IA Isolation Signal (7)
Closes MSIVs & Main Steam Line Drains.
Inboard valves (HV-41-*F022A/B/C/D, HV-41-*F016) - channels 'A' & 'B' for MSL Drain
Outboard Valves (HV-41-*F028A/B/C/D, HV-41-*F019) - channels 'C' & 'D' for MSL Drain

MSIVs require channels ‘A’ -OR- ‘C’ -AND- ‘B’ -OR- ‘D’

1) Low low low Rx level (-129")
2) Low Rx press (756#)[mode switch in RUN]
3) High temp in outboard MSIV room (192°F)
4) High temp in turbine tunnel (165°F)
5) High steam line flow (140%)
6) Low condenser vacuum (10.5 psia) (8.54” of Hg)
7) Manual ('A' or 'C' AND 'B' or 'D' pushbuttons)
IB Isolation Signal (2)
Closes Main Steam sample valves (HV-41-*F084/*F085), recirc sample valves (HV-43-*F019/*F020),
& trips mechanical vacuum pump (high MSL rad only) (A & B channels only)

1) Low low Rx level (-38")
2) Manual ('A' pushbutton for inbds & 'D' pushbutton for outbds)
Note: Mech Vac pump requires a single channel for trip.
IIA Isolation Signal (3)
Closes HV-51-*F009, *F008, *F015A(B), *51A(B), & *F050A(B)

1) Low Rx level (12.5") A&B OR C&D
2) High Rx press (75#) Single Channel
3) Manual 'A' inbd (*F009, *F050A(B), *51A(B)), 'B' outbd (*F008, *F015A(B))
Note: *F008 has a separate 93# interlock to prevent opening w/ high Rx Press for App R. (normally in isolation during normal power operations, due to level being >12.5” and pressure >75#)
IIB Isolation Signal (4)
RHR HX Sample lines & RHR Drains to RW
Closes HV-51-*F040, *F049, *F079A(B), *F080A(B)

1) Low Rx level (12.5") A&B OR C&D
2) High drywell press (1.68#) A&B OR C&D
3) Manual: 'A' outboard [*F080A(B), *F040], 'B' inboard [*F079A(B), *F049]
4) *F040: high temp isolation (140°F)
III Isolation Signal (9)
RWCU (Isolation Channel A-> *F001, Channel B-> *F004 Valve)
Closes HV-44-*F001, *F004
1) Low low Rx level (-38") A&B OR C&D
2) SLC Initiation ('A' or 'C' for *F001, 'B' for *F004) Single channel
3) RWCU Differential high flow (>54.9 gal for 45 sec TD) Single channel
4) RWCU pump room high temp (155°F) Single channel
5) RWCU Pump room delta temp (>52°F) Single channel
6) RWCU HX room temp (132°F) Single channel
7) RWCU HX delta temp (>32°F) Single channel
8) NRHX outlet temp (140°F)[*F004 only]
9) Manual: 'A' inboard (*F001), 'D' outboard (*F004)
IVA Isolation Signal (7)
HPCI Valves: Closes HV-55-*F002 (inboard), *F003 (outboard), *F100 (bypass), *F041 (supp pool inboard), *F042 (supp pool outboard), & trips HPCI turbine.

