Which RCS loop does the Letdown Line tap off?

Loop B Tc


What will auto close RC-427, Letdown Isolation Valve?


-


What is the power supply for RC-427?


-


What will happen if RC-427 loses power?


RC-427 auto closes at 12% in the Pressurizer


-


Powered from 1(2)B-42


-


When RC-427 loses power or leaves its open seat the Letdown Orifice Isolation Valves CV-200A, B, and C will go shut.

What will auto close CV-200A,B, and C Letdown Orifice Outlet Isolation Valves?


- RC-427 Leaving its open seat


- RC-427 Losing power


- Securing the final charging pump


- Closing CV-371 or 371A, Letdown Containment Isolation Valves


What is the purpose of CV-203 Relief Valve?


-


What is its setpoint?


-


Where does it relieve to?


CV-203 protects the low pressure section of CVCS Letdown, and RHR.


-


Set for 600 psig, capacity of 160 gpm (full letdown flow)


-


Relieves to the PRT.

What is the purpose of the delay loop in the letdown line?

Allows for the decay of N-16 gammas. @ 40gpm will give a 67 sec time delay.


What is the purpose of CV-133, RHR to Letdown Control valve?


-


RH-703 RHR to Letdown cross connect?


Allows for the initial pressurization of the RHR system.


-


RH-703 allows RHR to use CV-203 relief valve for overpressure protection.

What is the purpose of CV-369A RHR to Letdown Cross Connect valve?

CV-369A allows purification with CVCS demins when on RHR.


How is the NRHX temperature controlled?


-


What is the fail position of the control valve?


-


How are the ill effects of this failure minimized?


NRHX temperature is controlled by CC-130, NRHX TCV.


-


CC-130 fails open on a loss of control air.


-


CC-130 is gagged to prevent it from going full open. Limits flow to 685 gpm.


What is the purpose of CV-135 Letdown Line PCV?


-


What is the fail position of this valve?

CV-135 maintains letdown line pressure downstream of the letdown orifices and upstream of CV-135 at 250 psig. Also is used to maintain RCS pressure when solid.


What is the purpose of CV-209, Low Pressure Letdown Relief Valve?


-


What is the capacity of this valve?


-


Where does it relieve to?


CV-209 Relieves at 200# on Low Pressure Letdown.


-


Capacity is 160 gpm, maximum letdown flow.


-


Relieves to VCT.


What is the purpose of CV-145, Letdown Temperature Divert Valve?


-


What is the setpoint?


CV-145, Letdown Temperature Divert Valve directs letdown line flow around the demineralizers and to the VCT on high letdown line temperature. Protects Demin resin.


-


Setpoint is 145F.


What is the purpose of the Reactor Coolant Filter?


-


When do the filters need replacing?


Reactor Coolant Filter removes resin fines from the CVCS water after it leaves the demins.
-


Replace at 20 psid.

What is the minimum VCT pressure for RCP operation? What does this pressure provide?

Minimum pressure in the VCT for RCP operation is 15 psig. This maintains adequate backpressure on the #2 RCP seal.


What processes send water to the VCT via the common return header?


-


How is this line introduced to the VCT?


Excess Letdown, sample Returns, and relief valves send water to the common return header to the VCT.


-


Enters under the water line to prevent steam from entering the VCT without being condensed.


What is the primary use of the HUTs where CVCS is concerned?


-


Which tank is aligned to which Unit?


The CVCS HUT's receive water diverted from the VCT by CV-112A.


-


Unit 1 is aligned to T-8C, Unit 2 is to T-8A.

What is the interlock associated with CV-112C, VCT Outlet Valve?

CV-112B, RWST to Charging Pump Suction must be off its shut seat to allow CV-112C to close.

What is the design flowrate of the CVCS Charging Pumps?

Charging Pumps are designed for 60 gpm flow.


What trips are associated with the CVCS Charging Pumps?


-


How is the instrumentation distributed between pumps?


-


How would the pumps be affected by a trip signal on 1 set of sensors?


Charging pumps have a low suction pressure trip @12" Hg with an 8 sec time delay.


