Receptacle outlets in dwelling units shall be installed so that no point along floor line in any wall space is more than ____

1800

Recep outlets shall not be counted as part unless located within _____mm from wall

450

Receptacle outlets at each space that is ____ mm or wider

300

Recep shall be installed so that no point in wall line is more than ____mm

1800

Recep shall be located but not more than ____ above counter top

500

Hallways of ____mm shall have atleast 1 recep

3000

Show windows 1 recep shall be installed for each ____ lineal meters

3.6

Recep for appliance shall be installed ____ within the intended location

1800

Outlets for heavy duty shall have minimum of ____VA per outlet

600

Signage and lighting shall be computed at minimum of ____VA per branch circuit

1200

Guest room and hotel shall have not exceed ____V nominal between conductors for lighting fixtures

230

Electrocution by accident can be prevented by installing ____

GFCI

Branch circuit larger than ____A shall supply only non lighting loads

50

The min size for lighting branch circuit conductors shall be ____ mm2

2

For branch circuit supplying loads consisting of motor operation utilization equipment that is fastened in place babd that has a motor larger than 1/8 hp in combination with other loads, the total computed load shall be based on ____ percent of the largest motor load plus the sum of the other loads

125

For 600V nominal or leas open individual conductors shall not be smaller than ____mm2 copper

8

For over 600V nominal, open conductors shall not be smaller than ____mm2 copper

14

Service drop and service lateral conductors shall not be smaller than ____mm2 copper

8

Service drop conductors shall have a minimum vertical clearance of ____mm for sidewalks

3000

The pt of attachment of the service drop conductors to a building shall not be less than ____mm above finished grade

3000

Service drop conductors shall not be less than ____mm over driveways

3600

For installations to supply only limited loads of single branch ckt, the service disconnecting means shall have rating not less than ____A

30

For family single dwelling, disconnecting means shall have a rating of not less than ____A 3 wire

60

Plug fuses shall be permitted to be used in ckts not exceeding ____V line to line

250

A fuse is a ____ device

1phase protective

Factors for fuse rating for protection

-voltage


-branch current


-ampacity of branch cond

Reason to connect metal enclosures for electrical grounding system

Current path continuity

Ground ring specs

-depth not less than 750mm


-consists at least 6000mm cond


-not less than 30mm2

Electeodes of rods of iron or steel shall be at least ____mm diameter

16

Plate electrodes shall be installed not less than ____ mm below earth surface

750

Minimun size of grounding electrode conductor

8mm²

At least ____ of free conductor measured from the point in the box where it emerges from its raceway shall be left from its outlet.

150mm

Temporary lighting power and lighting installations shall be permitted for a period of ____ days of christmas lighting

90

In open wiring on insulators ____mm2 or larger conductors supported on solid knobs shall be securely tied by tie wires

8

Open wiring insulator shall be separated at least ____mm from metal and any exposed signalling conductors

50

Maximum number of quarter bend in one run

3

Radius of bending shall not be less than ____ times diameter of cable

5

Busways shall be securely supported at intervals not exceeding ____mm

1500

Receptacle outlet shall be installed within ____mm of outside edge of basin

900

Fixture never to be installed near closet

Surface mounted incandescent

Data processing system conductor ampacity shall have ____ % of total load

130

Minimum ampacity for window type AC with 8A rated current

20

Min ampacity for AC with 12A rated current

1.25*12= 15A

Hermetic compressor multiplier

1.15* rated current

Continuous duty of secondary of wound rotor minimum ampacity

125% of FL

Disconnecting means for motor circuits 600v or less shall have at least ____% of FL ampacity

