Use LEFT and RIGHT arrow keys to navigate between flashcards;
Use UP and DOWN arrow keys to flip the card;
H to show hint;
A reads text to speech;
183 Cards in this Set
- Front
- Back
basic controls are those with |
start,stop,regulate, protect |
|
primary controls in marine refrigeration are |
start, and stop |
|
secondary controls are |
regulate,and protect |
|
the three basic types of controls are electric pneumatic and electronic. how are distinguished apart? |
the type of message they send or recieve |
|
which control devices are used as primary control for a refrigeration cycle |
pressurstat,hummidistat,thermostat, and a time clock are used as primary control for a refrigeration cycle. |
|
when the thermostat is used as a primary control for the refrigeration cyclce |
its located in various places depending on the type of system |
|
what is the difference between a bimetal thermostat and a mercury bulb |
bimetal has open contacts while a thermostat has an enclosed bulb |
|
what would cause flash gas to form in the liquid line |
a pressure drop in the liquid line would cause flash gas in the liquid line |
|
describe the expected observed conditions when a compressor is started after being idle for a long time |
excessive foaming during startup |
|
describe the normal set pints for a LPCO switch (also known as a low pressure cut off switch) |
cuts out at a lower pressure than it cuts in |
|
what does a thermostatic control device sense |
temperature of the space that its in |
|
describe the location of the txv sensing bulb with respect to the back pressure regulating valve, and explain the purpose of this location |
txv is before the backpressure regulator valve |
|
describe the location and purpose of a back pressure regulating valve |
in the suction line off the high temperature evaporator |
|
describe the normal sequence of events for the proper operation of a thermostatically controlled high pressure refrigeration system |
at set point liquid line solenoid valve shuts low cuttout stops compressor top range liquid line opens allows compressor to start |
|
describe the flow path through the relief valve of a modern high pressure system |
relief valve relieves to suction side |
|
how do solenoid valves open and close |
solenoid valves open and close through electromagnetism |
|
list possible cause for and corrective measures required for a compressor that is short cycling on the low pressure cuttout switch |
the system has low refrigerant if its short cycling on low pressure cuttout switch, recharge the system |
|
list possible causes for and corrective actions required to correct a compressor that is short cycling on the high pressure cutout switch |
if the compressor is short cycling on high pressure, it has too much refrigerant, condenser is hot, restore condenser flow |
|
if a compressor is not starting why is it not starting and how can you fix it |
check its power, it has low refrigerant, oil pressure cuttout |
|
describe the purpose and location of liquid strainer in a modern high pressure refrigeration system |
the purpose of the liquid strainer is to protect the metering device from contamination, located prior to the TXV |
|
List possible cause and corrective actions for liquid flood back |
causes for liquid floodback improper TXV operation, evap full of oil, loss of fan flow, low load |
|
describe the conditions that could cause a high pressure refrigeration compressor to be noisy upon startup |
liquid slugging could cause the compressor to be noisy upon start up |
|
describe the condition that could cause a refrigerated space to be to cold |
a refrigerated space could be to cold because of too much refrigerant or imporoper thermostat conditions |
|
describe the causes for and corrective actions to correct a low pressure condition |
low pressure conditions could be caused by a clogged meter, slow charge |
|
describe the causes for and corrective actions to correct a high suction pressure condition coupled with a low discharge pressure condition |
high suction pressure condition coupled with a low discharge pressure condition can be caused by, refrigerant overcharge, dirty condensor, improper mounting of TXV and TXV bulb is loose or dirty |
|
concerning the toxicity of flourocarbons |
In their natural state flourocarbons are mildly toxic |
|
what are the two most practical refrigerant leak testing methods |
electronic sniffer,and bubble method are the two most practical leak testing methods |
|
which two conditions are most likely to cause a system to leak |
the vibration of the systme and open compressors are the two most likely things to cause leaks |
|
harmful chemical reactions between refrigerant and contaminants mixed with it double with |
the harmful chemical reactions double with every 18 degree rise in temperature |
|
