heat pumps that use R- 410A should be leak check with

pressurized nitrogen

Heat pumps that have been retrofitted from R-22 to R-407c should be leak checked with

pressurized nitrogen

To change the compressor on a system containing R -410A you must isolate the compressor then

Evacuate the isolated section of the system to atmospheric pressure and hold if system pressure does not rise remove the compressor

the method to change a system that has a normal charge of 80 pounds is to charge with

Liquid through the liquid line service valve

After installation of a field piped R- 410A split heat pump the unit should first be

Pressurized with nitrogen then leak checked

Pressure relief valves must not be

Installed in series

When charging an R12 refrigeration system that uses a water-cooled condenser you must first charged with Vapor to a pressure of at least ______before switching to liquid charging

35 PSIG

Your recovery recycling machine has R22 refrigerant in it you now have to recover refrigerant from a unit with R-410A what must be done before your recovery unit can be used to recover R- 410A?

the recovery unit must be EPA certified for us with r 410 a the recovery tank must be designed for the pressure of R 410 a the filter and lubricant in the recovery unit must be charged and the recovery unit evacuated( all of the above )

After reaching the required recovery vacuum on a system you must

Wait to see if the system pressure Rises indicating that there is still refrigerant in liquid form or refrigerant trapped in the oil

In a refrigeration system the component directly following the evaporator is the

Accumulator

A reciprocating compressor should not be energized

The discharge service valve is closed

R410a requires a high pressure manifold gauge and hose that they must have a

4000 PSIG burst pressure 800 PSIG working pressure

The refrigerant pressure inside an R 410 a unit which is at room temperature and not operating is

Approximately 210 PSIG

Every air conditioning and refrigerating system should be protected by a

Pressure relief device

To charge the compressor on a system containing 40 pounds R- 500 using a recycling machine that was manufactured AFTER November 15th 1993 you must isolate the compressor then

Evacuate the isolated section of the system to 10 inches of vacuum and hold if system pressure does not rise remove the compressor

When inspecting a system for leaks you should look for

Traces of oil

When a new system has been assembled the first thing to do is

pressurize the system with an inert gas and leak check

R-410A is different from other ASHRAE 400 series non azeotropic blends because

R-410A behaves as a near azeotropic refrigerant and can be topped off

Manifold gauge set hoses should have self-sealing connectors or hand valves to

Minimize the release of refrigerant when the hoses are connected and disconnected

When using recovery or recycling equipment that was manufactured AFTER November 15th 1993 must evacuate a system containing MORE than 200 pounds of CFC 12 to_____ before making a major repair

15 inches of HG vacuum

With an air-cooled condenser on the roof of a building in the evaporator on the first floor recovery should first occur

From the liquid line entering the evaporator

Never use oxygen or compressed air to leak check Hardware because R 410A can

Explode when mixed with air or oxygen

Dry nitrogen should be used to break the first vacuum when dehydrating by the double evacuation method however it

Can be dangerous if not used with a pressure regulator

A recovery machine that uses a hermetic compressor will overheat when drawing a deep vacuum because

The motor needs the flow of refrigerant through the compressor to provide motor Cooling

The proper charging method for Blended non isotropic refrigerant 400 series is to use a remove the charge from the cylinder as a

Liquid

When a refrigerant Trace gas becomes absolutely necessary which of the available refrigerant should be used to identify a leak?

HCFC-22

After refrigerant liquid has been removed from a system any remaining vapor is

Condensed by the recovery system

an oil sample should be taken when

the compressor has a burnout

In a refrigeration system with a TXV or other type of throttling device the component directly following the condenser is the

Receiver

Recovered refrigerant may contain which of the following?

Acids moisture & oils (all of the above )

The back seating of a suction shutoff valve will close the

Gauge port

Which repair would always be considered major under EPA's regulations?

Replacement of an evaporator coil

R410a require Certified Recovery and recycling machines rated for at least

400 PSIG

A compressor heater is used to

Reduce the amount of refrigerant in the lubricating oil

Your recovery recycling machine has r502 refrigerant in it you now have to recover refrigerant from a unit with R22 what must be done before the R-22 refrigerant can be recovered recycled?

