What does NFPA stand for?

National Fire Protection Association 4-1

What does stand for ANSI?

American National Standards Institute 4-1

What does stand for IEEE?

Institute of Electrical and Electronics Engineers, INC. 4-1

______ is the connection intended to safely and effectively equalize the potential differences between two metallic items.

Bonding 4-2

A primary responsibility of the ITS installer is ___________.

safeguarding personnel, property, and equipment from foreign electrical voltages and currents.

What do they mean by foreign electrical voltages?

To electrical voltages or currents that normally are not carried by or expected in the telecommunications distribution systems. 4-2

The most common electrical shock occurs from ___________.

inadvertent contact with energized devices or circuits. 4-2

Until verified, always assume that equipment is _________.

energized. 4-2

ITS installers are not responsible for engineering the portions of __________.


the electrical systems related to ac electrical ground faults, structural lighting protection systems or surge protective devices. 4-4

ITS installers must incorporate effective ___________.

bonding, grounding and installation procedures for a building or structure that has been in place for years. 4-4

If the ITS installer finds a conflict among local safety code, BICSI guidelines and the manufacturer's requirements _________.

the conflict should be resolved with the authority having jurisdiction and the manufacturer';s installation guidelines before proceeding. 4-4

The ITS installer must recognize that three distinct grounding systems:

AC grounding electrode system


Equipment grounding system


Telecommunications bonding infrastructure 4-5

The ITS installers are not responsible for __________.

the ac grounding systems. 4-5

The ITS installer should _____________________.

identify the type of grounding electrode used for the building's ac electrical system for the purpose of ensuring an effective bonding connection for the grounding bus bars and telecommunications references points within the TRs. 4-5

The ITS installer should ensure that _______.

the bus bars within the telecommunications bonding infrastructure are bonded to the building's metal frame where they are readily available. 4-5

Telecommunications personnel should not ________.

move, modify, or disconnect any grounding electrode conductor with out the direct participation of a qualified electrical maintenance person. 4-5

A supplemental bonding structure within an equipment room or data center is a __________, which is often associated with raised flooring.

signal reference grid (SRG) 4-6

A bonding conductor must be run between the __________.

room's associated busbars and to at least two points within the SRG if a raised floor is used within an ER, TR, or data processing center. 4-6

The overall purpose for the telecommunications bonding infrastructure is to _______________.

equalize potentials between metallic surfaces predominantly in the event of lighting, ac electrical system faults, electromagnetic induction or electrostatic discharge. 4-7

The ITS installers of the telecommunications infrastructure must ____________.

examine the site and give practical consideration to a variety of options that are available to them. 4-7

Bonding conductors are not designed to intentionally carry ac ground fault current or lighting strike current, they are installed so that ____________.

voltages may be equalized when those events occur. 4-7

In small ERs and entrance facilities, the bonding and grounding begins at the ______________, which must be referenced to the nearest approved grounding electrode.

Telecommunications main grounding busbar (TMGB) 4-7

___________ must have an effective bonding connection to the nearest approved building grounding electrode and the equipment grounding system.

TGB and TMGB 4-10

Provide a minimum of _________ clearance behind the busbar when mounted.

51 millimeters ( 2 inches) 4-12

____ is the grounding connection point for telecommunications systems and equipment in the area served by an ER or TR. And should be mounted providing minimum 51 mm (2 in) clearance.

Telecommunications Grounding Busbar (TGB) 4-14

A ___ is a copper conductor that inerconnects the TMGB or TGB.

Telecommunications Bonding Backbone (TBB) 4-16

A ____ is a minimum 6 American wire gauge insulated, stranded copper conductor intended to equalize potentials between TRs on the same floor of a structure.

Grounding Equalizer 4-16

_______ recommends that this connection be made on every third floor and the top floor of multistory structures.

Telecommunication Industry Association (TIA) J-STD 607 4-16

The ____ connects the TMGB/TGB to the equipment racks/cabinets.

Telecommunications Equipment Bonding Conductor (TEBC) 4-17

The TEBC shall be a continuous copper that is sized for a minimum ______ insulated, copper conductor.

6 AWG 4-17

Visual inspection can usually reveal problems such as:

Loose connection


Corrosion


Physical damage


System modifications 4-21

The recommended maximum value for the bonding resistance between these two points is _______.

0.1 ohms (100 milliohms) 4-21

Interbuilding cable runs of ____ or less, directly or in underground conduit.

42.7 m (140 ft) 4-21

Areas having an average of five or fewer thunderstorms day per year and earth resistivity of less than ________.

100 ohmmeters 4-21

Intended for application on exposed circuits and must be installed immediately adjacent to the exposed cable's points of entry.

Primary Protectors 4-22, 4-23

This type of protector protest against sneak current.

Secondary Protectors 4-22

Perform like a primary protection against lighting transients.

Data and fire alarm protectors 4-22

Do not locate primary protectors near ______

any hazardous or easily ignitable material. 4-23

The protector terminals will located up to _______ away from the electrodes.

6.1 (20 ft) 4-23

Two types of primary protectors are ____ and ____.

fused (typical) and fuseless (legacy) 4-24

What does ATIS stand for?

Alliance for Telecommunications Industry Solutions 4-27