a disadvantage of a oil miscible refrigerant is that |
the disadvantage of a oil misciable refrigerant is the refrigerant may dilute the oil, reducing its lubricating qualities |
|
as system pressure drops saturation temperature |
as system pressure drops the saturation temperature also drops |
|
what is specific volumes |
specific volume is the space a substance occupies per unit |
|
the larger the specific volume of a refrigerant |
the larger the specific volume of a refrigerant the larger the compressor and piping to move the refrigerant |
|
a tubing system often requires |
a tubing system often requires less pressure than a piping system to produce a given flow rate |
|
short straight runs of tubing do not take advantage of its natural tendency to withstand |
short runs of tubing do not take advantage of tubing's ability to withstand vibration |
|
the three most important factors to consider when selecting tubing |
the material the tubing is made out of, the inside diamater, and the wall thickness of the tubing |
|
copper tubing type k and l are available in |
K and L are available in two tempers |
|
copper water tubing type M is for use only with |
Copper water tubing type M is for use only with Solder fittings |
|
Corrosive fluids are most frequently carried by |
corrosive fluids are mostly carried by Plastic, or Stainless tubing |
|
What type of tubing is usually used to handle products intended for human consumption |
plastic tubing is usually used to handle products intended for humans |
|
can brass fittings be used with plastic tubing |
yes brass fittings can be used with plastic tubing |
|
when using a tubing cutter to cut tubing how do you use the cutter |
rotate the cutter around the tubing |
|
how do you cut hard tubing |
you cut hard tubing with a hacksaw |
|
in order to remove small chips of material left by cutting |
you should debur the end length of the tubing |
|
the reference mark for all tubing measurments is the |
the centerline of the tubing is the reference mark for all tubing |
|
in order to calculate tubing length through a bend, |
you need to know the typical radius of the bend |
|
how many directions can Manuel tubing benders operate in |
Manuel tubing benders can operate in one direction |
|
when making a 120 degree bend in a length of tubing you should line up the scribed mark on the tubing with a line tangent |
a line tangent to the 90 degree mark on the radius block |
|
tubing has a tendency after bending to |
tubing has a tendency to spring back a small amount after bending |
|
refillable refrigerant cylinders maximum refillable volume is
|
a refillable refrigerant cylinders maximum refrigerant volume is 80% |
|
a common cause of compressor burnout is |
high head pressure is a common cause of compressor burnout |
|
Suction valve sticks open because of impurities in the system |
When suction valve is stuck open discharge pressure is lower while suction pressure is higher |
|
Crankcase heater helps with |
Crankcase heater helps keep oil out refrigerant |
|
What device takes oil out of the hot gas line and put it back in the compressor |
The oil separator takes oil out of the hot gas line and sends it back to the compressor |
|
Liquid slugging is a |
Liquid slugging is a liquid shot back to the compressor |
|
Liquid slugging is a |
Liquid slugging is a liquid shot back to the compressor |
|
Receiver is on the |
The receiver is on the liquid line |
|
On initial pull down |
split plant systems will be isolated from each other and use two compressors to pull it down. Once temperature is achieved they will be paralleled onto one compressor |
|
How do you operate a timer |
Push in the dial and adjust time. |
|
How does the Solenoid valve on a hot gas bypass valve decide the time to open |
It decides it's opening time based on a timer for the defrost cycle |
|
Is it normal for frost to form In a freezers evaporator |
It is normal for frost to form In a freezers evaporator |
|
The faster a contact opens |
The faster a contact opens the less arcing occours |
|
How many winding are running on a single phase motor evaporator and condenser fans |
On the single phase motor only the run winding is energized after start |
|
When placing electrical equipment how much should they plan to exceed the load by |
The electrical equipment should exceed expected load by 50% |
|
Weak overload protectors could cause what |
Weak overload protectors could cause short cycling |
|
What is short cycling |
Short cycling is frequently starting and stopping |
|
If there's a thermostat monitoring a liquid line Solenoid valve |
The thermostat is monitoring box temperature for the liquid line Solenoid valve |
|
The tail coil contact temp is |
The tail coil contact temp is at least 15 degrees cooler than box |
|
What operates a Solenoid valve |
Electromagnetism operates a Solenoid valve |
