State the CCR operator actions in the event the auxiliary operator called and said there was a fire on a steam turbine servo system.

Notify ES&S (333) and the IRL. CCR Should trip the turbine from the CCR.



Direct the Aux to shutdown the servo oil pumps to stop the flow of oil to the fire.

State the CCR operator actions in the event that the auxiliary operator called and said there was a fire on ST1 Lube oil system?

Notify ES&S (333) and the IRL should be notified. CCR should trip the turbine from the CCR.



Direct aux operator to shutdown the servo pumps and the DC lube oil pumps . Once the turbine coasts down shutdown the ac lo pump.

Explain what you would do if the Aux called you and said he was going to activate fire suppression station #3 or #4?

Instruct them not to. This direction should only come from the the IRL.

What must be done if the Aux called and said a section of fire protection piping has ruptured and it must be isolated?

Notify ES&S (8888), a plan will be developed for isolation and backup fire protection while the line is out of service.