Schedule 40 pipe is rated for a max of what psi?

125psi

Can copper used for gas be soldered?

No. Only flared, brazed or compression. Compression must be double ferrule system

What coppers can be used for gas lines?

Type K,L and G. L and G must be coated with PVC resin or extruded polyethylene

What kind of plastic can be used for gas?

Polyethylene. Fused or compression

Polyethylene pipe must be installed with what when underground?

Tracer wire

Minimum rated working pressure for a hose and hose fittings?

350psi (2400kpa)

Max length of hose on a permanent installation?

10 feet

If there is less then 1 3/4 clearance from finished wall and gas tight what must be installed?

16 gauge protection plates

Steel bushings may reduce one or more sizes but malleable bushings must reduce?

Two or more sizes


Max length of flex connector on a vented appliance and unvented appliance?

2 feet and 6 feet

Why should plastic pipe underground be snaked?

Allows for contraction and settling

All gas lines should to be buried at depth underground?

15". 24" for driveways

Density of propane and gas?

1.5 and 0.6

Additional appliances may be installed within how many feet of the meter outlet?

2 feet or 2 feet of secondary reg on propane line

Minimum pressure test requirements for low pressure gas line?

15 psi for 15 mins. 15psi for 60 mins over 200' of pipe

Finish piping must be tested at?

Working pressure for 10 mins

A purge on a gas line should be how far from any building or air intake?

10'

How must a 4" or bigger gas line be purged?

Using an inert gas usually carbon dioxide

All welded gas pipe will be tested for?

50 psi or 1.5 times max operating pressure for 180 minutes

When can a dual stage regulator be used on a propane install?

Only for temporary installs

Can a second stage regulator set at 11" WC be used to supply a 2 psi gas pressure?

Yes

Every hose and hose fittings shall have minimum pressure rating of?

350psi

A defective section of gas pipe or tubing may be repaired by a qualified gas fitter?

False

A corrugated metal connector shall not exceed 2' in length when?

Connecting a suspended appliance

How far is the valve from purge point?

No more then 5 feet

Underground piping approved for direct burying? (No protection or coating)

Type K copper tubing

Min bury depth under commercial driveway?

24 inches

When installing PE plastic pipe underground is shall have what buried with it?

Tracer wire

Final test preformed on a piping system?

10 mins at working pressure

A branch piping outlet (future outlet) installed on main supply must be what size?

Full size

When a fabricated tee is used to provide an outlet on a 3 inch gas line, it is sized?

No larger then 50 percent of supply pipe and no smaller then 3/4

Max pressure for CH4 in an industrial building?

66psi

Other then a building under construction, max pressure for C3H8 in piping system?

20psi

When sizing 2psi gas lines, TFD allowance must be added?

No. Only 5psi

Cathodic protection is used to prevent damage to a gas line from?

Galvanic action

Pressure gauge for testing a standard residential gas line should have a max pressure reading of?

60psi

When should you purge a gas line?

After every test with air and before a gas line is dismantled for repair

What will cause a manual re-set type of regulator to drop out?

Closing upstream valve and opening the downstream valves

How many 90 degree elbows are used in war is know as 3 elbow swing joint?

3

Gas leaking from regulator vent could indicate that something on the seat is preventing it from closing?

Yes

Replacing a piece of 1/2 schedule 40 piping with a piece of 1/2 schedule 80 would cause?

Reduction in operating pressure at the appliance

System regulator should be tested to a maximum of what pressure?

Working pressure

Underground piping is often snaked before back filling why?

Contraction and expansion

A gas line from a house to detached garage would require how many gas cocks?

3. 1 leaving house, 1 entering garage and 1 at the appliance

Best type of sling to lift 2" schedule 40 pipe?

2 leg choker sling

Flow rate in 1" steel pipe supplying 200cfh at 7" WC and 1" pipe supplying 75cfh at 7" WC. would pressure be at first pipe more or less?

More then

Fittings with left hand threads may be used on a propane gas piping where?

On outlet of a cylinder

The installation of natural gas regulator fall under the B-149gas code when they are?

Downstream of the meter and supplied as part of the appliance

What is included as part of the total equivalent length in high pressure gas system?

Shut off valve at second stage regulator and fittings

In a 2psi gas system the max pressure drop allowed is?

1.5psi

If a gas meter needs to be changed, what should be done?

Notify the owner

Incomplete combustion will produce?

CO, CO2 and H2O

What kind of pipe cannot be used above ground?

Plastic PE pipe

Before dismantling any gas line you should?

Shut off gas, shut off appliance power supply and purge

Every hose and fitting must be rated for what minimum working pressure?

350psi

Copper gas line is residential must be marked with yellow bands every?

6 feet

Largest component of natural gas is ?

Methane

The term volatile in gas fitting trade is used in reference to?

How easy gas mixes with air

Mercaptan is added to gas to?

Increase safety in handling

What gas is almost never handled as a liquid by a gas fitter?

Natural gas CH4

The UEL of natural gas is?

15 percent

2 gallons of propane liquid would weigh?

10 pounds

Natural gas has density of?

.60

Max pressure an appliance gas control valve can be subject to?

.5psi or 14" WC or 8 OSI

2psi. It's before the regulator

Max length of corrugated metal flex connector permitted on a vented appliance and unvented appliance?

2 feet and 6 feet

Second stage regulator on propane line is set to what water column?

11" WC but can be adjusted to supply 2 psi gas pressure

Max pressure drop on 2psi systems?

1.5psi, 75 percent

Can an appliance under 400MBH have its gas line purged to the burner?

Yes but the burner cannot be inside of a combustion chamber

Natural gas requires how much cubic feet of air to burn 1 cubic feet of gas?

10 cubic feet

Propane requires how much cubic feet of air to burn 1 cubic feet of gas?

24 cubic feet

What kind of wiring diagram is most widely used?

Ladder diagram

What does a "relay" do?

Opens and closes a set of electrical contacts and is activated by a coil

What does a "contactor" do?

Same as relay but works with larger current rating. 20 amps or larger

How does low limit switch work?

Low limit will open (turn off) if temperature drops below 40 degrees Celsius

Volts are?

Pressure

Amps are?

Current

Ohms are?

Resistance

Series circuit?

One path and most likely one load controlled by switch or series of switches

Parallel circuit

More than one path with most likely having one load or path. Voltage drop across each load with be the same

Series parallel?

Combination of the two, within that circuit the loads wired in parallel and switching devices in series

What does a rod and tube thermostat sense?

Liquid

What does a bimetal thermostat sense?

Air temperature change

What does a heat anticipator do?

Designed to prevent system lag or temperature overshoot

Where is a diaphragm and solenoid gas valve located?

Downstream of 100 percent shut off valve and the appliance regulator

A direct fired makeup air heater cannot be installed in?

A space that doesn't have a exhaust fan

A stationary gas engine (generator) must have exhaust connected too?

Separate high temp chimney or exhaust

Swimming pool heaters must have what kind of base?

Non combustible