1) High steam line flow (300% w/ 3 sec TD) Sensors are two out of two once per DIV 2 or DIV 4
2) Low steam line press (100#) Sensors are two out of two once per DIV 2 or DIV 4
3) Rupture diaphragm press (10#) Sensors are two out of two once per DIV 2 or DIV 4
4) High room temp (225°F) Single channel
5) High piping area temp (175°F) Single channel
6) High room delta temp (126°F) Single channel
7) Manual: *F003, *F041, *F042, & *F100 (only works with initiation signal sealed in)
Note: HPCI logic is energize to actuate
Note: Valves only require a single channel for isolation.
IVB Isolation Signal (1)
HPCI Vacuum Breakers
Closes HV-55-*F093 & *F095
1) High drywell press (1.68#) & low Rx press (100#)
Auto reset. No manual initiation
ONE out of ONE ONCE!!
VA Isolation Signal (7)
RCIC
Closes HV-49-*F007 (inboard), *F008 (outboard), *F076 (bypass), & trips RCIC turbine.
1) High steam line flow (300% w/ 3 sec TD) Any sensor actuation closes inbd & outbd isolation valve.
2) Low steam line press (64.5#) Any sensor actuation closes inbd & outbd isolation valve.
3) Rupture diaphragm press (10#) Any sensor actuation closes inbd & outbd isolation valve.
4) High room temp (205°F) Single channel
5) High piping area temp (175°F) Single channel
6) High room delta temp (109°F) Single channel
7) Manual: *F008 & *F076 (only works if initiation signal was received and not reset)
Note: RCIC logic is energize to actuate
ONE out of ONE ONCE!!
VB Isolation Signal (1)
RCIC Vacuum Breakers
Closes HV-49-*F080, *F084
1) High drywell press (1.68#) & low Rx press (64.5#)
Auto reset. No manual initiation.
ONE out of ONE ONCE!!
VIA Isolation Signal (10)
Containment Purge Supply & Exhaust
Closes big CAC valves (N2 supplies, purge supplies, DW purge exhaust, Supp Pool purge exhaust)
[Isolates BOTH Units]

1) Low low Rx level (-38")  A&B OR C&D
2) High drywell press (1.68#)  A&B OR C&D
3) Low RE D/P (-0.1") 50 min TD Single channel
4) Low RF D/P (-0.1") 100 sec TD Single channel
5) High RE exhaust rad (1.35mr/hr)  A&B OR C&D
6) High RF exhaust rad (2.0 mr/hr)  A&B OR C&D
7) High North Stack rad (2.1 micro curies/cc)  A&B OR C&D
8) RE/SBGT connecting valves not closed (196/197)
9) RF/SBGT connecting valves not closed (019/020)
10) Manual (pushbuttons 'A' & 'D' OR key lock switches *78A & *78B).
Note: Closing SGD-206-1, SGD-206-2, or SGD-506-3 bypasses the isolation signal from the associated zone’s logic (i.e. closing SGD-206-1 means that any isolation signal from U-1 will not cause an isolation).
VIB Isolation Signal (9)
Containment exhaust to REECE, Inerting Block Valves
Closes little CAC valves (DW exhaust to REECE, Supp Pool exhaust to REECE, N2 supply block valves)
[Isolates BOTH Units] Bypassable
1) Low low Rx level (-38")  A&B OR C&D
2) High drywell press (1.68#)  A&B OR C&D
3) Low RE D/P (-0.1") 50 min TD Single channel
4) Low RF D/P (-0.1") 100 sec TD Single channel
5) High RE exhaust rad (1.35mr/hr)  A&B OR C&D
6) High RF exhaust rad (2.0 mr/hr)  A&B OR C&D
7) RE/SBGT connecting valves not closed (196/197)
8) RF/SBGT connecting valves not closed (019/020)
9) Manual (pushbuttons 'A' & 'D' OR key lock switches *78A & *78B).
Note: Closing SGD-206-1, SGD-206-2, or SGD-506-3 bypasses the isolation signal from the associated zone’s logic (i.e. closing SGD-206-1 means that any isolation signal from U-1 will not cause an isolation).
VIC Isolation Signal (4)
GROUP 6C: Containment sampling & recombiner lines
Closes sample & recombiner valves (common N2 purge M/U supply, CASS, DW rad sample sys)
[isolates only affected unit] Recombiner and CASS isolations ONLY are bypassable
1) Low low Rx level (-38")
2) High drywell press (1.68#)
3) RE high rad (1.35 mr/hr)
4) RF high rad (2.0 mr/hr)
ONE out of ONE ONCE!!
VIIA Isolation Signal (4)
PCIG
Closes PCIG process lines (HV-59-*01, *02, *29A(B), *35)
Bypassable
1) Low low low Rx level (-129") A&B OR C&D
2) High drywell press (1.68#) A&B OR C&D
3) RE high rad (1.35 mr/hr) A&B OR C&D
4) Manual
VIIB Isolation Signal (3)
TIP purge lines
Closes TIP supply (HV-59-*31) No bypass.
1) Low low Rx level (-38") A&B OR C&D
2) High drywell press (1.68#) A&B OR C&D
3) RE high rad (1.35 mr/hr) A&B OR C&D
NO Manual
VIIC Isolation Signal (1)
PCIG to ADS
Closes PCIG to ADS [HV-59-*51A(B)]
No Bypass
1) Low d/p PCIG to drywell (2 psid)
NO Manual
ONE out of ONE ONCE!!
VIIIA Isolation Signal (3)
DWCW & RECW
Closes DWCW valves (HV-87-*20A(B), *21A(B), *22, *23, *28, *29) & Recirc Pump cooling water isolation valves (HV-13-06, *07, *08, *11).
1) Low low low Rx level (-129") A&B OR C&D
2) High drywell press (1.68#) A&B OR C&D
3) Manual
VIIIB Isolation Signal (3/3)
GROUP 8B: Misc. Process lines
Closes drywell floor (HV-61-*10, *11) & equip sumps (HV-61-*30, *31), Supp Pool Cleanup pump suction (HV-61-*27, *28), & TIP withdrawal.
1) Low low Rx level (-38") A&B OR C&D
2) High drywell press (1.68#) A&B OR C&D
3) Manual

