what is the greatest advantage of hydronic heating over any other system?

multiple zoning

which floor covering has the greatest R Value?

carpet and underlay

what can affect a way a house in zoned?

north and south exposures

which three factors must be known in order to properly size tubing for an application?

GPM


Velocity


length of circuit

what two factors must you know in order to determine floor surface temperature?

btus per square foot


and


room temperature

when installing tubing in a radient floor heating system the water temperature at the beginning of the circuit is the highest. which area of the room should the beginning of the circuit be installed?

in the areas with the greatest heat loss

double wall serpentine is best suited to which one of the following applications?

two adjacent walls that are exposed to the outside

is insulation required below a poured in concrete application?

code requires installation below poured in concrete applications

what is the minimum pressure test on tubing in radient floor heating?

the greater of either 60 psi or 1.5 times the working pressure for a period of 1 hr with no pressure drop

when are supplemental heating units installed in radient floor heating systems?

when the radient floor goes not keep up with the heat load

what two factors are required to calculate header size?

GPM and Velocity

why are zone valves required in a system?

to stop and start flow in the system as required

what is required when piping a low mass boiler that is flow sensitive?

a bypass pump between the supply and return boiler piping

what is required when a conventional boiler is installed in a low temperature radient floor heating system?

a mixing valve

what function does a 3 way or 4 way valve perform in a hydronic heating system?

mixes water from the heat source and the system return in order to temper system water supply

what must be installed with a three way or four way mixing valve in order to protect the heat source and the radient floor system?

a drive motor and controller

what should be installed to separate the boiler water and the system water when glycol is added to the water in a radient floor heating system?

a plate heat exchanger

what is required when a variable speed injection pump is installed in a two temperature system?

a controller for the pump