|
How much hydrogen does a full halogenated molecule contain |
Fully halogenated molecule contain no hydrogen |
|
Filling a cylinder more than 80% could cause |
Filling more than 80% could cause an explosion |
|
What do you use to pressure test |
Nitrogen should be used to pressure test |
|
Is R12 toxic when burned |
Yes R12 is toxic when burned |
|
When adding refrigerant to suction service valve what form should it be in |
The refrigerant should be added to the suction service valve as a vapor |
|
High head pressure can cause what and what's one cause |
High head pressure can cause compressor to burn out, can be caused by dirty condenser |
|
Overcharging can cause |
Overchargeing can cause short cycling on high pressure cut-out as well as normal head pressure with a normal box temperature |
|
Broken valves can cause a compressor to |
Broken valves can cause a compressor to stick or lock up |
|
How many cylinders can a reciprocating compressor have |
Reciprocating compressors can have 1-12 cylinders |
|
Compressor crankcase foaming will increase with what |
Compressor crankcase foaming will increase with the length of time a unit was secured |
|
Cut in means |
Cut in means start |
|
Cut out means |
Cut out means stop |
|
With an lpco what is true about cut in and cut out |
It cuts out at a lower set point than it cuts in. |
|
Psig in a system is relative to what |
Psig is relative to the amount of refrigerant in system |
|
A unit will not run |
Unit has broken timer |
|
Refrigerator section too warm |
Air duct not positioned correctly |
|
Refrigerator section too cold |
Defective airflow control |
|
Freezer and refrigerator section too warm |
Shortage of refrigerant |
|
Noisy operation of compressor |
Cabinet not level |
|
Unit cycles on overload |
Weak overload protector |
|
Stuck motor compressor |
Broken valve |
|
Use to check systems pressures |
A gauge manifold |
|
Used to bleed capacitors |
20k ohm 2 watt resistor |
|
Used to prevent freezing at door seals |
Mullion heater |
|
The common refrigerator refrigerant of today |
R134a |
|
May act as insulator resulting in poor cooling |
Ice |
|
Can be used to check door seals for leaks |
Paper |
|
Can be used to check for proper grounding |
Voltmeter |
|
The standard condition of refrigerant used in charging domestic or small commercial units |
For charging domestic and commercial units VAPOR |
|
The amount of refrigerant to be charged can be precisely measured with |
Digital weighing scale |
|
Liquid refrigerant in the compressor may cause |
Broken valves |
|
Most internal problems are due to |
Air and moisture |
|
Piercing valves may be |
Piercing valves may be braized or bolted on a line |
|
Condenser which uses water flowing through an inside tube to cool refrigerant in an outer tube is called |
Tube within a tube condensor |
|
Shell and tube refers to |
Shell and tube refers to water cooled condensers |
|
A number of evaporators connected to a single condensing unit |
Eight |
|
Controls the number of cylinders which are pumping |
Hydraulic or electric unloading device |
|
Location where the sudden change of some of the liquid flash gas occours |
Refrigerant control |
|
Shell and tube within a tube condensor mediums |
Water cooled |
|
Number of possible defrost systems |
Six |
|
Used on the suction line to ensure one way refrigerant flow |
Check valve is used on suction line to ensure one way refrigerant flow |
|
A water pressure regulating valve is operated by |
A water pressure regulating valve is operated by head pressure |
|
Two temperature valves are sometimes called |
Two temperature valves are sometimes called pressure reducing valves |
|
Two types of temperature valves are |
Two types of temperature valves are pressure operated and temperature operated |
|
Are types of compressor oil return systems |
Separator,regulator, and resivoir are compressor oil return syy |
|
If pressure drop of 1 psi for low temperature, or up to 6 psi for high temp systems what should be replaced |
If those pressure drops occur replace the filter drier |
|
It is often necessary to clean or replace the |
Clean or replace the strainer in a water valve system |
|
What is used to assure the return of oil in the compressor |
an oil seperator is often used to assure the return of oil to the compressor |
|
what maybe installed to red condensor movement being transferred into the high side or low sides lines |
vibration absorbers |
|
what do bubbles in the sight glass indicate |
bubbles in the sight glass show a lack of refrigerant |
|
if the expansion valve is stuck open what may happen |
if the expansion valve is stuck open may get frosting on the suction line |
|
improperly adjusted shut out switches may cause |
improperly adusted shut out switches may cause short cycling |
|
