What is the procedure to archive the NERC CPS information for auditing purposes?
1. Go to the savecase directory.
2. Select RTGEN.
3. On the textbox type "ECCF_PROD_ARCHIVE_YYYYMMDD"
4. Click "save" right besides the NERCCPS label.
Is is posible to read the content of the NERC CPS savecase file? How?
Yes.
Using HDBRIO
When a database update takes place, what systems are impacted?
EMS, SMP, OAG, and RDS.
What is the first thing to do when performing a database update?
Start two web sessions: an EMS primary webfg session; and a secondary one:
When you click on "Save binary" in the FGBuilder, where does the output goes?
to the folder c:\display\scada.

The file has the extension .fgdisplay
If you want to quickly look for information about a particular station, what can you do?
1. You can use the "scadafinder.pl" application I wrote. Which is located on the desktop of EFPDS01.
2. You can also look in the EMS system.
What is the procedure to generate the ICCP down times report?
Procedure (Reporting Down Times):

1. Search on the alarm viewer (http://pececc/PEFTransAlarmViewer/MainViewer.aspx) for the following combination of strings: "ICCP & FPL & FAILED" and "ICCP & FPL & ESTABLISHED"

2. Identify those time stamps that match with either a database update or a patch application.

3. Update the following folder in the secure system: \\EFPDS01\D\Tools\ICCP\Downtimes

4. Copy the file to the corporate system and send an email to the DEWG with the file content.
What plants have the lowest SO2 emissions?
Intersection city and Shady Hills
What is NOx?
?
What is SO2?
?
What's the difference between the "control economic dispatch" and the "advisory economic dispatch"?
The difference is that in the "control economic dispatch" the basepoint of the units is calculated for those units that 1. are online
2. are economically dispatchable
3. are on AGC control.

The "advisory economic dispatch" is calculated only for those units that

1. are economically dispatchable.
What is the new (as of 01/12/09) procedure to model CB reclosers?
When a breaker has multiple "deadline" or "deadbus" recloser settings, we need to insert additional devices immediatelly after the device containing all of the other breaker modeling.

For example, for CB 2845, we would have two devices like
2845_DL_HNCK and
2845_DL_HOLD, a similar situation for deadbuse:
1425_DB_1
1425_DB_2
There is a document created by Brady explaining this better. It is just one page.
What is the OAG system also called?
e-terracomm
What is e-terrapclink?
Is a product written to open e-terrahabitat databases to off-the-shelf PC applications.
What is ICCPLink?
Is a process of the e-terracommm system that implements ICCP protocol.
What is ISDLink?
Is a process of the e-terracommm system that implements ISD protocol.
What does MMS means?
it means Manufacturing Message Specification. ICCP is based on MMS.
In the ICCP world, what does the term SCOPE means?
It means the accessibiity level of a data object. All ICCP data objects have a scope that limits its visibility and accessibility to the remote sites that have the data object specified in their bilateral table.
Defined scope are:
VMD -> Global scope
Domain -> restricted to a single remote site
Association -> restricted to a single association with a remote site.
How do you load an OAGMODEL savecase in the OAGSERVE clone?
you do it from the OAGSERVE master display.
What does the excel template scadamdl_data_template.xltm does?
The template "scadamdl_data_template.xltm" contains macros that assist in putting together the information that is extracted by the program "eccu_extract_scadamom".

The program put together a spreadsheet with addresses, analogs, controls, counts, devices, limits, meas, and points information.
How do you control a generation output in the DTS environment?
Follow the steps:
1. Look for the screen LOCAL_UNIT_CONTROLLER in the Dtspsm application.
2. Find the plant you need.
3. Change PLC status and Unit status to LOCAL.
4. Enter the desired MW level.
5. Hit the RAMP button.