Use LEFT and RIGHT arrow keys to navigate between flashcards;
Use UP and DOWN arrow keys to flip the card;
H to show hint;
A reads text to speech;
17 Cards in this Set
- Front
- Back
How do you convert water column to ounces (oz/in^2) |
Multiply by 0.578 |
|
How do you convert water column to pounds (psig) |
Multiply by 0.0361 |
|
Where is line pressure taken |
Downstream of service reg and upstream of appliance reg with no gas flow |
|
Where is standing pressure taken |
Downstream of service reg and upstream of appliance reg with only the pilot burning |
|
Where is operating pressure taken? |
Downstream of service reg and upstream of appliance reg with appliance main burner operating |
|
What is differential pressure |
Difference between standing pressure and operating pressure |
|
Where is manifold pressure taken |
Downstream of appliance reg while main burner is operating |
|
What is the venturi effect |
The faster the flow, the lower the pressure |
|
What is gauge pressure |
Pressure in a closed system read 0 at atmospheric pressure |
|
What is absolute pressure |
Gauge pressure added to atmospheric pressure |
|
What is 10 psig in psia |
24.7 |
|
What happens to atmospheric pressure in relation to elevation |
Psi drops 0.5 for every 1000 ft increase |
|
What is inversely proportional to pressure loss |
Pipe size |
|
Who's responsibility is it to ensure all pressure tests are preformed and verified |
The installer so probably you |
|
Which two tests should be preformed at the same place? |
Standing and operating pressure, ideally the dirt pocket of the furthest appliance |
|
Manifold pressure for natural gas |
3.5 in wc or manufacturers specs |
|
Manifold pressure for propane |
11 in wc or manufacturers specs |