• Shuffle
    Toggle On
    Toggle Off
  • Alphabetize
    Toggle On
    Toggle Off
  • Front First
    Toggle On
    Toggle Off
  • Both Sides
    Toggle On
    Toggle Off
  • Read
    Toggle On
    Toggle Off
Reading...
Front

Card Range To Study

through

image

Play button

image

Play button

image

Progress

1/157

Click to flip

Use LEFT and RIGHT arrow keys to navigate between flashcards;

Use UP and DOWN arrow keys to flip the card;

H to show hint;

A reads text to speech;

157 Cards in this Set

  • Front
  • Back
  • 3rd side (hint)

49-1301: a) Sinks or other fixtures installed in island counters may be discharge to an _ trap under provision.

A) s trap


B) p trap


C) drum trap


D) anti-siphon trap

D) anti-siphon trap

49-1301: b) island fixture anti-siphon traps waste must be _ one pipe size.

A) elavate


B) degrade


C) increase


D) decrease

C) increase

49-1301: c) island anti-siphon traps must be as _ to the fixture as possible.

A) square


B) close


C) far below


D) in line

B) close

49-1301: d) the continuous vent for an ant-siphon trapped fixture must be carried above the what?

A) trap wier


B) strainer


C) flood rim


D) fixture rim

C) flood rim

49-1301: e) what standard rule of waste arms does not apply to anti-siphon traps?

A) the three foot rule


B) the five foot rule


C) vent run full size


D) dual vent for water closets

B) the five foot rule

49-1301: f) when the waste is run underground on an anti-siphon trapped fixtue the increased 1 1/2" to 2" waste is only required on the _ portion.

A) above ground


B) below ground


C) clean out


D) vent side

A) above ground

49-1302: a) where vent pipes are connected to a horizontal soil or waste pipe ahead of the trap being served they shall be taken of above what?

A) the crown


B) the center line


C) the invert


D) flood rim

B) the center line

49-1302: b) the connection of a vent to soil or waste the vent must rise to _ inches above the flood rim before off-setting to horizontal.

A) 0" inches


B) 1 1/2" inches


C) 3" inches


D) 6" inches

C) 3" inches

49-1302: c) under what conditions may a vent off-set horizontally prior to three inches above the flood rim where connected to a soil or waste pipe?

A) minimal


B) extenuating


C) approved


D) structural

D) structural

49-1302: d) when installing vents for bathtubs and other such fixture the vent shall be rolled to _ degree angle before off-setting horizontally.

A) 22


B) 45


C) 60


D) 90

B) 45

49-1303: 1) two identical fixtures adjacent or located on opposite side of a wall or partition one _ pipe with restriction.

A) soil


B) waste


C) vent


D) soil, waste, or vent

D) soil, waste, or vent

49-1303: a) each fixture branch _ will be perscribed in table {49-1403} based on fitting and size.

A) condition


B) rise


C) length


D) slope

C) length

49-1303: b) soil, waste, and vent pipes shall be sized based on individual installation. the exception being two water closents shall have at the least a _ inch vent.

A) 1 1/2"


B) 2"


C) 3"


D) n/a

B) 2"

49-1303: c; 1) two identical fixtures a lavatory and a kitchen sink could not use a dual vent the fixtures should have the same?

A) fixture units


B) trap wier


C) flood rim


D) point of use

C) flood rim

49-1303: c; 2) adjacent dual venting a _ could only be used on 3" inch or larger pipe.

A) cross


B) double wye


C) figure 5


D) double combo

A) cross

49-1304: V/S) what size of vent pipe does a residential bar sink require?

A) 1 1/4"


B) 1 1/2"


C) 2"


D) indirect {ID}

A) 1 1/4"

49-1304: S/V) what size vent pipe does a commercial bar sink require?

A) 1 1/4"


B) 1 1/2"


C) 2"


D) indirect {ID}

D) indirect {ID}

49-1304: S/V) a bathtub requires what size of vent pipe?

A) 1 1/4"


B) 1 1/2"


C) 2"


D) indirect {ID}

B) 1 1/2"

49-1304: S/V) a beer tap requires what size of vent pipe?

A) 1 1/4"


B) 1 1/2"


C) 2"


D) indirect {ID}

A) 1 1/4"

49-1304: S/V; n1) beer taps should be run _ when possible?

