Transformers
2 Main 22KV to ___ |
230 KV
|
|
Transformers
3 station |
A / B = 22 KV to 13.8KV
c = 22 KV to 4160 |
|
Transformers
4 Reserve |
E/F 230 kv to 13.8
C/D = 230 kv to 4160 |
|
4 Reserve trandformers
D/F for outsides located ____ |
SW Turbine Building
|
|
P=
|
13.8 kv
|
|
N=
|
4160 V
|
|
J
|
480 V
|
|
H =
|
MCC (480)
|
|
D/C
4 outside all ___ V except intake structure which is ___ V |
125 / 48
|
|
Bat Hazards
|
acid
leads Hydrogen |
|
CWS pumps
|
4 (25%) 4160 V
|
|
CWS Valves
|
closed at start
trip 110 seconds and not 95%open |
|
CWS TRIPS
|
110 sec, 95% open
undervoltage overcurrent |
|
CWS need s what
|
2 inlets / outlets on H20 box of condenser
|
|
2 pumps
cool pump shaft and bearings does not run if not running on a pump, condensation Autostart trip |
BCS
|
|
VPS
how many pumps and when do they start |
1 pump 2 eductors
pump starts when eductors are 10% open |
|
11 A powers
|
BCS A
VPS |
|
11B powers
|
BCS B
|
|
CWS cooling fan trips
|
overcurrent
undervoltage high vibration (10 sec) |
|
Strainer goes to __
|
FLume
|
|
NSW
how many pumps |
3
|
|
NSW pump trips?
|
undervoltage
low suction low suction pressure 5PSI , 2 of 3 for 45 sec |
|
What powers the NSW pumps?
|
NNS-SWG 2 A/B
|
|
SWC how many pumps?
|
3 (50%)
|
|
SWC autostarts?
|
pump trip
low psig |
|
SWC how many heat exchangers / type?
|
8 / plate frame
|
|
SWC cooling fans, how many ? trips?
|
5 (480v)
overcurrent undervoltage low-low oil hi - hi vib cell inlet MOV closed |
|
12 & 13 riser bypass
|
12 is AUTO
13 is MANUAL |
|
MWS pumps?
|
2 NNS 3A / 3B
|
|
MWS pump trips
|
Discharge valve not open in 120 seconds
NOOOOOO AUTO START!!!! |
|
MWS well water pumps do what?
|
fill tank, cool MW pump bearing and seals and VPS
|
|
Clarifiers supplies water to what two systems?
|
Flume or SWC basin
|
|
Justin likes ____
|
men
|
|
NSW pump autostarts at ___
|
97 psi
|