Water
Class A - Common combustibles - leaves an ash or has glowing embers

Class B - Flammable liquids
Class C - Energized electrical equipment

Removes heat
Foam (Extinguishers)
Class B - Flammable liquids

Class A - Common combustibles - leaves an ash or has glowing embers

Smother and remove heat
Dry Chemical (Purple K)
Class B - Flammable liquids

Class C - Energized electrical equipment

Interrupts reaction
CO2
(Cardox)
Class C - Energized electrical equipment

Class A - Common combustibles - leaves an ash or has glowing embers
Class B - Flammable liquids

Smother
Halon
Class C - Energized electrical equipment

Class A - Common combustibles - leaves an ash or has glowing embers
Class B - Flammable liquids

Interrupts reaction
Wet Potassium Acetate
Class K - Involves a liquid cooking medium (oil or grease)

Class A - Common combustibles - leaves an ash or has glowing embers
Class B - Flammable liquids

Smothers and removes heat
Electric Motor Driven Pump
2500gpm at 125psig, Powered by 480 VAC non safeguard load center

Auto Start:
- 100 psig in fire main
Manual Start (either):
- Pushbutton on MCR panal
- Pushbutton on local panal

Manual Shutdown
- Local panel (ONLY)
Diesel Driven Fire Pump
2500gpm at 125psig, start via two DC batteries, 550 gal fuel tank (40 hrs)

Auto Start:
- 95 psig in fire main
Manual Start (either):
- Pushbutton on MCR panal
- Pushbutton on local panal

Manual Shutdown
- Local panel (ONLY)
Backup Fire System Pump
1500gpm at 125psig, start via two DC batteries, 275 gal fuel tank (33 hrs)
Independent water source – 500,000 gal backup fire water storage tank (parking lot)

Auto Start:
- 95 psig in fire main
Manual Start (either):
- Pushbutton on local panal
Auto Shutdown:
- No system demand for 30 mins
Manual Shutdown
- Local panel (ONLY)
Wet Pipe Sprinkler System
Fusible sprinkler elements, water supplied to sprinkler heads

Actuation:
- Fusible elements melt at ~ 212°F
Shutdown - Close OS&Y valve
Pre-Action Sprinkler System
Fusible sprinkler elements, water supplied to closed deluge valve.

Actuation (BOTH):
- Deluge valve OPENS (heat detector trips 190°F OR Manual at valve)
- Sprinkler fusible elements melt at ~ 212°F
Shutdown - Close OS&Y valve
Automatic and Manual Deluge Sprinklers
Open sprinkler heads, water supplied to closed deluge valve

Actuation:
- Deluge valve OPENS (heat detector trips 190°F OR Manual at valve)
Shutdown:
- Close OS&Y valve
Water Curtains and Hatchway
Open sprinkler heads, water supplied to closed deluge valve.

Actuation:
- Manual initiation of deluge valve at pull station or at valve
Shutdown - Close OS&Y valve
Charcoal Filter Spray Equipment
Open spray heads, OS&Y valve outside filter

Actuation:
- Manual opening of OS&Y valve (heat detector alarms ONLY)
Shutdown - Close OS&Y valve
b. Carbon Dioxide Subsystem
Used where equipment damage is undesirable
Personel protection - Automatic initiation utilizes an alarm and time delay. & wintergreen sent is release.

U1 & U2 Cable Spreading Room/ U1 & U2 Exciter Housing
Actuation (EITHER):
- Pull stations for each unit (located outside of cable spreading room/ outside of control room door)
- Reposition electro manual pilot cabinets located next to CO2 storage unit (available on loss of power)
Hose Reels - U1 & U2 Turbine bearing #10 & Exciter Panal
- 13.2 KV switchgear compartment
- Outside MCR doors
Actuation:
- Pulling hose reel out of play pipe will charge hose reel
c.          Halon 1301 Subsystem
Odorless, colorless gas, that interrupts chemical chain reaction
does NOT displace oxygen – semi-habitable
Personel protection – pre-charge alarm sounds in local area and control room

U1 & U2 Aux Equipment Room – 7 main & 7 reserve cylinder
Automatic Actuation
- Heat detectors (Main cylinders ONLY)
Manual Actuation (EITHER)
- Local pull box located in AER (Main cylinders ONLY)
- Manual lever on Halon pilot cylinder located in TE 269' U1 & U2 (available on loss of power)

Remote Shutdown Panel – 1 main & 1 reserve cylinder
Automatic Actuation
- Heat detectors (Main cylinders ONLY)
Manual Actuation (EITHER)
- Local pull box located inside RSP (Main cylinders ONLY)
- Manual lever on Halon pilot cylinder located U1 TE 269' (available on loss of power)

An additional Halon system is located in TSC computer room

Hanlon system can NOT be secure after initation
d.          Protein Foam
Foam

Actuation:
- Pull stations located outside fuel oil storage and transfer house
Shutdown:
- Close OS&Y valve
State the power supply to the fire protection pumps.
Engine Driven Fire Pump - Non Safeguard AC power
Diesel Driven Fire Pump - DC battery starting power
Back up Fire Pump - DC battery starting power
Determine how to initiate a fire suppression subsystem when power is not available. (Diagnostic)
Diesel Driven Fire Pump - DC battery starting power
Back up Fire Pump - DC battery starting power

Wet pipe – will not be effected (links melt)
Pre – action, Deluge, water curtin & hatchway – must manually actuate deluge valve
Charcoal – manually open OS&Y
Cardox – Manually at Electro manual pilot cabinet
Halon – manual lever on cylinder