• Shuffle
    Toggle On
    Toggle Off
  • Alphabetize
    Toggle On
    Toggle Off
  • Front First
    Toggle On
    Toggle Off
  • Both Sides
    Toggle On
    Toggle Off
  • Read
    Toggle On
    Toggle Off
Reading...
Front

Card Range To Study

through

image

Play button

image

Play button

image

Progress

1/90

Click to flip

Use LEFT and RIGHT arrow keys to navigate between flashcards;

Use UP and DOWN arrow keys to flip the card;

H to show hint;

A reads text to speech;

90 Cards in this Set

  • Front
  • Back

A sensor, controller and controlled device to control variable value describes:

A control system

The control systems most likely to be found in a building may be:

Pneumatic or DDC

A closed loop control system is controlled by:

A self-containrd control system

An example of _______________ is when a controller cycles a chilled water pump ON when the outside temp is above 65°F but sends NO signal back showing the status of the pump.

Open loop control

Valves and dampers are examples of:

Controlled devices (or end devices)

A _______ control is a control in which the controlled device is positioned (modulated) in direct response to the amount of offset in the system.

Proportional (analog)

The desired value to be maintained by a control system is the:

Setpoint

_______ is the difference between a control point and a setpoint.

Offset

In a hybrid control system, _______ are used as a common interface between different control systems technologies.

Transducers

A drawing of a mechanical system that illustrates actual controls and piping between devices is called:

A control drawing

In a hot water tank, electric elements heat up the surrounding water until the hot water rises, which is then replaced by cooler water. This is and example of:

Convection

The ____________ is when the heat losses through a building are the same as the amount of heat provided by the heat pump.

Balance point

Comfort is usually attained at normal cooling and heating temperatures with humidity levels of about:

50%

The outside air dry-bulb temp of _______ is common for outside air economizer use.

45°-65°F

What is the primary cause of excessively hot or cold temperature complaints?

Incorrect setpoint

A compressor, dryer, filter, PRV and relief valve are all elements found in:

An air supply system

The ______________ attached to the receiver starts and stops the air compressor and enables the compressed air station to deliver the correct system air pressure

Pressure switch

Number of starts per hour of the air compressor should not exceed;

The manufacturer recommended limit

______ in a compressed air tank causes controls and air compressor problems, receiver to rust and should be drained.

Moisture

An excessive amount of lubricating oil leaking by the Piston rings and carried into the compressed air system is called:

Carry over

The ability of a liquid to resist flow is called:

Viscosity

A _____ compressor uses interlocking rotors to compress air.

Screw

Dampers that regular air flow, calves that regulate water or steam, and refrigeration compressors that deliver cooling are examples of:

Controlled devices

__________ dampers have a nonlinear flow characteristic and are widely used on VAV terminal boxes.

Round blade

What is the normal position of a controlled device?

The position of the device when no energy is applied

______________ is when control pressure is required to move the end device from fully open to fully closed or vise versa.

Spring range pressure

_______ dampers regulates the air flow in carrying ducts.

Opposed or parallel

_______ is the most common blade damper used in HVAC systems.

Parallel

A _______ valve has one inlet and two outlets.

Diverting

A _______ valve has two inlets and one outles.

Mixing

____________ control the flow of fluids (water or steam) in an HVAC system.

Control valves

__________ thermostats increase in branch line pressure as temperature increases.

Direct acting

__________ thermostats decrease in branch line pressure as the temp increases.

Reverse acting

Heating/cooling or day/night thermostats are:

Dual pressure thermostats

The range between two temperatures in which no heating or cooling takes place is called:

Dead band

The _______________ in a pneumatic humidistat accepts moisture from, or rejects moisture to, the surrounding air.

Hygroscopic element

The ____________ senses the room temp and responds accordingly.

Bimetal element

The small heater in a thermostat that causes an HVAC unit to stop heating before normal shut down to avoid overshooting is called:

A heating anticipator

A device that sends signal to controller is:

A transmitter

All pneumatic transmitters produce a _____ to _____ output signal.