A) horizontal


B) verticle


C) indirect


D) direct

C) indirect

49-1304: S/V) a bidet requires what size of vent pipe?

A) 1 1/4"


B) 1 1/2"


C) 2"


D) indirect {ID}

B) 1 1/2"

49-1304: S/V) cuspidor requires what size of vent pipe?

A) 1 1/4"


B) 1 1/2"


C) 2"


D) indirect {ID}

A) 1 1/4"

49-1304: S/V) what size of vent pipe is required for a dental unit?

A) 1 1/4"


B) 1 1/2"


C) 2"


D) indirect {ID}

A) 1 1/4"

49-1304: S/V) what size of vent pipe is rquired for a disposal unit residential or commercial?

A) 1 1/4"


B) 1 1/2"


C) 2"


D) indirect {ID}

B) 1 1/2"

49-1304: S/V) what size of vent pipe is required for a drinking fountain?

A) 1 1/4"


B) 1 1/2"


C) 2"


D) indirect {ID}

A) 1 1/4"

49-1304: S/V) what size vent pipe is required for a residential dishwasher?

A) 1 1/4"


B) 1 1/2"


C) 2"


D) indirect {ID}

B) 1 1/2"

49-1304: S/V) what size vent pipe is required for a commercial dishwasher?

A) 1 1/4"


B) 1 1/2"


C) 2"


D) indirect {ID}

D) indirect {ID}

49-1304: S/V) what vent pipe size is required by a floor drain?

A) 1 1/4"


B) 1 1/2"


C) 2"


D) indirect {ID}

B) 1 1/2"

49-1304: S/V; n2) floor drians, floor sinks, mop sinks, and shower stalls may not require what?

A) trap


B) supply


C) vent


D) drain

C) vent

49-1304: S/V) what vent pipe size is required by a floor sink?

A) 1 1/4"


B) 1 1/2"


C) 2"


D) indirect {ID}

B) 1 1/2"

49-1304: S/V) what vent pipe size is required for a flushing rim sink?

A) 1 1/4"


B) 1 1/2"


C) 2"


D) indirect {ID}

B) 1 1/2"

49-1304: S/V) what size of vent pipe is required for a glass washer?

A) 1 1/4"


B) 1 1/2"


C) 2"


D) indirect {ID}

B) 1 1/2"

49-1304: S/V) what size of vent pipe is required for a laundry sink?

A) 1 1/4"


B) 1 1/2"


C) 2"


D) indirect {ID}

B) 1 1/2"

49-1304: S/V) what size of vent pipe is required for a lavatory (basin)?

A) 1 1/4"


B) 1 1/2"


C) 2"


D) indirect {ID}

A) 1 1/4"

49-1304: S/V) what size of vent pipe is required for a mop sink?

A) 1 1/4"


B) 1 1/2"


C) 2"


D) indirect {ID}

B) 1 1/2"

49-1304: S/V) what size of vent pipe is required for a service sink?

A) 1 1/4"


B) 1 1/2"


C) 2"


D) indirect {ID}

B) 1 1/2"

49-1304: S/V) what size of vent pipe is required for a shower stall?

A) 1 1/4"


B) 1 1/2"


C) 2"


D) indirect {ID}

B) 1 1/2"

49-1304: S/V) what size of vent pipe is required for a sink residential or commercial?

A) 1 1/4"


B) 1 1/2"


C) 2"


D) indirect {ID}

B) 1 1/2"

49-1304: S/V) what size of vent pipe is required for a sitz bath?

A) 1 1/4"


B) 1 1/2"


C) 2"


D) indirect {ID}

B) 1 1/2"

49-1304: S/V) what size of vent pipe is required for a urinal?

A) 1 1/4"


B) 1 1/2"


C) 2"


D) indirect {ID}

B) 1 1/2"

49-1304 S/V) what size of vent pipe is required for a water closet?

A) 1 1/4"


B) 1 1/2"


C) 2"


D) indirect {ID}

B) 1 1/2"

49-1304: S/V) what size of vent pipe is required for a wash fountain?

A) 1 1/4"


B) 1 1/2"


C) 2"


D) indirect {ID}

B) 1 1/2"

49-1304: S/V) what size of vent pipe is required for a residential clothes washer?

