What is the wire designator for the compressor module?
1U49 (SCM-MCM)
What is the wire designator for the Human Interface module?
1U65 (HI)
What is the wire designator for the HeatModule?
1U50
What is the wire designator for the Ventilation Overide Module?
1U53 (VOM)
What is the wire designator for the Interprocessor Comunication Board?
1U55 (IPCB)
What is the wire designator for the Trane Communication Interface Module?
1U54/1U104 (LCI/BCI)
What is the wire designator for the Exhuast/Comparative Enthalpy Module?
1U52 (ECEM)
What is the wire designator for the Generic Building Automation System Module?
1U51 (GBAS)
What is the wire designator for the Supply Air Sensor?
3RT9
What is the wire designator for the Return Air Sensor?
3RT6
What is the wire designator for the Entering Evaporator Temperature Sensor?
3RT28 & 3RT29
What is the wire designator for the Leaving Evaprator Temperature Sensor?
3RT14 & 3RT15
What is the wire designator for the Filter Switch?
3S21
What is the wire designator for the Supply and exhaust/return airflow proving switch?
3S68 & 3S69
What is the wire designator for the Supply and Exhaust/Return Fan Circuit Breaker?
1CB1 , 1CB2
What is the wire designator for the Saturated Condenser Temperature?
2RT1 and 2RT2
What is the wire designator for the Outdoor Air Humidity Sensor?
3U63
What is the wire designator for the Return Air Humidity Sensor?
3U64
What is the wire designator for the Space/Duct Humidity Sensor?
5U108
What is the wire designator for the Space Pressure Transducer?
3U62
What is the wire designator for the Compressor Motor Windings Thermostats?
2B7S1,2B17S2,2B27S5,2B8S3,2B18S4,2B28S6
What is the wire designator for the Freezestat?
4S12
What is the wire designator for the High Duct Temp Thermostats?
3S16,3S17
What is the wire designator for the Compressor Circuit Breakers?
1CB8,1CB9,1CB10,1CB11 1CB14,1CB15,1CB16,1CB17
Device prefix location code 1 is in what area?
INSIDE UNIT CONTROL BOX
Device prefix location code 2 is in what area?
CONDENSER SECTION
Device prefix location code 3 is in what area?
AIR HANDLER SECTION
Device prefix location code 4 is in what area?
HEATING SECTION
Device prefix location code 5 is in what area?
EXTERNAL FIELD MOUNTED DEVICE
What is the voltage used by the Generic Buildung Automation System Module?
0-5 or 0-10 vdc
Where does the Multipurpose Module get its information to control the return fan static setpoint?
Return Plenum Pressure Sensor
Where does the Supply Air Temperature Sensor connect to control supply air temp,reset,low limt,and tempering?
The RTM(1U48)
When the Return Air Temp Sensor is used with a humidity sensor to control enthalpy on CV&VAV units it is connected to the ?
Exhaust Comparitive Enthalpy Module(1U52)
Where does the Entering and leaving Evaporator temp sensors connect when used as a low charge protection?
SCM & MCM(1U49)
This sensor is attached to the 1U49 mudule and is used to prevent the coil from freezing up and is set for 30 deg from the factory?
Leaving evaporator temp sensor (3RT14,3RT15)
How long do you have to wait for the compressor to be allowed to stage on after a possible freeze has been detected?
Coil temp rizes 10 deg above freeze setpoint and a three minute off timer has elapsed..
What module is the filter switch(3S21) connected to so that a diagnostic service signal is sent if the filters get cloged?
RTM(1U48)
Where are the Supply and Exhaust /Return airflow switches attached to give alerts that the fan is operating?
RTM(1U48)
Durring fan operation the airflow proving switch is open consecutively for more than 40 sec the compressors are allowed to come on if there is a call for cooling? True / False
False
What switch located in the control cabinet is used to cycle power to the RTM?
1S70
This is the selectable mode on 40-130 ton units that alternates the first starting compressor on each bank?
Lead Lag
What module is the Return Plenum Pressure High Limit sensor connected to?
RTM(1U48)
What is the operating pressures of the Low Pressure Control?
22+/- 4psig closes and opens at 7+/- 4psig
What is the minimum off time for a low pressure cutout alarm?
3 Minutes
What module is the Low Pressure Cutout Control sensor connected to?