3psig to 15psig

Most transmitters are _____ pipe, _____ volume devices.

One-pipe, low volume

A two-piped transmitter uses:

Full volume of the compressed air available

_______ are accurate when shipped from the factory.

Transmitters

A device that senses total pressure and static pressure in a duct is:

A pilot tube

A device that allows an air pressure signal to energize or de-energize an electrical device such as a fan, pump, compressor, or electric heating devices is:

A pneumatic/electric switch (p/e switch)

A device that has a capillary tube sensing element and is used to protect against damage due to freezing conditions is called:

A low temp cutout control (freeze stat)

The _______ sends a signal to the controlled device (end device).

Controller

Excessive actuator hunting or cycling is caused by:

A throttling range that is too small

_________________ is capable of resetting the setpoint.

A dual input receiver controller

__________ is designed for basic zone control and uses a standard wall-mount temp sensor.

A unitary controller

Typically a variable air volume (VAV) air handling unit controls building space by changing:

The volume of air, not the temperature

Most VAV air handling units maintain a constant static pressure, and duct static pressure of _____.

1"wc

Most VAV air handling units maintain a constant discharge air temp of:

55°F

The constant volume system provides constant air flow by:

Varying the temperature

Low voltage is voltage at:

30 VAC or less

A device that changes AC voltage into DC voltage is:

A rectifier

An electronic control system has a power supply of:

24 VDC or less

The most common building automation system controller power supply is:

120 VAC to 24 VAC step down transformer

DDC systems may be part of a larger system called:

A building automation system

HVACequiptment, lighting, security, and other essential functions are controlled by:

The building automation system

Packaged units, VAVs, hot water, and chilled water are:

Direct digital controls

Features of ____________ may be economizer lockout control, lead/lag control, high/low signal select, and averaging control.

Direct digital control

DDC controllers are often reffered to as:

Modules or panels

Appliaction-specific controllers are designed to control:

Only one type of HVAC system

______________ are fully programmable, can be used in most HVAC systems and have fixed number of inputs and outputs.

Universal input-output controllers

Inputs and outputs connected to DDC controllers are called:

Points

__________ are digital inputs used to obtain the operational status of pumps, fans, compressors, and lighting.

Current-sensing relays

A configuration in which multiple controllers are connected in series is called:

A daisy chain

A device that has a unique address and is attached to a network is a:

Node

A network switch board that allows a number of nodes to communicate with each other is called:

A concentrator

Control algorithm that automatically adjusts it's response time based on environmental conditions is called:

Adaptive control algorithm

What follows commands sent to it from the CPU of a central DDC system?

Field interface devices

______________ may be reffered to as data gathering panels (DGPs) or data acquisition panels (DAPs)

Field interface devices

The building automation system is commonly reffered to as:

The BMS

An analog input signal:

Leaves the sensor and travels to the controller

An analog/digital output signal:

Leave the controller and travels to the end device

A proportional signal that controls a modulating device would use a/an _______ signal.

Analog

A two-position signal that is sent to the controller would use a/an _______ signal

Digital

Temperature, pressure and humidity sensors are examples of:

Analog inputs

Dampers, valves, VFDs and transducers are examples of:

Analog outputs

The control of a low voltage coil of a relay is an example of:

Digital output

The process of adding the individual input and output points to the data base of human-computer interface is called:

Point mapping

The total amount of electricity used during a billing period is:

Electrical consumption

The highest amount of electricity used during a specific period of time is called:

Electrical demand

An electric load that has been turned OFF by an electrical demand supervisory control strategy is:

A shed load

The amount of money a utility is permitted to charge to reflect the constantly changing cost of energy is:

The fuel recovery rate

Indication of abnormal conditions (alarms), providing information regarding energy consumption and equipment maintnence may be found:

In the BAS (building automation system)

Duty cycling, optimization, and load shedding are examples of:

Supervisory control strategies (energy consuming functions)

The primary desktop PC used to communicate with a building automation system is commonly referred to as the:

Front end

The amount of change required in a variable for the alarm to return to normal after it has been in alarm status is called:

An alarm differential