A) 1 1/4"


B) 1 1/2"


C) 2"


D) indirect {ID}

C) 2"

49-1305) fixtures entering a stack at different levels require a _ except for the highest fixture.

A) dual vent


B) revent


C) loop vent


D) battery vent

B) revent

49-1306: a; 1) floor drains, mop sinks, floor sink floor urinal, shower, area drain shall be connected _ to the horizontal soil or waste line.

A) vertically


B) horizontally


C) indirectly


D) directly

C) indirectly

49-1306: a; 2) floor drains, mop sinks, floor sinks, showers, and area drains shall be located _ feet downstream from the base of a stack.

A) 1' foot


B) 3' feet


C) 5' feet


D) 10' feet

B) 3' feet

49-1306: a; 2.2) floor dains, mop sinks, floor sinks, floor urinals, showers, and area drains shall be located _ feet from any water closet opening.

A) 1' foot


B) 3' feet


C) 5' feet


D) 7' feet

C) 5' feet

49-1306: a; 2.3) when the fixture drain for an "unvented fixture" and verticle fixture drain are both _ then the point of connection may be closer than 3' feet.

A) same size


B) same size and smaller


C) one size smaller


D) 1/2 the diameter

C) one size smaller

49-1306: a; 2.4) washer has no exception to 3' from the base of a stack.

A)

A)

49-1306: a; 2.5) what must always be counted for unvented fixtures?

A) developed length


B) degree of fall


C) fixture units


D) distance to clean out

C) fixture units {vent load}

49-1306: a; 3) what is maximum developed length for a 2" unvented fixture?

A) 3'


B) 5'


C) 12'


D) 16'

D) 16'

49-1306: a; 3.2) what is the maximum developed length of a 3" unvented fixture?

A) 14'


B) 20'


C) 24'


D) 32'

C) 24'

49-1306: a; 3.3) what is the maximum developed length of a 4" unvented fixture?

A) 18'


B) 24'


C) 32'


D) 57'

C) 32'

49-1306: a; 3.4) what is the maximum developed length for a 5" or larger?

A) 25


B) 35


C) 45


D) 55

C) 45

49-1306: a; 4) waste piping for unvented fixtures may not exceed a single verticle rise of what?

A) 3' 2"


B) 4' 4"


C) 6' 6"


D) 7' 6"

C) 6' 6"

49-1306: a; 4.2) where should the fixture units be counted for the unvented fixture?

A) waste fixture units


B) vent fixture units


C) the verticle vent


D) the vent for the horizontal soil & waste

D) the vent for the horizontal soil & waste

49-1306: b) name three appurtenances that do not require a vent?

A) soda fountain, beer tap, bar sink


B) downspout, rainwater leader, subsoil sump pit


C) area drains, storm drains, culverts


D) commercial dishwasher, garbage can washer, wash sinks

B) downspouts, rainwater leader, subsoil sump pit

49-1306: c) a verticle waste that receives condensate or _ .

A) mop sink


B) floor sink, floor drain


C) area drain


D) water heater pan, relief valve

D) water heater pan, relief valve

49-1307: ) In buildings having five or more branch intervals above an offset to horizontal in a soil or waste stack a _ shall be provieded for both above and below the offset.

A) valve


B) vent


C) relief drain


D) bypass

B) vent

49-1307: a; 1) the upper section of the stack offset shal be treated as a _ stack.

A) vent stack


B) waste stack


C) special waste stack


D) seperate stack

D) seperate stack

49-1307: a; 1.2) as the upper portion of an offset is treated as a seperate stack it will require a vent taken from its base which may serve as what?

A) stack vent


B) relief vent


C) return vent


D) air admittance vent

B) relief vent

49-1307: a; 2) the vent for the upper section of the offset shall be sized for?

A) the upper section


B) 1 1/2 time the upper section


C) both the upper and lower section


D) the upper and 1/2 the lower section

A) the upper section

49-1307: a; 3) the vent shall be sized _ than the smaller of the vent stack or soil & waste stack.

A) larger


B) smaller


C) no larger


D) no smaller

D) no smaller

49-1307: a; 4) what condition must me met to connect the lower section vent with th upper section?