Recover as much of the r502 from The Recovery Unit as possible change filter and evacuate

The faster way to recover refrigerant from a system is to remove it in the _____ phase?

Liquid

Before using every covery unit to remove a charge what steps should be taken

Check service valve positions check the oil level in The Recovery Unit evacuate Recovery Unit and recovery tank(all of the above )

A deep vacuum is usually measured in

Microns

Before transferring refrigerant to an empty cylinder?

The cylinder should be evacuated to avoid mixing air with the recovered refrigerant

To recover liquid refrigerant you must connect one hose to the

Liquid line

A system can be evacuated to only atmospheric pressure when

Leaks in the Appliance make evacuation to the prescribed level unattainable

A system can be evacuated to only atmospheric pressure when

Leaks in the Appliance make evacuation to the prescribed level unattainable

The vacuum pump used to evacuate a system should be capable of pulling a vacuum of

500 microns

While r410a is a high pressure refrigerant it can be stored in the back of your service van as long as

The temperature inside the vehicle does not exceed 125F this is the same guidance given for R22 and other common refrigerant

When under a deep vacuum the motor winding of a hermetic Refrigeration compressor

Will overheat only if the crankcase heater is energized

Which statement is not true about Recycling and Recovery equipment manufactured after November 15th 1993?

it must have an oil separator

When are you getting it is opened for servicing the______ should always be replaced

Filter drier

When servicing an operating unit that has a receiver storage tank the

Refrigerant should be recovered into the receiver

Use_____ to remove ice from a sight glass

An alcohol spray

The refrigerant pressure inside an R12 unit which is at room temperature and not operating is

Approximately 74 PSIG

You are going to service a newer residential split system air conditioner you would expect to find the system charged with which refrigerant?

R-410A

A routine maintenance tasks which must be performed on refrigerant recycling machines is to

Change filter in compressor oil (if any)

refrigerant should be removed from the condenser Outlet if the

condenser is below the receiver

when evacuating a system the use of a large vacuum pump could

cause trapped water to freeze

On refrigeration units that use an open compressor the_____ is most likely to leak if the unit is not used for several months

Rotating shaft seal

The primary water source for cooling the condenser of a water cooled Recovery Unit is

local Municipal Water Supply

when using recovery and recycling equipment manufactured BEFORE November 15th 1993 technicians must evacuate a unit that has a normal charge of 10 pounds of CFC 500 to ______ before disposing of the system

4 inches of Hg vacuum

the evaporation temperature of R 410A at 100 PSIG is about

30°F

Noncondensables in a system cause a

Higher discharge pressure

R 410 A requires recovery tanks rated for at least

400 PSIG

The recovery rate can be increased by

Packing the recovery vessel in ice

Oil foaming usually occurs in the

Compressor

During the evacuation of a system that contains large amounts of moisture it may be necessary to increase pressure in the system with_____ to counteract the freezing of the moisture

Nitrogen

Prior to replacing the condenser coil in a high pressure system the refrigerant was recovered and stored in a refillable cylinder the refrigerant

can probably be charged back into the system

The evaporation temperature of R134a at 0 PSIG is

-15°F

The EPA regulations require that any appliances containing more than 50 pounds of refrigerant except for commercial and Industrial process Refrigeration must be repaired when the leak rate exceeds_____ of the charge per year

15%

The EPA regulations require that leaking commercial or industrial process Refrigeration equipment must be repaired when the leak rate exceeds_____ of the charge per year

35%

You are going to service an older residential split system air conditioner you would expect to find the system charged with which refrigerant

R-22

For what refrigerant is an equipment room Refrigeration monitor required under ASHRAE standard 15?

R-123

Heat pumps that use R134A should be leak checked with

Pressurized nitrogen

On a high pressure system______ is an indicator of a possible leak

excessive super heat

system dependent recovery equipment cannot be used with

Appliance contains over 15 pounds of refrigerant

moisture is removed from a system by

using a filter drier

which component is not part of the low side of the system

Receiver

Soap bubble testing is used

To pin point refrigerant leaks

Refrigerant leaves the receiver of a system as a

High pressure liquid

The recovery of refrigerant from a system as a vapor only will minimize the loss of

Oil