30 minutes of establishing containment sump Recirc.

What are the inputs to the White / Yellow Bus Ventilation Trouble?


- Standby Fan Running


- Low Air Flow


- High Room Temperature