A) a bypass


B) relief vent


C) sized for total load


D) figure five fitting

C) sized for total load

49-1307: b; 1) the lower section of the stack offset may be vented as a continuation of the soil and waste stack using what?

A) return vent


B) relief vent


C) backup vent


D) air admittance vent

B) relief vent

49-1307: b; 1.2) a yoke vent may be used to vent the lower section it must connect a minimum _ below the offset and above the next lower branch below the offset.

A) 1' foot


B) 18" inches


C) 2' feet


D) 3' feet

C) 2' feet

49-1307: b; 2) the vent for the lower side of the offset must be what?

A) offset


B) run full size


C) run independantly


D) be sized for the lower load

D) be sized for the lower load

49-1307: b; 2.2) as long as the stack is sized for the total load the upper relief vent may be connected to what?

A) the lower relief vent


B) a seperate vent stack


C) independant through the roof


D) air admittance vent

A) the lower relief vent

49-1308: a; 1) vents from a _ must not be connected to any other vents.

A) drinking fountain


B) bathroom grouping


C) grease interceptor


D) unvented fixtures

C) grease interceptor

49-1308: a; 1.2) blow off basins and chemical waste require _ vent.

A) direct vent


B) independant vent


C) relief vent


D) consentric vent

B) independant vent

49-1308: b) any vent originating from a closed or sealed portion of a type 1 interceptor must be what?

A) air admittance


B) independant


C) combined


D) direct

B) independant

49-1308: c) air admittance valves are?

A) encouraged


B) permissable


C) prohibited


D) conditional

C) prohibited

49-1309: ) soil and waste stacks in buildings exceeding _ branch intervals shall be provided witha relief vent.

A) third


B) fifth


C) tenth


D) thirteenth

C) tenth

49-1309: .1) a relief vent shall be provided at what interval?

A) third


B) fifth


C) seventh


D) tenth

D) tenth

49-1309: a) what floor should the relief vent originate?

A) the top


B) the bottom


C) the fifth


D) the tenth

A) the top

49-1309: b) the size of the relief vent shall be?

A) the total load


B) the branch load


C) the vent stack


D) the waste stack

C) the vent stack

49-1309: c) the lower end of the relief vent shall connect to the soil or waste stack through a _ below the horizontal branch serving the floor.

A) tee


B) combo


C) wye


D) figure five

C) wye

49-1309: d) the upper section of the relief vent shall connect to the vent stack through a wye not less than _ inches above the floor level.

A) 18"


B) 32"


C) 42"


D) 48"

C) 42"

49-1310: ) return vents may be used for what type of fixtures?

A) bar sinks


B) kitchen sinks


C) island sinks


D) shower drains

C) island sinks

49-1310: a) on return vents _ should be placed as close to the fixture as possible.

A) vent connection


B) waste stack


C) san tees


D) p-traps

D) p-traps

49-1310: b) a _ vent shall be carried from above the flood rim of the fixtures and extend horizontally to a vent stack or stack vent.

A) level


B) verticle


C) horizontal


D) continuous

D) continuous

49-1310: c) where the vent cannot be run under the counter it may be run _ to a branch or main vent

A) through the air


B) through the wall


C) below the floor


D) air admittance valve

C) below the floor

49-1310: d) the vent shall be run in such a manner that condesation will _.

A) not form


B) dry out


C) drain


D) cannot be used as a waste

C) drain

49-1311: ) a fixture revent shall be placed as close to the fixture opening, not to exceed _ inches.

A) 12"


B) 18"


C) 24"


D) 32"

C) 24"

49-1312: a) the total area of vents shall be equal to or greater than the area of the _ of the building drain.

A) total


B) 3/4 total


C) 1/2 total


D) largest section

D) largest section

49-1312: b) the vent must be increased to a min _ inches and the increased area shall not be counted for vent load.

A) 3"


B) 4"


C) one size


D) 1 1/2 diameter

B) 4"

49-1312: c) there shall be a minimum of one _ inch stack in a dwelling unit.

A) 1 1/2"


B) 2"


C) 3"


D) 4"

C) 3"

49-1312: c; 1) a three inch stack plus a two inch stack plus a one and a half inch stack will be considered equal to what size of stack?

