  • Front
  • Back

How do you convert water column to ounces (oz/in^2)

Multiply by 0.578

How do you convert water column to pounds (psig)

Multiply by 0.0361

Where is line pressure taken

Downstream of service reg and upstream of appliance reg with no gas flow

Where is standing pressure taken

Downstream of service reg and upstream of appliance reg with only the pilot burning

Where is operating pressure taken?

Downstream of service reg and upstream of appliance reg with appliance main burner operating

What is differential pressure

Difference between standing pressure and operating pressure

Where is manifold pressure taken

Downstream of appliance reg while main burner is operating

What is the venturi effect

The faster the flow, the lower the pressure

What is gauge pressure

Pressure in a closed system read 0 at atmospheric pressure

What is absolute pressure

Gauge pressure added to atmospheric pressure

What is 10 psig in psia

24.7

What happens to atmospheric pressure in relation to elevation

Psi drops 0.5 for every 1000 ft increase

What is inversely proportional to pressure loss

Pipe size

Who's responsibility is it to ensure all pressure tests are preformed and verified

The installer so probably you

Which two tests should be preformed at the same place?

Standing and operating pressure, ideally the dirt pocket of the furthest appliance

Manifold pressure for natural gas

3.5 in wc or manufacturers specs

Manifold pressure for propane

11 in wc or manufacturers specs