- Front
- Back
WT2
|
Specs: 208+-2 F
High coolant temp Yes Alarm S16 |
|
WT1
|
217+-2 F
High coolant temp Yes all S17 |
|
OT2
|
245+-3 F
High oil temp Yes Alarm |
|
OP2
|
39+-2 psi
Low oil pressure (armed after 600 rpm, 15-25 sec) Yes Alarm S15 |
|
OP1
|
30+-2 psi
Low oil pressure (armed after 600 rpm, 15-25 sec) Yes all S14 |
|
SS3
|
2050-2200 RPM
Overspeed Yes all ---------------- SS2 2010-2110 RPM |
|
FL3 on MEP-208
|
~30 gal
low fuel level (starts 35 min timer) Yes Alarm, ?? |
|
FL4 on MEP-208
|
~110 gal
high fuel level Yes Alarm |
|
S13
|
13 cm
low coolant level Yes Alarm |
|
S14
|
18 cm
low coolant level Yes all |
|
K107
|
56.5+-1 Hz (2-3 sec)
underfrequency relay 60 Hz (armed after 600 rpm + 10 sec) Yes Alarm, trip |
|
K108
|
46.5+-1 Hz (2-3 sec)
underfrequency relay 50 Hz (armed after 600 rpm + 10 sec) Yes alarm, trip |
|
K109
|
13-26 amps
reverse power relay Yes Alarm, trip K24 |
|
K110
|
239+-5 VAC
Overvoltage relay Yes All K23 |
|
K111
|
177 VAC (1.5+-1 sec)
undervoltage relay Yes Alarm, trip |
|
K114
|
130% overload
overcurrent relay (169 amps output of a line for 15-25 sec = 130% overload) Yes Alarm, trip K25 |
|
K115
|
28 VAC
ground fault relay (28 VAC across R100 = ground fault of 506 VAC @ .92 amps of T100) Yes Alarm, Trip K22 |
|
K116
|
V = less 5%
Hz = less .5 Phase Angle = 12+-6 degrees synchrocheck relay (permissive device, ensures CB101 cannot close onto a live bus until parameters are met for paralleling) Nothing K21 |
|
OP3
|
4 PSI
Air box disconnect pressure switch (deenergizes air control valves L2A & L2B) Yes All |
|
M7
|
4 cycled start attemps
Crank cycle timer (cycles K3 through 4 cycles of 15/15 sec start attemps then locked out of K3 and energizes K16 relay) Yes Alarm |
|
FS1 on MEP-012
|
At top
Shutoff for Manual Mode at 40 gallons, shuts off fuel FS1 opens, K26 opens, K31 opens, voltage removed from fuel pump solenoid |
|
FS2 on MEP-012
|
Second from top
Shutoff for Automatic mode at 37 gallons, shuts off fuel |
|
FS3 on MEP-012
|
Third from top
Turn on for Automatic mode (S20) at 32 gallons, turn on fuel |
|
FS4 on MEP-012
|
Bottom
Turn on for alarm in Manual or Auto mode 10 minutes remaining at 17 gallons, alarm and horn |
|
K33
|
Fuel Time delay module
Nothing |
|
G1
|
Battery changer not operating
Battery charging alternator Yes Alarm |
|
S24
|
Blown fuse
Blown fuse indicator Yes Alarm |