115

Maximum overload protection of motor compressor

140% of FL current

Fire resistance of transformer vaults shall last at least ____

1 hour

Minimum ampacity of capacitor circuit conductor

135% of Rated current

____ hazardous location contain flammable gas or combustible vapor

Class I

____ hazardous location contains combustible dust

Class II

____ location containing ignitable fibers

Class III

Bank,office lighting VA

28

Dwelling unit lighting VA

24

Hosp club hotel restaurants lighting VA

16

Large rooms lighting VA

12

Assembly hall, churches lighting VA

8

Hallways lighting VA

4

Continuous Load

3 hours

Location subject to saturation with water

Wet location

Maximum number of disconnect for service mains

6

SPUG

Small Power Utilities Group

Static friction is ____ dynamic friction

Greater than

Max number of conductors permitted in wireway at any cross section signal circuit not included

30

SOLR

Supplier of Last Resort

Grounding conductor larger than ____ shall be identified by a continuous white or gray or by white stripes other than green

14mm2

Branch circuits shal be rated in accordance to ____ or setting of overcurrent device

Max permitted ampere rating

3phase 4wire system shall be used to supply ____ to suppress harmonic neutral current

Nonlinear

Voltage shall not exceed 600 volts on branch circuits supplying only ballasts for electric discharge lamps in tunnels not less than ____mm

5500

Allowable efficient voltage drop

3%

Nominal supply voltage for residential

230VAC

Lighting load for specified occupancies , the floor area for each floor shall be calculated ____ from the building

Outside

Vertical clearance above roof level shall be maintained not less than ____mm in all directions from roof edge

900

If the allowable ampacity is not available, the next higher should be chosen provided that the current does not exceed ____amp

800

Enclosures for overcurrent devices shall be mounted on ____ position

Vertical

Fuse rated ____ volts shall be permitted or be used for voltages at or lower than them

600

Not to be grounded

Electrically operated cranes

For service entrance of phase conductors larger than 500mm2 or 850mm2 aluminum, the required grounding shall not be sized less than ____% of the largest

12.5%

Grounding impedance shall be installed between

Grounded eletctrode and system neutral

Rod and pipe electrodes shall not be less than____ length

2400mm

The minimum level for ground service conductors shall be ____volts

600

Boxes shall be durably marked by the manufacturers with their volume of ____ or less

1650cm3

____ is a space in the hoistway, intended to be accessed with or without bodily entry, that contains the elevator controller

Control space

Spectral distribution that fluctuates with time

Flicker

Indicative plan for expansion of power generation

Power Development Plan (PDP)

Boxes and fittings shall be ____ in class III division I location

Dustight

Live parts exposed in switchboard shall not be less than ____mm

760

Grounding electrode connection that is encased in concrete or or directly buried shall

Not required to be accessible

Wire size for swimming pools

8mm

____ switches shall be used for capacitor switching

Group operated

Connection devices or fittings must not connect grounding conductors to equipment by means of

Solder

Not included in PDC

Ensure distribution system to be operated by one distribution company

All wires shall be protected by an approved electrical conduit including ____ conductor

Grounding

Maximum distance between receptacle outlets

3.6m

In the left hand rule, point finger always represent

Magnetic field

In dwelling, the minimum mounting height of outlet above bath tab is ____mm.

900

What is the rule for disconnection means of a motor is near to the motow protected

Installation Rule

For hermetic motor, what rule is the disconnecting means is 115% of the full load current?

Wiring design Rule

Is the total duration of sustained customer power interruption within a goven period divided by the total number of customer served within the same period.

SAIDI

What is the use of differential relay in relay in power Transformer?

Detect internal faults

A conducting connection, whether intentional or accidental between an electrical circuit or equipment and the earth or to some conducting body that serves in place of the earth.

Ground

Refers to the condition when the loading of trasmission lines or substation equipment or between 90 percent ang 100 percent of the continuous rating.

Critical loading

In philippine grid code, large generator has an aggregate capacity in excess of ____MW

20MW

Long duration voltage variation is a variation of the rms value of the value of the voltage from nominal voltage for a time greater than____

1 min

The maximum voltage unbalance factor for zero and negative sequence os _____% diring normal operating condition.

1 %

The grid shall be considered at normal state when the frequency is within limits of ____ and ____.