-


Each pump has its own instrumentation.


-


Only the affected pump will be tripped by a low suction pressure signal on one set of instruments.

What alarms are provided by the Charging Pump VFD's?


- Hi Speed @ 1740 rpm (max 1900, trip at 2000)


- Low Speed @ 527 rpm (min is 480)


- High Frequency


- Overcurrent


- Undervoltage


- High Motor Temp (Local Amber Light)

What are the normal and alternate power supplies to the CVCS Charging Pumps?


1P-2A 1B-03 Normal B-08 Alternate


1P-2B 1B-03 Normal 2B-03 Alternate


1P-2C 1B-04 Normal


2P-2A 2B-03 Normal B-09 Alternate


2P-2B 2B-03 Normal 1B-03 Alternate


2P-2C 2B-04 Normal


How does the Charging Pump Control Switch work from Pullout to pump running?


-


Is there an alternate way to accomplish this?


Taking the control switch for a charging pump from Pullout to Auto gives you indication (green light. Taking the control switch to start will close the main breaker and power the VFD, starting a 6.5 sec warm up. Taking the switch to start a second time (after the 6.5 sec warm up) will start the pump.


-


Holding the switch in start for 6.5 sec will cause the VFD to warm up and the Charging Pump to start.

What is the soft start feature of the VFD?

Regardless of controller manual potentiometer output the charging pump will start at minimum, and then will slowly ramp up to the designated output.

How is a charging pump started if using the alternate power supply breaker?

The charging pump breaker is controlled from the alternate control switch, opposite unit C-04 or B-08/09, and the pump is controlled from the normal switch and controller.


What is the purpose of CV-142 Charging Line Flow Control Valve?


-


How does this valve fail?


CV-142 controls backpressure on the charging line, forcing flow to the RCP seals.


-


CV-142 fails open.


Where do the charging pump relief valves relieve to.


-


What is their setpoint?


Charging Pum[p Discharge Relief valves relieve to the charging pump suction.


-


Set for 2735 psig.

What flow is represented by F-128, Charging Line Flow?

Only charging line flow is represented on F-128, Seal Injection Flow is indicated outside PW 1 & in Pipeway 4.


What RCS loop does the Normal Charging Line penetrate?


-


How is the charging line connected to the RCS?


Normal charging is sent to A Tc vi CV-1298, Charging Line MOV.


-


Connected to the RCS via a thermal sleeve.

What is the purpose of the Seal Injection Filters?

Seal Injection Filters remove all particulate from the seal injection lines protecting the RCP seals.


What is the purpose of the seal return MOV's CV-270A and B?


-


What alarms are associated with the seal returns?


Seal return MOV's isolate seal returns from the VCT.


-


High Seal Return Flow @ 4.6 gpm


Low Seal Return Flow @ 0.9 gpm


High seal return temperature @190F


What is the purpose of CV-314, Seal Return Relief Valve?


-


What is its setpoint?


-


What is the capacity of CV-314?


CV-314 lifts to maintain seal return flow / direct it to the PRT.


-


Lifts at 150#.


-


Capable of passing 2 RCP seal return flows and XSLD.


Where does Excess Letdown tap off of the RCS?


-


What happens to Excess Letdown on a CI?


-


If this occurs, what action is required?


Excess Letdown comes from Loop A Tc.


-


CC-769 closes on a containment isolation, taking away cooling to the XSLD Heat Exchanger.


-


Manual action is required to isolate excess letdown if this occurs.

What functions are provided by VCT Level Channel L-112, and what are their setpoints?
78% - CV-112A Divert full flow to the HUT
70% - High Level Alarm Reset
70% - CV-112A Resets to VCT
28% - Auto Makeup Stops
17% - Auto Makeup Starts
4% - CV-112B Auto Opens to Makeup from RWST (Also requires 4% on L-141)
What functions are provided by VCT Level Channel L-141, and what are their setpoints?

78% - High Level Alarm


56% - Modulate for CV-112A


8% - Low Level Alarm


4% - CV-112B Auto Opens to Makeup from RWST (Also requires 4% on L-112)