What does hertz mean? What do our generators run at? |
Hertz = cycles per second. 3600 rpms or 60 cycles per second. |
|
Why do we use H2 in our generators instead of air? |
Hydrogen is lighter and more efficient at transferring heat than air. |
|
What is the explosive range of H2? |
5% - 75% H2 in air. |
|
What H2 pressure do we maintain in 100 / 200? |
22 - 25 psi |
|
What H2 pressure do we maintain in 300? |
25 - 28 psi |
|
What is CO2 used for on the generators? |
To purge the generators and evacuate any air or H2 to prevent the creation of an explosive atmosphere. |
|
When purging from H2 to air explain the gasses used and what goes in top or bottom. Also from air to H2. |
CO2 in bottom, air on top. CO2 in bottom H2 on top. |
|
What should be done in the event of a low purity in the generator? |
Vent H2 from the bottom and replace with fresh H2. |
|
When unsynchronized, what will happen as the speed is raised on the turbine? |
The frequency will go up. |
|
What is the 300 generator H2 safety set at? |
50 psi |
|
What is the purpose of the H2 system excess flow valve? |
It's designed to go closed in the event of a leak. |
|
What is the low pressure alarm set at? |
30 psi |
|
What type of tools should be used when working on H2? |
Non ferrous tools only. |
|
What does a liquid level alarm indicate? |
Liquid in the generator. |
|
What is the rated MW capacity of 100/200 generator? |
85 MW |
|
What is the rated MW capacity of 300 generator? |
120 MW |
|
What is the H2 high pressure alarm set at? |
60 psi |