Narrow Range Level
Range and Calibration
Reactor Safeguard and Feedwater control inputs
– 0 to + 60,
Calibrated 1045psig and 135°F in Drywell
Wide Range Level
Range and Calibration
Level indication for loss of FW, RPV inventory loss, and ECCS initiation
-150 to +60,
Calibrated 1045psig and 135°F in Drywell
Upset Range Level
Range and Calibration
to follow abnormal rises in RPV level
0 to +180 for normal operation,
rescaled 0 to +500 for refueling,
Calibrated 1045psig and 117/135°F in Drywell.
Shutdown Range Level
Range and Calibration
Level indication when reactor is shutdown in a COLD condition
0 to 370
rescaled 0 to +500 for refueling,
calibrated for 0 psig and 120°F in RPV and 80°F in Drywell.
Fuel Zone Range Level
Range and Calibration
LOCA level indication
-100 to -350,
calibrated for 212°F in RPV and Drywell.
Non-Calibrated Jet Pump Flow
Range
All Jet Pumps have a pressure tap on the throat which is compared to the Below Plate Core Pressure to provide a DP, the square root of this DP gives a signal that represents flow.
Calibrated Jet Pump Flow
Range & Failure Modes
#5, #10, #16(Unit 1)/#15(Unit 2), #20

Flow is measured from pressure taps at the Jet Pump throat and diffuser sections

Calibrated pump flow is displayed in MCR and used to calibrate other Jet Pumps
Jet Pump Loop Flow
Range
All 10 Jet pump flows are are summed together to provide a Recirc Loop flow signal.
Core Flow
Range
0 to 100 Mlb/hr
Core Plate Differential Pressure (DP)
Range
0 to 30 psid
Wide Range Pressure
Range
0 to 1200 psig
Wide Range (PAMS)
0 to 1500 psig
Narrow Range
900 to 1100 psig
Narrow Range RPV Level
Normal Full Power Values
+35"
Wide Range RPV Level
Normal Full Power Values
+ 35"
Upset Range RPV Level
Normal Full Power Values
+ 40"
Shutdown Range RPV Level
Normal Full Power Values
Low
Fuel Zone Range RPV Level
Normal Full Power Values
Off scale - high
RPV Pressure
Normal Full Power Values
1045 psi
Jet Pump Loop Flow
Normal Full Power Values
50 Mlbm/hr
Core Flow
Normal Full Power Values
100 Mlbm/hr
Calibrated Jet Pump Flow
Normal Full Power Values
5 Mlbm/hr
Core plate Differential Pressure (DP)
Normal Full Power Values
16 psid
Leak in reference leg
Weight of fluid in reference leg drops due to reduction in water density.
Transmitters "sees" lower DP (variable leg versus reference leg).
Indicated RPV level goes up.
Leak in variable leg
Excess flow check valve closes
Variable leg drains
Indicated level lowers
Equalizing valve open
Equalizes pressure across transmitter
Reference leg level will drain down to variable leg level
Indicated level rises
Hole in detector diaphragm
Diaphragm no longer senses DP
Indicated level rises
Operation at low Reactor Vessel temperatures on instruments calibrated hot
Narrow, Wide, and Upset Ranges are calibrated for Hot conditions.
At lower temperatures, water is more dense.
A set column of cold water will yield a higher DP as the same column of hot water.
If indicated RPV level remains constant as temperature drops:
Actual RPV level must have lowered
In Cold Shutdown, an actual RPV level of +45 inches will read +60 inches on Narrow Range instruments.
Operation at high Reactor Vessel temperatures on instruments calibrated cold
Shutdown Range is calibrated for cold conditions.
Effects are opposite those for Narrow Range.
Shutdown Range will indicate a lower than actual RPV level during hot conditions.
Elevated Drywell temperatures
Effects are similar to reference leg flash.