Threaded schedule 40 gas pipe has a pressure rating of?

125 psi. Pounds per square inch.

125 ,pounds per square inch for gas.

Malleable fittings, class 150. What's the. Pounds per square inch ,what's the rating.

125, pounds per square inch.

Steel fittings class 300, what's the PSI rating.

300 ,pounds per square inch.

What is the pressure rating, for All Copper fittings, on gas lines.


125, pounds per square inch.


For high-pressure gas ,over 125 p,s,i. All fittings must be rated for 250, p,s,i.

When using compression fittings, Farrell's must have, A double _______ not A single.

Double ferrules. Not single

K , L ,& G, are approved for above-ground use for gas.


What is approved for, underground use, in Copper.

K is approved for underground. L,&,G are approved for ,underground if they have their, Factory PVC coating.

There's only one type of plastic pipe ,approved for gas lines what is it.

Polyethylene plastic, p, e, is used for outdoors, underground only must connect to a ,steel riser for transition to inside a building, with the special transition fitting, Fusion is the preferred method, of joining plastic pipe together. although compression fittings are acceptable.

Flexible rubber gas hoses are rated for what PSI of working pressure.

350 pounds per square inch

The maximum length of a hose for a permanent installation is.

10 feet, or 3,meters.

The minimum length , and maximum length, of a hose for construction heater is.

15, feet minimum, 75, feet maximum.

The maximum length, of a hose for portable, Appliance / BBQ is.

30 feet, or 9.5, meters.

Can you pass a gas line hose, from one wall to another.

No is it against the law.

What is the max temperature a ,gas hose should be subject to.

125, degrees Fahrenheit or, 50 degrees Celsius.

A radiant tube heater must have a gas hose of which length.

36 inch plus or minus 6 inches. Must have a 12in curve in the hose, to absorb fluctuations.

Iron malleable pipe hanger spacing 4 horizontal pipe. What is hanger, spacing for. Half-inch. Three quarters of an inch to 1 inch.


1 and one quarter inch,too


Two and a half inch.


1/2",Half inch, 6 feet or 2 meters.


3/4",to1"Three quarters of an inch ,to


1inch,8,feet,or 2.5,meters.


11/4",to,2", 1 and a quarter inches, to, 2 inch, 10 feet, or 3 meters.


Vertically supported gas, pipe 1 and 1/4 inches or larger, and, tubing sizes horizontal or vertical. All sizes. What's the spacing.

One and a quarter inch or larger ,vertical ,every floor but no more than, 125% of the horizontal spacing.


Tubing all sizes, horizontal or vertical, 6 feet or 2 meters.

What's the max length ,of a flex connector, on an unvented appliance.


I e / gas dryer. Gas stove. Etc

Max length of the flex connector is 6 feet.

A vented Appliance ,can have a Max Flex connector length of.

2 feet.

When using a quick connect, for a barbecue ,what must be directly Upstream of that quick connect.

A gas cock. For emergency shut-off and on and off use.

When a gas line sticks through, the ceiling or through the wall, or through the floor ,what is the minimum depth, not including the threads.

Through the ceiling or, through the wall it is 1 inch minimum, not including the threads.


When it comes up through ,a floor it is 2 in minimum not including the threads.

What's the minimum depth of a buried gas line.

15 inches,or 400, millimeters.


What's the minimum buried depth on a, commercial gas line. Where the ,gas lines Traverse a driveway, parking lot ,or Farm installations.

A minimum of 24 in Love cover.

When a gas line travels 25 feet or more ,horizontally what is required.

A vent / inspection point,


In case there is a, possible leak underground it will ,vent safely.

When you are transitioning, from plastic underground, gas pipe. To steal gas pipe, how close to the, premises and the transition joint, be made.

Must be at least 15, feet or 4.6 meters from any building.

Identifying gas piping lines. Commercial building, Gas pipe can ,be painted yellow. Banding or markings, stating the pressure the nature ,of the product should be ,at what intervals.

There must be a yellow band every 20 feet or 6, meters. There must be a natural gas or propane marking every 20 feet or 6, meters.

In a residence what are the intervals, of marking gas pipe or, copper gas pipe.

Standard black iron pipe, does not need to be marked, in a residential situation. Copper pipe must be ,marked every 6 ft.

The gas cock can be placed, on the horizontal in residential piping ,if it's within?

2 feet of the appliance.

What is the max distance a gas cock can be ,placed in a residence.

Up to 50 feet away, or 17, meters as long as it is accessible ,and clearly tagged.

Supporting roof gas line, and tubing ,what are the support distances.

Piping must be supported at every threaded joint. Tubing must be supported its entire length.

When installing an appliance in a, residential garage what are the clearances.

Must be installed a minimum of 18in above the floor.

When installing an appliance in a commercial garage what are the clearances.

No less than 4.5 feet from the floor. I shall be protected from damage.

What is the minimum ,test time in pressure ,for A low pressure gas line. 200 ft or less ,and 200 feet and over.

15 PSIG, for 15 minutes.


The test gauge face must be a minimum of 3 in diameter.



For more than 200 ft ,15 psi for 60 minutes.

What's the test pressure, and time for . Over 2, pounds per square inch, but not more than 33, pounds per square inch.


200 feet or less, in length. Over 200 feet in length.

50 psi 460 minutes 4 under 200 feet. More than 200 ft 50 psi for 180 minutes.

Pressure and time test for over 33 pounds per square inch gas line or welded pipe. What's the pressure ,and time.

Over 33 PSI the test will be for, 1.5, times the max operating pressure, 180 minutes.


Welded pipe 50 psi or 1.5 times the maximum, operating pressure for, 180 minutes.

Low pressure gas line sizing. General formula.

Find the BTU load for all your appliances. Find the longest run. Go to the correct chart, and size everything from the longest run and BTU load line.