A) 3"


B) 4"


C) 6"


D) two 3"

B) 4"

49-1312: c; 2) a single increaser may recieve _.

A) roof drain


B) branch vents


C) return vents


D) relief vents

B) branch vents

49-1312: c; 2.2) what is the maximum horizontal length to the branch vent added to a single increaser.

A) 5'


B) 10'


C) 15'


D) 25'

C) 15'

49-1312: c; 2.3) minimum rise above the roof for the vent?

A) 6"


B) 12"


C) 18"


D) 1' 6"

B) 12"

49-1312: c; 2.4) what is the minimum distance below the roof for the vtr?

A) 6"


B) 12"


C) 18"


D) 24"

B) 12"

49-1312: c; 3.5) the maximum distance below the roof the vtr may extend?

A) 12"


B) 18"


C) 24"


D 32"

B) 18"

49-1312: c; 3.6) when a branch vent is added to the increaser of a vtr the size for the stack and branch should be?

A) 2" or smaller


B) 3" or smaller


C) 3"


D) 4" or smaller

B) 3" or smaller

49-1313: dfu) an 1 1/4" vent has a maximum length of 45'. what are the drainage fixture units it provides?

A) 1


B) 3


C) 8


D) 18

A) 1

49-1313: dfu) how many drainage fixture units does an 1 1/2" vent provide?

A) 1


B) 3


C) 8


D) 16

C) 8

49-1313: dfu) what is the maximum length of an 1 1/2" vent?

A) 45'


B) 50'


C) 60'


D) 75'

C) 60'

49-1313: dfu) with a maximum legth of 120' a 2" vent provides a total of how many drainage fixture units?

A) 8


B) 16


C) 18


D) 21

C) 18

49-1313: dfu) how many drainage fixture units does a 3" vent provide?

A) 60


B) 72


C) 75


D) 80

B) 72

49-1313: dfu) what is the maximum length of a 3" vent?

A) 200'


B) 212'


C) 240'


D) 244'

B) 212'

49-1313: dfu) what is the maximum length of a 4" vent?

A) 300'


B) 330'


C) 340'


D) 344'

A) 300'

49-1313: dfu) what is the maximum drainage fixture units allowed by a 4" vent?

A) 200


B) 212


C) 240


D) 244

D) 244

49-1313: dfu) the maximum length of a 6" vent is 510', what is the maximum drainage fixture units?

A) 1029


B) 1296


C) 1413


D) 2137

B) 1296

49-1313: dfu) the 8" vent has a miximum length of 750' and a total of _ drainage fixture units.

A) 1500


B) 2500


C) 3500


D) 4500

C) 3500

49-1313: dfu; n1) what is the maximum number of water closets run from an 1 1/2" vent?

A) 0


B) 1


C) 2


D) 3

B) 1

49-1313: dfu; n2) a bathroom grouping containing one water closet, one lavatory and one urinal may be vented through _?

A) single 1 1/2"


B) single 2"


C) a 3"


D) unvented

A) single 1 1/2"

49-1314: ) the highest fixture on a stack may be run through a soil or waste branch without a _ . this is known as stack venting.

A) vent


B) revent


C) return vent


D) air admittance vent

B) revent

49-1314: a) a maximum of how many drainage fixture units may be permitted to drain above a stack vented water closet?

A) 1


B) 3


C) 4


D) 8

C) 4

49-1314: a) a maximum of how many drainage fixture units may be permitted to drain above a stack vented water closet?

A) 1


B) 3


C) 4


D) 8

C) 4

49-1314: b) bathtubs and showers may be stack vented using what fitting at the same level as the water closet?

A) sanitary tee


B) side inlet sanitary tee


C) side inlet 90 ell


D) figure five

B) side inlet sanitary tee

49-1315: a stack vent is the portion of a waste stack between the roof penitration vertically down to a point _ inches above the flood rim of the highest fixture.

A) 0"


B) 1"


C) 3"


D) 6"

C) 3"

49-1316: a) in all dwelling units with basements, a minimum of one full _ is required in the basement for future use.

A) 1 1/2" drain


B) 1 1/2" vent


C) 2" waste


D) 2" vent

B) 1 1/2" vent

49-1316: a; .2) a future vent will be installed in such a manner that it cannot be used as what?

