What is the wire designator for the compressor module?
|
1U49 (SCM-MCM)
|
|
What is the wire designator for the Human Interface module?
|
1U65 (HI)
|
|
What is the wire designator for the HeatModule?
|
1U50
|
|
What is the wire designator for the Ventilation Overide Module?
|
1U53 (VOM)
|
|
What is the wire designator for the Interprocessor Comunication Board?
|
1U55 (IPCB)
|
|
What is the wire designator for the Trane Communication Interface Module?
|
1U54/1U104 (LCI/BCI)
|
|
What is the wire designator for the Exhuast/Comparative Enthalpy Module?
|
1U52 (ECEM)
|
|
What is the wire designator for the Generic Building Automation System Module?
|
1U51 (GBAS)
|
|
What is the wire designator for the Supply Air Sensor?
|
3RT9
|
|
What is the wire designator for the Return Air Sensor?
|
3RT6
|
|
What is the wire designator for the Entering Evaporator Temperature Sensor?
|
3RT28 & 3RT29
|
|
What is the wire designator for the Leaving Evaprator Temperature Sensor?
|
3RT14 & 3RT15
|
|
What is the wire designator for the Filter Switch?
|
3S21
|
|
What is the wire designator for the Supply and exhaust/return airflow proving switch?
|
3S68 & 3S69
|
|
What is the wire designator for the Supply and Exhaust/Return Fan Circuit Breaker?
|
1CB1 , 1CB2
|
|
What is the wire designator for the Saturated Condenser Temperature?
|
2RT1 and 2RT2
|
|
What is the wire designator for the Outdoor Air Humidity Sensor?
|
3U63
|
|
What is the wire designator for the Return Air Humidity Sensor?
|
3U64
|
|
What is the wire designator for the Space/Duct Humidity Sensor?
|
5U108
|
|
What is the wire designator for the Space Pressure Transducer?
|
3U62
|
|
What is the wire designator for the Compressor Motor Windings Thermostats?
|
2B7S1,2B17S2,2B27S5,2B8S3,2B18S4,2B28S6
|
|
What is the wire designator for the Freezestat?
|
4S12
|
|
What is the wire designator for the High Duct Temp Thermostats?
|
3S16,3S17
|
|
What is the wire designator for the Compressor Circuit Breakers?
|
1CB8,1CB9,1CB10,1CB11 1CB14,1CB15,1CB16,1CB17
|
|
Device prefix location code 1 is in what area?
|
INSIDE UNIT CONTROL BOX
|
|
Device prefix location code 2 is in what area?
|
CONDENSER SECTION
|
|
Device prefix location code 3 is in what area?
|
AIR HANDLER SECTION
|
|
Device prefix location code 4 is in what area?
|
HEATING SECTION
|
|
Device prefix location code 5 is in what area?
|
EXTERNAL FIELD MOUNTED DEVICE
|
|
What is the voltage used by the Generic Buildung Automation System Module?
|
0-5 or 0-10 vdc
|
|
Where does the Multipurpose Module get its information to control the return fan static setpoint?
|
Return Plenum Pressure Sensor
|
|
Where does the Supply Air Temperature Sensor connect to control supply air temp,reset,low limt,and tempering?
|
The RTM(1U48)
|
|
When the Return Air Temp Sensor is used with a humidity sensor to control enthalpy on CV&VAV units it is connected to the ?
|
Exhaust Comparitive Enthalpy Module(1U52)
|
|
Where does the Entering and leaving Evaporator temp sensors connect when used as a low charge protection?
|
SCM & MCM(1U49)
|
|
This sensor is attached to the 1U49 mudule and is used to prevent the coil from freezing up and is set for 30 deg from the factory?
|
Leaving evaporator temp sensor (3RT14,3RT15)
|
|
How long do you have to wait for the compressor to be allowed to stage on after a possible freeze has been detected?
|
Coil temp rizes 10 deg above freeze setpoint and a three minute off timer has elapsed..
|
|
What module is the filter switch(3S21) connected to so that a diagnostic service signal is sent if the filters get cloged?
|
RTM(1U48)
|
|
Where are the Supply and Exhaust /Return airflow switches attached to give alerts that the fan is operating?
|
RTM(1U48)
|
|
Durring fan operation the airflow proving switch is open consecutively for more than 40 sec the compressors are allowed to come on if there is a call for cooling? True / False
|
False
|
|
What switch located in the control cabinet is used to cycle power to the RTM?
|
1S70
|
|
This is the selectable mode on 40-130 ton units that alternates the first starting compressor on each bank?
|
Lead Lag
|
|
What module is the Return Plenum Pressure High Limit sensor connected to?
|
RTM(1U48)
|
|
What is the operating pressures of the Low Pressure Control?
|
22+/- 4psig closes and opens at 7+/- 4psig
|
|
What is the minimum off time for a low pressure cutout alarm?
|
3 Minutes
|
|
What module is the Low Pressure Cutout Control sensor connected to?
