how many fixtures are between a circuit vent and a relief vent, before adding an additional circuit vent?

8

a continuous vent is considered to be a..

dry vent

what is the hydraulic load for a soil or waste pipe serving as a relief vent?

6

what information is required to size a continuous or circuit vent?

fixture units/developed length

what is the maximum number of fixture units allowed on a circuit vent?

1


or


2 if they symmetrically connected

when connecting a fixture to a circuit vent, what is the maximum allowable fixture unit load?

1-1/2

what dont you count when finding the fixture unit load for a circuit vent?

fixtures on the relief vent

how can you determine the size of a relief vent?

can be one size smaller than the circuit vent but no more than 2

when must an additional circuit vent be added?

-when there are more than 8 fixtures in between circuit vent/relief vent



-when an offset is more than 45°

what must be done if 1-1/4 or 1-1/2 traps are installed a circuit vented branch that serves 2" or larger traps?

must be individually vented

what is the minimum size of a circuit vented branch if serving 1-1/4 & 1-1/2 traps?

2"

what is the minimum size of a circuit vented branch serving 2" or larger traps?

3"

when must a vent stack be installed?

when a soil or waste stack receives discharge from more than four storeys

what is the purpose of a vent stack?

to reduce the probability of pressure fluctuation from surge flows that fill the stack

how is a vent stack connected?

to the upper end of the vent header or outside air


to


the soil or waste stack at or below the lowest pipe connection

how many fixture units can be installed on the vent stack?

8

where are the fixtures located on a vent stack ?

on the lowest story served by the vent stack

what is the minimum size of a vent stack?

not less than one half the size of the soil or waste stack at its base

when must a yoke vent be added?

when a soil or waste stack receives discharge from more than 11 stories

when fixtures that receive discharge from 5 stories in row, what must be added?

a yoke vent

how many fixtures can be connected to a yoke vent?

1


or


2 if they are connected to a sanitary tee y.

when can you avoid using yoke vents when fixtures from more than 11 stories are being discharged?

when a vent stack is interconnected to the soil or waste stack at each story using fixtures.

when interconnecting at each floor instead of using a yoke vent, how must the branch be sized?

equal in size or 2" in size.


whichever is smaller

when must an offset relief vent be installed?

when a soil or waste stack receives a hydraulic load of more than 100 fixtures and passes through more than 2 stories.

how long is the offset for the stack at its base for a offset relief vent?

1.5 M


or


5 ft

how is a offset relief vent sized?

one size smaller than the stack vent

when venting a sewage sump, what size is the vent pipe?

1 size smaller than the drain

what is the minimum and maximum size of a vent pipe serving a sewage sump?

2" minimum


4" maximum

what is the size of vent serving a man hole?

2"

how far off should yoke vents be installed off the floor?

1m

how many vents are required for oil interceptors?

2

how far above ground must oil interceptor vents terminate?

2 m above ground

what is the difference in height for the two vents of a oil interceptor?

300 mm

how are oil interceptors sized?

1 size smaller than the largest connected drainage pipe.


not less than 1-1/4

wet vents that are 2" or less in size cannot exceed an offset of..

1.2 m

wet vents that are larger than 2" in size cannot exceed an offset of..

2.5 m

what is the minimum height of a vent pipe for a RV sewage dump?

7'

a sewage dump station will have what size of trap?

4"

potable water source is used to refill the water tank in the RV and is a minimum ____m or____ft distance from the sewage connection.

7.6m


25 ft