Do not place telcommunications cabling systems and associated path way next to active equipment. that can _____________.

generate EMI such as can be be found in an ER. 3-40

Telecommunications cabling should not be_______________.

installed parallel to electrical power lines. 3-41

Unshield power lines or electrical equipment in proximity to open or nonmetal pathways

610 mm (24 in) 3-43

Unshield power lines or electrical equipment in proximity to a grounded metal pathway

305 mm (12 in) 3-43

Power lines enclosed in a grounded metal in proximtiy to a grounded metal conduit pathway.

1220 mm (48 in) 3-43

Arc welders

800 mm (31.5 in) 3-43

Frequency inductions heating

1000 mm (39.5) 3-43 in

An ___________ generally houses equipment that serves an entire building, campus, or customer.

Equipment Room (ER) 3-44

A ______ generally serves a single floor or portion of a floor and is designed for the installation of a limited amount of equipment necessary to serve a dedicatied floor area.

Telecommunications Room (TRs) 3-44

An ________ is an entrance to a building for both public and private network service cabling.

Entrance Facility (EF) 3-45

A TE generally serves a limited space maximum of ___________.

335 m2 (3600 ft2) 3-45

It is recommended that TRs have __________ thick, fire-retardant plywood backboards installed on at least two walls of the TR.

19 mm (3/4in) 3-45

Plan for a minimum of _____ work and aisle space between and around equipment.

1 m (3.28) 3-45

It is important that the ITS installer prepare at least _______________ of the space and equipment to be instilled to identify potential areas of conflict.

dimensioned sketch 3-46

Plywood backboards are mounted on walls in the ____________.

ERs and TRs 3-48

Plywood sheets thicker than ___________ are not usually required.

25 mm (1 in) 3-48

Grade ____ is the highest grade and is without any surface blemishes

Grade A 3-49

Grade ____ has the knotholes cut out and replaced with a patch of clean wood.

Grade B 3-49

Grade ___ contains some blemishes and an occasional small knothole.

Grade C 3-49

Grade ____ contains knotholes without ang repair or corrective action by the manufacturer.

Grade D 3-49

Plywood should be void _____.

free 3-49

For ITS use, grade ____ plywood should be used.

A/C 3-49

Start mounting the plywood ______ above finished floor (AFF) to an installed height of _________.

203 mm (8 in) 3-49, 2.6 m (8 ft, 8 in) 3-50

BICSI strongly recommends that plywood be painted with _________ of fire-retardant paint.

two coats 3-49

Recessing the bolt head on plywood less then _____ thick may affect the ability of the plywood to hold the desired load of equipment and termination hardware.

25 mm ( 1 in) 3-52

The toggle bolts should be installed _______ from the edges of the sheet of plywood on approximately _______ centers.

51 mm (2 in), 610 mm (24 in) 3-52

It is suggested that a cable tray or ladder rack be installed on _____ in the TR.

every wall 3-53

D-rings are used to support small bundles of cables and ______ as they route from one termination point on the plywood backboard to another.

cross-connections 3-55

D-rings should not be _________ for a cable tray or ladder rack.

substituted 3-55

The inside bend radis shall be _____ the internal diameter of the conduit when used for optical fiber or trade size diameters greater than _______.

10 times, 51 mm (2 in) 3-56

If the conduit has a trade size diameter of 51 mm (2 in) or less, the inside bend radius shall be at least ______ the internal diameter.

6 times 3-56