Use LEFT and RIGHT arrow keys to navigate between flashcards;
Use UP and DOWN arrow keys to flip the card;
H to show hint;
A reads text to speech;
90 Cards in this Set
- Front
- Back
A sensor, controller and controlled device to control variable value describes: |
A control system |
|
The control systems most likely to be found in a building may be: |
Pneumatic or DDC |
|
A closed loop control system is controlled by: |
A self-containrd control system |
|
An example of _______________ is when a controller cycles a chilled water pump ON when the outside temp is above 65°F but sends NO signal back showing the status of the pump. |
Open loop control |
|
Valves and dampers are examples of: |
Controlled devices (or end devices) |
|
A _______ control is a control in which the controlled device is positioned (modulated) in direct response to the amount of offset in the system. |
Proportional (analog) |
|
The desired value to be maintained by a control system is the: |
Setpoint |
|
_______ is the difference between a control point and a setpoint. |
Offset |
|
In a hybrid control system, _______ are used as a common interface between different control systems technologies. |
Transducers |
|
A drawing of a mechanical system that illustrates actual controls and piping between devices is called: |
A control drawing |
|
In a hot water tank, electric elements heat up the surrounding water until the hot water rises, which is then replaced by cooler water. This is and example of: |
Convection |
|
The ____________ is when the heat losses through a building are the same as the amount of heat provided by the heat pump. |
Balance point |
|
Comfort is usually attained at normal cooling and heating temperatures with humidity levels of about: |
50% |
|
The outside air dry-bulb temp of _______ is common for outside air economizer use. |
45°-65°F |
|
What is the primary cause of excessively hot or cold temperature complaints? |
Incorrect setpoint |
|
A compressor, dryer, filter, PRV and relief valve are all elements found in: |
An air supply system |
|
The ______________ attached to the receiver starts and stops the air compressor and enables the compressed air station to deliver the correct system air pressure |
Pressure switch |
|
Number of starts per hour of the air compressor should not exceed; |
The manufacturer recommended limit |
|
______ in a compressed air tank causes controls and air compressor problems, receiver to rust and should be drained. |
Moisture |
|
An excessive amount of lubricating oil leaking by the Piston rings and carried into the compressed air system is called: |
Carry over |
|
The ability of a liquid to resist flow is called: |
Viscosity |
|
A _____ compressor uses interlocking rotors to compress air. |
Screw |
|
Dampers that regular air flow, calves that regulate water or steam, and refrigeration compressors that deliver cooling are examples of: |
Controlled devices |
|
__________ dampers have a nonlinear flow characteristic and are widely used on VAV terminal boxes. |
Round blade |
|
What is the normal position of a controlled device? |
The position of the device when no energy is applied |
|
______________ is when control pressure is required to move the end device from fully open to fully closed or vise versa. |
Spring range pressure |
|
_______ dampers regulates the air flow in carrying ducts. |
Opposed or parallel |
|
_______ is the most common blade damper used in HVAC systems. |
Parallel |
|
A _______ valve has one inlet and two outlets. |
Diverting |
|
A _______ valve has two inlets and one outles. |
Mixing |
|
____________ control the flow of fluids (water or steam) in an HVAC system. |
Control valves |
|
__________ thermostats increase in branch line pressure as temperature increases. |
Direct acting |
|
__________ thermostats decrease in branch line pressure as the temp increases. |
Reverse acting |
|
Heating/cooling or day/night thermostats are: |
Dual pressure thermostats |
|
The range between two temperatures in which no heating or cooling takes place is called: |
Dead band |
|
The _______________ in a pneumatic humidistat accepts moisture from, or rejects moisture to, the surrounding air. |
Hygroscopic element |
|
The ____________ senses the room temp and responds accordingly. |
Bimetal element |
|
The small heater in a thermostat that causes an HVAC unit to stop heating before normal shut down to avoid overshooting is called: |
A heating anticipator |
|
A device that sends signal to controller is: |
A transmitter |
|
All pneumatic transmitters produce a _____ to _____ output signal. |
3psig to 15psig |
|
Most transmitters are _____ pipe, _____ volume devices. |
One-pipe, low volume |
|
A two-piped transmitter uses: |
Full volume of the compressed air available |
|
_______ are accurate when shipped from the factory. |
Transmitters |
|
A device that senses total pressure and static pressure in a duct is: |
A pilot tube |
|