A) vent


B) condensate


C) dryer vent


D) waste

D) waste

49-1316: a; .3) the future vent must carry a full _ drainage fixture units.

A) 1


B) 3


C) 8


D) 16

C) 8

49-1317: ) all vent pipe shall be free of drops and sags the minimum slope for a vent pipe is _ inch per foot down toward the the soil and waste pipe.

A) .01


B) 1/16"


C) 1/8"


D) 1/4"

B) 1/16"

49-1318: ) vent pipe shall be connected in such a manner to prevent them from serving as _ in case of stoppage.

A) vent line


B) return vent


C) waste line


D) siphon

C) waste line

49-1319: a) a vent stack shall terminate independently in the open air above the roof of the building or shall be connected with a _ .

A) stack vent


B) vent stack


C) vtr


D) future vent

A) stack vent

49-1319: b) a vent stack shall be run downward, full size and be connected with the soil or waste at or below the lowest horizontal waste branch or with the _ .

A) storm drain


B) back vent


C) future vent


D) building drain

D) building drain

49-1319: c) whenever back vents, relief vents, or other branch vents are rquired on _ or more floors, the vent stack shall be installed with soil or waste stacks.

A) 1


B) 2


C) 3


D) 5

B) 2

49-1320: a; 1) the vtr shall be at least _ inches above the roof.

A) 6"


B) 12"


C) 18"


D) 24"

B) 12"

49-1320: a; 1.2) the vtr shall increase to a minimum _ inch diameter.

A) 2"


B) 3"


C) 4"


D) 6"

C) 4"

49-1320: a; 2) the increase in the vtr shall be made a minimum of _ inches below the roof.

A) 6"


B) 10"


C) 12"


D) 18"

C) 12"

49-1320: a; 2.2) the vtr shall increase a maximum of _ inches below the roof.

A) 10"


B) 12"


C) 18"


D) 24"

C) 18"

49-1320: a; 3) the vtr shall be properly _.

A) supported


B) insulated


C) flashed


D) secured

C) flashed

49-1320: b; 1) the vtr shall not terminate directly beneath any door, window, or other ventalating opening nor within _ feet horizontally.

A) 2'


B) 5'


C) 7'


D) 10'

D) 10'

49-1320: b; 1.2) the vtr shall not terminate directly beneath any door, window, or other ventalating opening and shall be at least 10' horizontally unless at least _ feet above.

A) 1'


B) 2'


C) 3'


D) 5'

B) 2'

49-1320: b; 2) the vtr shall not terminate closer than _ feet under any roof gable.

A) 2'


B) 3'


C) 6'


D) 10'

A) 2'

49-1320: b; 3) the vtr shall not terminate closer than _ feet to any wall extending above a flat roof.

A) 2'


B) 6'


C) 7'


D) 10'

A) 2'

49-1320: b; 4) the vtr shall not terminate any closer than _ feet to any firewall above the roofline or otherwise.

A) 2'


B) 3'


C) 6'


D) 10'

C) 6'

49-1320: b; 5) the vtr shall not terminate where a roof is used for any other purpose than weather protection unless extended at least _ feet above the roof.

A) 2'


B) 6'


C) 7'


D) 10'

C) 7'

49-1320: b; 6) the vtr shall not terminate through a sidewall with the exception as provided for _ .

A) condensate


B) area drains


C) interceptors


D) storm drains

C) interceptors

49-1320: b; 7) the vtr shall not terminate less than _ feet higher than any walls extended above a commercial kitchen when two or more walls extend above the roof.

A) 1'


B) 2'


C) 6'


D) 7'

A) 1'

49-1321: a; 1) battery venting is a horizontal branch sized to recieve the discharge of 2 but not more than _ floor outlet water closets.

A) 4


B) 6


C) 8


D) 10

C) 8

49-1321: a; 1.2) a battery vent may be a circut or a loop vent taken off _ the last fixture, and shall recieve no discharge from any soil or waste.

A) from above


B) from below


C) in front


D) from behind

C) in front

49-1321: a; 2) battery venting in multiple level buildings the lower floor branches connected to a vertical stack and serving more than _ fixtures shall be provided with a relief vent.