59.7Hz & 60.3Hz

Short duration voltage variation of the rms value of the voltage from its nominal value for a time greater that _____ of the power frequency but not exceeding one minute.

1/2cycle

Premises wiring shall not be electrically connected to supply system unless it contains

A grounded conductor

A grounded conductor of a mineral insulated, metal sheathed cable shall be identified at the time of installation by ____ markin at its termination

Distinctive

Grounded conductor larger than 14mm2 shall be identified by ____ at its termination

White or gray

Which of the following is not a standard classification for a branch circuit supplying several loads

25

Multiwire branch circuit shall supply only _____

Line to neutral loads

The feeder conductor ampacity shall not be less than that of the service entrance conductors with ampacity of ____ or less

55A

Voltage drop on both feeders and branch circuit to the farthest outlet shall not exceed

5%

Allowble voltage drop from farthest outlet to the lighting panel

3%

Allowable voltage drop from MDP to farthest outlet

2%

Where computations in a fraction of an ampere that is less than ____, such fractions can be dropped

0.5

Open conductors on insulators shall be covered when they are within ____mm from building

3000

Power conductors shall maintain distance of ____mm from communication conductors

750mm

Overcurrent devices shall not be located near easily ignitable material such as

Closets

Fuses or circuit breakers shall be connected in ____ with each ungrounded conductor

Series

Single phase 3 wire , the ___ conductor is to be grounded

Neutral

Main bonding jumper and system bonding jumper shall be a ____ material

Corrossion resistant

A metal underground pipe in direct contact with earth for ____mm or more can be used as ground

3000

Conductor ____mm or larger shall be stranded

8.00

___mm or larger shall be permitted to be connected in parallel

50

Generating plant isolated from rest of the grid but capable of maintaning stable power

Island grid

Has exclusive franchise to operate distribution system

Distribution utility

Where installed in two or more raceways, the size of the grounded in each raceway shall not be smaller than ____

50mm²

A ground ring encircling the building or structure, in direct contact with the earth, consisting of at least 6000mm bare copper not smaller than

30mm²

Bonding jumper from grounding electrodes shall be permitted to be connected to an aluminum or copper not less than

6mm x 50mm

Minimum size of copper bonding jumper for a service raceway containing 100mm² is

22mm²

For multi grounded neutral system, the maximum distance between any two adjacent electrodes shall not be more than ____ meters

400

Grounding conductors not an integral part of a cable assembly shall not be smaller than ____ mm² copper

14

Size of wire for pools

8.0mm²

Ground ring in direct contact in the earth shall not be smaller than ___mm²

30

Example of a system permitted to be grounded is a corner-grounded____ transformer connection

Delta

A run of flexible metal conduit may be used as an equipment grounding conductor if the circuit overcurrent device is

20A or less

The neutral conductor shall be sufficient ampacity but not less than ____% of phase conductors

33

Type use service entrance may have a ____ concentric conductor applied and not required an outer overall covering

Bare copper

Connected to ground without inserting any resistor

Grounded solidly

In rigid metal wiring conduit, the minimum electrical trade size is:

15mm

Conductors must have a clearance from windows, porches, fire escapes of not less than

1000mm

Ground ring

6000mm length


300mm²

Bonding jumper

6mm x 50mm

Minimum bonding jumper for 100mm² THHN aluminum

22mm²

Maximum distance between two adjacent ground electrodes

400

Hardness

Boron


Chromium


Nickel

Chromium in alloying

Corrosion resistance

Manganese

Brittleness and hardness

Molybdenum in alloying

High temperature strength and hardness

Nickel in alloying

Toughness, hardness, reduce thermal expansion, corrosion resistance

Silicon in alloying

Strength, spring steel strength, improve magnetic properties

Sulfur in alloying

Brittleness and machinability

In construction steel, chromium is used as

Hardener

Ingot iron has maximum of 0.15% total impurities

True

Group of Air-hardened

Group A

Group of steel for cold working

Group D

Group of hot work steel

Group H

Equipment grounding conductor of a branch circuit shall be identified by color

Green