A device that allows an air pressure signal to energize or de-energize an electrical device such as a fan, pump, compressor, or electric heating devices is: |
A pneumatic/electric switch (p/e switch) |
|
A device that has a capillary tube sensing element and is used to protect against damage due to freezing conditions is called: |
A low temp cutout control (freeze stat) |
|
The _______ sends a signal to the controlled device (end device). |
Controller |
|
Excessive actuator hunting or cycling is caused by: |
A throttling range that is too small |
|
_________________ is capable of resetting the setpoint. |
A dual input receiver controller |
|
__________ is designed for basic zone control and uses a standard wall-mount temp sensor. |
A unitary controller |
|
Typically a variable air volume (VAV) air handling unit controls building space by changing: |
The volume of air, not the temperature |
|
Most VAV air handling units maintain a constant static pressure, and duct static pressure of _____. |
1"wc |
|
Most VAV air handling units maintain a constant discharge air temp of: |
55°F |
|
The constant volume system provides constant air flow by: |
Varying the temperature |
|
Low voltage is voltage at: |
30 VAC or less |
|
A device that changes AC voltage into DC voltage is: |
A rectifier |
|
An electronic control system has a power supply of: |
24 VDC or less |
|
The most common building automation system controller power supply is: |
120 VAC to 24 VAC step down transformer |
|
DDC systems may be part of a larger system called: |
A building automation system |
|
HVACequiptment, lighting, security, and other essential functions are controlled by: |
The building automation system |
|
Packaged units, VAVs, hot water, and chilled water are: |
Direct digital controls |
|
Features of ____________ may be economizer lockout control, lead/lag control, high/low signal select, and averaging control. |
Direct digital control |
|
DDC controllers are often reffered to as: |
Modules or panels |
|
Appliaction-specific controllers are designed to control: |
Only one type of HVAC system |
|
______________ are fully programmable, can be used in most HVAC systems and have fixed number of inputs and outputs. |
Universal input-output controllers |
|
Inputs and outputs connected to DDC controllers are called: |
Points |
|
__________ are digital inputs used to obtain the operational status of pumps, fans, compressors, and lighting. |
Current-sensing relays |
|
A configuration in which multiple controllers are connected in series is called: |
A daisy chain |
|
A device that has a unique address and is attached to a network is a: |
Node |
|
A network switch board that allows a number of nodes to communicate with each other is called: |
A concentrator |
|
Control algorithm that automatically adjusts it's response time based on environmental conditions is called: |
Adaptive control algorithm |
|
What follows commands sent to it from the CPU of a central DDC system? |
Field interface devices |
|
______________ may be reffered to as data gathering panels (DGPs) or data acquisition panels (DAPs) |
Field interface devices |
|
The building automation system is commonly reffered to as: |
The BMS |
|
An analog input signal: |
Leaves the sensor and travels to the controller |
|
An analog/digital output signal: |
Leave the controller and travels to the end device |
|
A proportional signal that controls a modulating device would use a/an _______ signal. |
Analog |
|
A two-position signal that is sent to the controller would use a/an _______ signal |
Digital |
|
Temperature, pressure and humidity sensors are examples of: |
Analog inputs |
|
Dampers, valves, VFDs and transducers are examples of: |
Analog outputs |
|
The control of a low voltage coil of a relay is an example of: |
Digital output |
|
The process of adding the individual input and output points to the data base of human-computer interface is called: |
Point mapping |
|
The total amount of electricity used during a billing period is: |
Electrical consumption |
|
The highest amount of electricity used during a specific period of time is called: |
Electrical demand |
|
An electric load that has been turned OFF by an electrical demand supervisory control strategy is: |
A shed load |
|
The amount of money a utility is permitted to charge to reflect the constantly changing cost of energy is: |
The fuel recovery rate |
|
Indication of abnormal conditions (alarms), providing information regarding energy consumption and equipment maintnence may be found: |
In the BAS (building automation system) |
|
Duty cycling, optimization, and load shedding are examples of: |
Supervisory control strategies (energy consuming functions) |
|
The primary desktop PC used to communicate with a building automation system is commonly referred to as the: |
Front end |
|
The amount of change required in a variable for the alarm to return to normal after it has been in alarm status is called: |
An alarm differential |