|
SCM/MCM(1U49)
|
|
What module is the Saturated Condenser Temp Sensor wired to?
|
SCM\MCM(1U49)
|
|
What module stages the condenser fans on to maintain the proper saturation temp?
|
SCM/MCM(1U49)
|
|
At what pressures does the High Pressure Switch shut down the compressors and what pressure does the HPS reset?
|
405+/-7psig and resets at 300+/-20psig
|
|
What module is the Outdoor Humidity Sensor(3U63) wired to?
|
RTM(1U48)
|
|
What module is the Return Air Humidity Sensor wired to?
|
ECEM(1U52)
|
|
At what temperature does the Low Ambient Compressor Lockout allow the compressor to run?
|
5 degrees above lockout set point
|
|
What module does the Space Pressure Transducer send its signal?
|
ECEM(1U52)
|
|
What is the name of the analog device used on Intelipacks to maintain the building static pressure along with Statitrack?
|
Space Pressure Transducer(3U62)
|
|
What module does the Compressor Motor Windings Thermostats send its signal?
|
SCM/MCM(1U49)
|
|
At what temperature does the compressor motor windings thermostat open and what temperature does it close?
|
221 degrees it opens and 181 degrees it closes
|
|
What is the name of the binary input device that prevents coil freeze up in units with Hydronic Heat?
|
Freezestat
|
|
When the heating coil reaches 40 degrees the freezestat opens and sends the signal to the Heat Module(1U50)? True/False
|
False (closes)
|
|
What module does the High Duct Temp Thermostat connect to?
|
TCI(1U54)
|
|
What is the temperatures that trip the High Duct Temp Thermostats on Intellipaks?
|
240 degrees on the supply and 135 degrees on the return
|
|
What module does the Compressor Circuit Breakers connect to?
|
SCM(1U49)
|
|
With Intellipaks what does the acronym BCI module stand for?
|
Bacnet Communication Interface Module
|
|
With Intellipaks what does the acronym CV stand for?
|
Constant Volume
|
|
With Intellipaks what does the acronym ECEM stand for?
|
Exhaust/Comparative Enthalpy Module
|
|
With Intellipaks what does the acronym GBAS stand for?
|
Generic Building Automation System
|
|
With Intellipaks what does the acronym HGBP stand for?
|
Hot Gas Bypass
|
|
With Intellipaks what does the acronym HI stand for?
|
Human Interface
|
|
With Intellipaks what does the acronym IGV stand for?
|
Inlet Guide Vanes
|
|
With Intellipaks what does the acronym IPC stand for?
|
Interprocessor Communications Bridge
|
|
With Intellipaks what does the acronym LCI-I stand for?
|
Lontalk Communication Interface for Intellipaks
|
|
With Intellipaks what does the acronym MCM/SCM stand for?
|
Multi and Single Compressor Module
|
|
With Intellipaks what does the acronym MPM stand for?
|
Multipurpose Module
|
|
With Intellipaks what does the acronym MWU stand for?
|
Morning Warm Up
|
|
With Intellipaks what does the acronym NSB stand for?
|
Night Set Back
|
|
With Intellipaks what does the acronym RTM stand for?
|
Rooftop Module
|
|
With Intellipaks what does the acronym TCI stand for?
|
Tracer Communication Interface module
|
|
With Intellipaks what does the acronym UCM stand for?
|
Unit Control Module
|
|
With Intellipaks what does the acronym VAV stand for?
|
Variable Air Volume
|
|
With Intellipaks what does the acronym VCM stand for?
|
Ventilation Control Module
|
|
With Intellipaks what does the acronym VOM stand for?
|
Ventilation Override Module
|
|
What is the resistance input to the RTM to get a setpoint of; 75deg, 70deg, 65deg ?
|
403, 500, and 597 ohms
|
|
If you are installing an Intellipak that has four condensate pipe connections you do not have to use all four? True/False
|
False
|
|
What is the recommended wire size for a control run from an Intellipak to its controller that is 5-460 feet away?
|
18 Gauge
|
|
What is the recommended wire size for a control run from an Intellipak to its controller that is 461-732 feet away?
|
16 Gauge
|
|
What is the recommended wire size for a control run from an Intellipak to its controller that is 733-1000 feet away?
|
14 Gauge
|
|
It is not ok to run low voltage wire with high voltage wire? True/False
|
True
|
|
On control wiring you should ensure that the resistance does not go over _____ ohms/conductor for the length of the run?
|
2.5 ohms
|
|
What is the wire designator for the Duct Pressure Transducer?
|
3U60
|
|
What is the wire designator for the Return Pressure Transducer?
|
3U106
|
|
What is the wire designator for the Space Calibration Solenoid?
|
3L21
|
|
What is the wire designator for the Return Plenum Calibration Solenoid?
|
3L24
|
|
Natural Gas Regulating Valve pressure must not exceed _____" w.c?
|
14
|
|
Natural gas pressure must not fall below ____"w.c. for proper operation of burners.
|
7
|