if the stewards leave the door open or don't fully close it what could happen |
if the stewards leave the door open could have decreased system efficiency and the compressor will continuously run |
|
restricted suction strainers can cause |
restricted suction strainers can cause low suction pressure |
|
a stuck open relief valve can cause |
a stuck open relief valve can cause a high suction and low discharge since relief valve sends flow back to suction side |
|
what controllers the compressor running |
the low pressure cutout switch controls the compressors running |
|
a broken timer could prevent the unit from what |
a broken timer could prevent the unit from running |
|
the difference between a follow through and a a surge type receiver is |
the way their piped and vented |
|
which of the statements is true about r22 |
r22 is miscible at high side operating conditions |
|
when taking readings the suction service valve (at the compressor inlet) of an operating system |
when taking reading at the compressor inlet a pressure and temperature reading is required because the refrigerant is probably superheated |
|
the best combination to use in selecting a compressor of the smallest possible displacement size is a refrigerant that |
a refrigerant that is low in specific volume but high in latent heat of vaporization |
|
which is true about suction and hot gas lines |
it is true that both under sizing and over sizing are bad, but under sizing tends to be the least damaging. |
|
an easy way to test for flashing in the liquid line is with |
an electronic temperature sensor |
|
the liquid line needs insulation when |
the liquid line needs insulation when the air surrounding it is warmer than the refrigerant within it |
|
the first line of defense against a resonating hot gas line is |
the first line of defense against a hot gas line is installing a hot gas muffler |
|
the suction line needs insulation mainly to |
the suction line needs insulation mainly to prevent condensation of air moisture in it |
|
which group of refrigerants holds least water in solution thus forming free water more easily |
hydrocarbons hold least water in solution |
|
in order to avoid adding moisture to the system coils, piping and accesories |
in order to avoid adding moisture to the system coils, keep them capped until installation time |
|
the evacuation dehydration should happen |
evacuation/dehydration should happen after the system has proven to be leak tight, but before it is changed |
|
a evacuation manifold set |
a evacuation manifold set usually has 5 hoses |
|
a schrader valve core remover is useful on |
a schrader valve core remover is useful on small systems to speed up evacuation/dehydration |
|
when a system is leak tight but still wet, what will the vacuum indicator do after the vacuum pump is stopped, and valved off from the system |
the vacuum indicator will rise then level off above 500 microns |
|
moisture removal by charge replacement is not |
moisture removal by charge replacement is not a substitute for proper evacuation methods of dehydration |
|
disposable refrigerant usually contain how much refrigerant |
disposable refrigerant usually contain 30lbs or less |
|
a untagged refrigerant cylinder is found in the storage area it is white the refrigerant contents should be |
the untagged white refrigerant should be R12 |
|
gauge manifold hoses for deep vacuum must be good to |
gauge manifold hoses for deep vacuum must be good to 29.90 hg vacuum |
|
when the gauge manifold is front seated it is turned |
when the gauge manifold is front seated it is turned clockwise all the way |
|
the benifits of a evactuation manifold over a standard manifold are |
the benifits of a evactuation manifold over a standard manifold are evaluation time is less |
|
the main difference between an inline service valve and a process valve is that |
the process valve simply provides access to the system while the inline isolates part of the system as well as providing service access |
|
a harding valve is |
a harding valve is a inline service valve |
|
a schrader valve is |
a schrader valve is a process valve |
|
Ice used is used in the charge migration method of refrigerant recovery to |
Ice used is used in the charge migration method of refrigerant recovery to lower the cylinder pressure |
|
the refrigerant recovery/recycle unit is normally connected to the system through the |
the refrigerant recovery/recycle unit is normally connected to the system through the UTILITY HOSE OF THE GAUGE MANIFOLD |
|
when using a recovery/recycle unit on a system in need of repair, the normal sequence of operation goes |
when using a recovery/recycle unit on a system in need of repair, the normal sequence of operation goes RECOVER,REPAIR,EVACUATE,RECYCLE AND RECHARGE |
|
The best way to determine the charge needed by a system that has had all its charge removed is by |