GROUP 8B(Part 2): Misc. ECCS valves
Closes HV-052-*F015A/B, HV-51-*F027A/B, HV-C-51-*F103A/*F104A.
1) low low low Rx level (-129")
2) high drywell press (1.68#)
3) Rx low pressure (455#)
ONE out of ONE ONCE!!
RE HVAC (6)
1) Low low Rx level (-38") A&B OR C&D
2) High drywell press (1.68#) A&B OR C&D
3) Low RE D/P (-0.1") 50 min TD
4) High RE exhaust rad (1.35mr/hr) A&B OR C&D
5) RE/SBGT connecting valves not closed (196/197)
6) Manual
RF HVAC (4)
1) Low RF D/P (-0.1") 100 second TD
2) High RF exhaust rad (2.0 mr/hr) A&B OR C&D
3) RF/SBGT connecting valves not closed (019/020)
4)Manual
Main Steam, N2, & Recirc Seals Blocks & Vents (5)
Main Steam blocks (HV-41-*42, *43) CLOSE, Recirc Pump Seals blocks (HV-46-*27, *28) CLOSE, N2 supply vents (HV-57-*65, 67) OPEN. This is a 6C mimic of initiation signals.
1) Low low Rx level (-38")
2) High drywell press (1.68#)
3) RE exhaust high rad (1.35 mr/hr)
4) RF exhaust high rad (2.0 mr/hr)
5) Manual
Note: Valves only require a single channel for isolation.
Note: Recirc pump seal vents (HV-46-*25, *26) and Main Steam vents (HV-41-*40, *41) are manual open only.
Inst Gas Blocks & Vents (3)
Inst air/inst gas blocks (HV-59-*40, 41) CLOSE, Inst air/inst gas vents (HV-59-42, *43) OPEN.
1) Low low low Rx level (-129") This is a 8A mimic PLUS RE RAD of initiation signals
2) High drywell press (1.68#)
3) RE exhaust high rad (1.35 mr/hr)
Note: Valves only require a single channel for isolation.
Loss of *AY160 OR *BY160 isolates (6)
1. DWCW
2. PCIG
3. RECW
4. RWCU
5. RE HVAC
6. Causes a 1/2 MSIV isolation.
Loss of 125VDC (2)
1. MSIV DC solenoids deenergize (valves stay open)
2. RE/RF HVAC DC solenoids deenergize (partial isolation & SGTS/RERS start)
Effect of LOCA on NSSS bypasses
Power is lost to NSSSS bypass relays and bypassed valves reisolate (valves must be rebypassed to be opened). Bypasses are energize to operate.
Reactor Level 3 - Low (2)
IIA - RHR S/D Cooling
IIB - RHR HX Sample Lines
Reactor Level 2 - Low Low (9)
IB - Main Steam And Rx Water Sample
III - RWCU Lines
VIA - Prim Cont Purge Supply AND Exhaust (big)
VIB - Prim Cont Exh to REECE AND N2 Block Valves (small)
VIC - Prim Cont Sampling & Recombiner Lines
VIIB - Prim Tip Purge Supply
VIIIB - Miscellaneous Process (Sumps, Tips, N2, Recirc Seal Purge, MSL Drain )
RE HVAC
RF HVAC
Reactor Level 1 - Low Low Low (9)
VIIIA - D/W Chilled Water & Recirc Pump Clg Water
VIIIB - ECCS Process Lines (CS test, SP Spray, HX vent)
VIIIB - Instrument Gas Block and Vents
Main Steam Line High Radiation (1)
Mechanical Vacuum Pump
Main Steam Line - High Flow (1)
IA - MSIV's and Steam Line Drains
Main Steam Line - High Flow (1)