A) 2


B) 3


C) 6


D) 8

B) 3

49-1321: a; 2.2) battery vents in multiple level buildings lower floor branches with 4 or more fixtures required relief vent should be taken off _ the first fixture.

A) before


B) after


C) above


D) below

A) before

49-1321: a; 3) in battery venting _ vent(s) shall be taken off from the top of the horizontal branch and sized accordingly

A) circuit


B) loop


C) relief


D) circuit, loop, and relief

D) circuit, loop, and relief

49-1321: a; 4) battery venting each water closet fixture drain shall connect _ to the horizontal branch.

A) vertically


B) directly


C) horizontally


D) indirectly

C) horizontally

49-1321: a; 4.2) battery venting the maximum distance between the horizontal soil branch and each water closet fixture opening shall be ?

A) 5'


B) 7'


C) 10'


D) no limit

A) 5'

49-1321: a; 5) in battery venting the horizontal soil branch shall be _ the fixture branch size.

A) increased one size from


B) the same size as


C) no smaller than


D) one size smaller

B) the same size as

49-1321: a; 6) in battery venting the maximum slope of the horizontal drain shall be _ inch per foot.

A) 1/8"


B) 1/4"


C) 3/8"


D) 1/2"

D) 1/2"

49-1321: a; 7) _ fixtures may be added to the battery vented fixtures and vented as required.

A) mop closet


B) floor drain, floor sinks


C) bathroom group


D) waste

C) bathroom group

49-1321: a; 7.2) what type of venting is not allowed in battery venting.

A) circuit


B) loop


C) relief


D) wet

D) wet

49-13**: bonus) what type of venting is not allowed in omaha?

A) wet


B) syphonic


C) air addmitance


D) return

C) air addmitance ( quickie vent)

49-1321: b; 1) when wet venting a water closet how many fixture units can the wet vent carry?

A) 1


B) 2


C) 3


D) 4

D) 4

49-1321; b; 1.2) the connection for the wet vent shall be within _ feet of the water closet opening.

A) 2'


B) 3'


C) 5'


D) 7'

A) 2'

49-1321: b; 2) A water closet and a tub may be vented through a lavatory waste when all three are _ and on the same wall.

A) adjacent


B) back to back


C) perpendicular


D) consecutive

A) adjacent

49-1321: b; 2.2) the connection for the lavatory shall be within _ of the tub trap.

A) 1' foot


B) 18" inches


C) 2' feet


D) 3' feet

C) 2' feet

49-1321: c; 1) stack venting the highest water closet on a stack may have a soil or waste branch exrended to a distance not to exceed _ developed length center of stack to fixture opening without installing a revent.

A) 2'


B) 3'


C) 5'


D) 7'

C) 5'

49-1321: c; 2) if the water closet branch requires a revent it should be as close to the fixture opening as possible but no more than _ developed from the floor.

A) 1'


B) 2'


C) 3'


D) 5'

B) 2'

49-1321: c; 3) the maximum number of fixture units permitted above a stack vented water closet is _ .

A) 1


B) 2


C) 4


D) 6

C) 4

49-1321: c; 3.2) a clothes washer may be discharged above a stack vented water closet provided the vertical distance between the branch arm for the water closet and the is _ .

A) 3'


B) 5'


C) 7'


D) 10'

C) 7'

49-1321: d; 1) two back to back water closets may be vented using a horizontal double wye provided?

A) the vent is ruduced only one size


B) the water closets are maximum 5'


C) the cleanout serves the line


D) the ninteies and clean out are the same size

D) the nineties and the cleanout are the same size

49-1321: d; 2) on a horizontal double wye back to back water closet vent you may permit _ fixure units.

A) 2


B) 3


C) 4


D) 6

C) 4

49-1322: a) if a branch line to the interceptor is _ from the main building drain line no vent will be required.

A) 10' feet or less


B) 10' feet or more


C) 15' or less


D) 20' or less

A) 10' feet or less

49-1322: b) if the branch line to the interceptor exceeds 10' it requires a _ vent.

A) 1 1/2"


B) 2"


C) 3"


D) 1/2 the diameter of the main

B) 2"

49-1322: c) commercial kitchen fixture vents shall _ to non kitchen fixture vents.

A) connect


B) not connect


C) cross


D) terminate

B) not connect