The best way determine the charge needed is by looking at the charge printed on the manufacturers nameplate |
|
in order to charge refrigerant as liquid into a system what must you do |
In order to charge refrigerant as a liquid you must flip the cylinder upside down |
|
When doing a full charge what does it mean when the bubbles disapear from the sight glass |
when the bubbles disapear it means there's saturated liquid at the sightglass |
|
when using the superheat method of charge adjustment, a superheat reading of 4F too high requires |
a superheat reading of 4F too high requires no charge adjustment |
|
its better to charge oil by drawing it into the compressor than by pouring it in because |
When oil is drawn in the compressor crankcase is not opened to contamination by the atmosphere, which does happen when pouring it in |
|
what component reverses coil function in a heat pump system |
a 4 way valve is the component reverses coil function in a heat pump system |
|
What is excessive blow-by |
When the piston goes up and down and less happens usually due to wear |
|
Discharge head valve stuck open causes what |
When the discharge head valve is stuck open discharge is low and suction pressure is lower |
|
Can excessive blow-by happen on a scroll compressor |
Excessive blow by can't happen on a scroll compressor |
|
What is the unloader |
A device that makes the discharge pump back into the suction |
|
If the unloader is stuck open |
If the unloader is stuck open discharge pressure will be low and suction pressure will be high. |
|
describe the conditions neccesary for R12 to be a health hazard 1 |
R12 must be burned to be a health hazard 1 |
|
describe the methods to remove moisture from a high pressure refrigeration system 2 |
dehydration 2 |
|
describe the results of not removing moisture from a high pressure system |
freezing the txv |
|
why are there bubbles in my sight glass |
the refrigerant charge is too low |
|
describe the purposes of liquid line in sight glass |
liquid line sight glass indicates moisture and state of charge |
|
describe the conditions that will cause and corrective actions required when frost forms on the suction line of a high pressure refrigeration system |
txv is stuck open so ya can either heat it with a hot air gun also check the sensing bulb |
|
describe the conditions that will cause and corrective actions required when frost or sweat forms on the crank case of a high pressure refrigeration system |
liquid returning to comperssor it will be evaporator related |
|
describe the indications of and corrective actions required when the air is trapped in a damn high pressure refrigeration system |
when the air is trapped in the system youll have high head pressure just remove the old refrigerant and place it with good refrigerant |
|
describe the relationship between temperature and pressure in a modern high pressure refrigerant system |
saturated at inlet and super-heated at outlet |
|
question-discuss the reasons for and corrective actions required when frost accumulates on the evaporator coils in a modern high pressure refrigeration system |
answer reason- its colder than the freezing point, high hummidity, Or the TXV is stuck open solution- reduce hummidity, put on defrost |
|
describe the results of a shitty leaking gasket in a walk in chillbox |
yet again increased hummidity, also the compressor will run for longer. because the gasket is a piece of WANKSTAIN apearantly |
|
Maggots-discuss the reason for and corrective actions required when the suction line is warmer than normal in a modern high pressure refrigerant system |
Its Bloody low on refrigerant so add refrigerant or there's a blockage of the refrigerant flow path |
|
describe the Damn effects of excess refrigerant in a modern high pressure refrigeration system PVT Pile |
Sir its the high suction and discharge pressure can be corrected by removing refrigerant sir |
|
Now maggot discuss the reasons for and corrective actions required when flash gas forms in the liquid line of a modern refrigeration system |
You will have a clogged strainer or loss of condser cooling causes flash gas, low subcooling |
|
how do you adjusting a txv |
you adjusting TXV through time and patience |
|
Describe the method to control water flow through a modern high pressure refrigeration condesor. |
INLET PRESSURE AND HEAD PRESSURE |
|
DESCRIBE THE EFFECTS OF SUPERHEAT BEING SET TO LOW IN A MODERN REFRIGERATION SYSTEM |
LIQUID RETURN TO THE COMPRESSOR CALLED SLUGGING |
|
DESCRIBE THE EFFECTS OF SUPERHEAT BEING SET TO HIGH IN A MODERN HIGH PRESSURE REFRIGERATION SYSTEM |
STARVED EVAP, HIGH BOX TEMP |
|
DESCRIBE THE FUNCTION OF AN INTERCHANGER IN A MODERN HIGH PRESSURE REFRIGERATION SYSTEM |
PROVIDE ADDITIONAL SUBCOOLING TO LIQUID, ADDITIONAL SUPERHEAT TO VAPOR LINE |