SCM/MCM(1U49)
What module is the Saturated Condenser Temp Sensor wired to?
SCM\MCM(1U49)
What module stages the condenser fans on to maintain the proper saturation temp?
SCM/MCM(1U49)
At what pressures does the High Pressure Switch shut down the compressors and what pressure does the HPS reset?
405+/-7psig and resets at 300+/-20psig
What module is the Outdoor Humidity Sensor(3U63) wired to?
RTM(1U48)
What module is the Return Air Humidity Sensor wired to?
ECEM(1U52)
At what temperature does the Low Ambient Compressor Lockout allow the compressor to run?
5 degrees above lockout set point
What module does the Space Pressure Transducer send its signal?
ECEM(1U52)
What is the name of the analog device used on Intelipacks to maintain the building static pressure along with Statitrack?
Space Pressure Transducer(3U62)
What module does the Compressor Motor Windings Thermostats send its signal?
SCM/MCM(1U49)
At what temperature does the compressor motor windings thermostat open and what temperature does it close?
221 degrees it opens and 181 degrees it closes
What is the name of the binary input device that prevents coil freeze up in units with Hydronic Heat?
Freezestat
When the heating coil reaches 40 degrees the freezestat opens and sends the signal to the Heat Module(1U50)? True/False
False (closes)
What module does the High Duct Temp Thermostat connect to?
TCI(1U54)
What is the temperatures that trip the High Duct Temp Thermostats on Intellipaks?
240 degrees on the supply and 135 degrees on the return
What module does the Compressor Circuit Breakers connect to?
SCM(1U49)
With Intellipaks what does the acronym BCI module stand for?
Bacnet Communication Interface Module
With Intellipaks what does the acronym CV stand for?
Constant Volume
With Intellipaks what does the acronym ECEM stand for?
Exhaust/Comparative Enthalpy Module
With Intellipaks what does the acronym GBAS stand for?
Generic Building Automation System
With Intellipaks what does the acronym HGBP stand for?
Hot Gas Bypass
With Intellipaks what does the acronym HI stand for?
Human Interface
With Intellipaks what does the acronym IGV stand for?
Inlet Guide Vanes
With Intellipaks what does the acronym IPC stand for?
Interprocessor Communications Bridge
With Intellipaks what does the acronym LCI-I stand for?
Lontalk Communication Interface for Intellipaks
With Intellipaks what does the acronym MCM/SCM stand for?
Multi and Single Compressor Module
With Intellipaks what does the acronym MPM stand for?
Multipurpose Module
With Intellipaks what does the acronym MWU stand for?
Morning Warm Up
With Intellipaks what does the acronym NSB stand for?
Night Set Back
With Intellipaks what does the acronym RTM stand for?
Rooftop Module
With Intellipaks what does the acronym TCI stand for?
Tracer Communication Interface module
With Intellipaks what does the acronym UCM stand for?
Unit Control Module
With Intellipaks what does the acronym VAV stand for?
Variable Air Volume
With Intellipaks what does the acronym VCM stand for?
Ventilation Control Module
With Intellipaks what does the acronym VOM stand for?
Ventilation Override Module
What is the resistance input to the RTM to get a setpoint of; 75deg, 70deg, 65deg ?
403, 500, and 597 ohms
If you are installing an Intellipak that has four condensate pipe connections you do not have to use all four? True/False
False
What is the recommended wire size for a control run from an Intellipak to its controller that is 5-460 feet away?
18 Gauge
What is the recommended wire size for a control run from an Intellipak to its controller that is 461-732 feet away?
16 Gauge
What is the recommended wire size for a control run from an Intellipak to its controller that is 733-1000 feet away?
14 Gauge
It is not ok to run low voltage wire with high voltage wire? True/False
True
On control wiring you should ensure that the resistance does not go over _____ ohms/conductor for the length of the run?
2.5 ohms
What is the wire designator for the Duct Pressure Transducer?
3U60
What is the wire designator for the Return Pressure Transducer?
3U106
What is the wire designator for the Space Calibration Solenoid?
3L21
What is the wire designator for the Return Plenum Calibration Solenoid?
3L24
Natural Gas Regulating Valve pressure must not exceed _____" w.c?
14
Natural gas pressure must not fall below ____"w.c. for proper operation of burners.
7