IA - MSIV's and Steam Line Drains
Drywell High Pressure and Reactor Low Press (1)
VIIIB - ECCS Process Lines
Drywell High Pressure (11)
IIB - RHR HX Sample Lines
VIA - Prim Cont Purge Supply AND Exhaust (big)
VIB - Prim Cont Exh to REECE AND N2 Block Valves (small)
VIC - Prim Cont Sampling & Recombiner Lines
VIIA - PCIG Process Lines
VIIB - Prim Tip Purge Supply
VIIIA - D/W Chilled Water and Recirc Pump Cooling Water
VIIIB - Miscellaneous Process (Sumps, SP cleanup, Tips, N2, Recirc Seal Purge, MSL Drain )
VIIIB - Instrument Gas Block and Vents
RE HVAC
RF HVAC
High Drywell Pressure & RCIC Low Steam Supply Pressure (1)
VB - RCIC Turbine Exh Vac Breaker Line
High Drywell Pressure & HPCI Low Steam Supply Pressure(1)
IVB - HPCI Turbine Exh Vac Breaker Line
RWCU - Flow, Area High Temp, Non-Regen Htx High Temp(1)
RWCU Lines
RCIC - RX Steam Line dP, Diaphram High Pressure, High Area Temperature (1)
VA - RCIC Process Lines
HPCI - RX Steam Line dP, Diaphram High Pressure, High Area Temperature (1)
IVA - HPCI Prcess Lines
HPCI - Steam Supply Low Pressure(1)
IVA - HPCI Prcess Lines
PCIG - PCIG to Drywell - Low dP (1)
VIIC - PCIG to ADS valves
Main Steam Line - Low Pressure (1)
IA - MSIV's and Steam Line Drains
Condenser Vacuum - Low (1)
IA - MSIV's and Steam Line Drains
Refueling Area Ventilation Exhaust - High Radiation (6)
VIA - Prim Cont Purge Supply AND Exhaust (big)
VIB - Prim Cont Exh to REECE AND N2 Block Valves (small)
VIC - Prim Cont Sampling & Recombiner Lines
VIIIB - Miscellaneous Process (N2, Recirc Seal Purge, MSL Drain )
RE HVAC
RF HVAC
Reactor Encl Ventilation Exhaust - High Radiation (9)
VIA - Prim Cont Purge Supply AND Exhaust (big)
VIB - Prim Cont Exh to REECE AND N2 Block Valves (small)
VIC - Prim Cont Sampling & Recombiner Lines
VIIA - PCIG Process Lines
VIIB - Prim Tip Purge Supply
VIIIB - Miscellaneous Process (N2, Recirc Seal Purge, MSL Drain )
VIIIB - Instrument Gas Block and Vents
RE HVAC
RF HVAC
Outside Atmosphere to Refueling Area Low DP (4)
VIA - Prim Cont Purge Supply AND Exhaust (big)
VIB - Prim Cont Exh to REECE AND N2 Block Valves (small)
RE HVAC
RF HVAC
Outside Atmosphere to Reactor Area Low DP (4)
VIA - Prim Cont Purge Supply AND Exhaust (big)
VIB - Prim Cont Exh to REECE AND N2 Block Valves (small)
RE HVAC
RF HVAC
Reactor Pressure - High (RHR valve permissive) (1)
IIA - RHR S/D Cooling
North Stack Effluent High Radiation (1)
VIA - Prim Cont Purge Supply and Exhaust
SLCS Initation(1)
III - RWCU Lines
Reactor Encl or Refuel Floor / SGTS Connecting Valve Failed Open (4)
VIA - Prim Cont Purge Supply and Exhaust
VIB - Prim Cont Exh to REECE AND N2 Block Valves (small)
RE HVAC
RF HVAC