1E AC Power Purpose

Provide class 1E loads required for :


Safe shutdown


Maintain plant in a safe condition


Mitigate consequence of accident

Incoming Feeder Voltage <w% for x seconds or bus decreases to y%



The z device will...

w=92


x=20


y=70


z=27



27 device will trip and initiate:


All motor circuit breakers trip


LOP sequencing alarm is initiated


Emergency start of EDG if both normal infeed voltages are <92%


Alternate supply breaeker will close to supply power...


Provided....


Following a time delay of 0.7 sec.


Time delay is to ensure motor breakers are open prior to closure of the alternate breaker




Provided:


Auto close block is not selected


Associated feeder is >92%


No bus lockout signals


Normal spply breaker is open

Motor feeders on 1E USS

Have time delayed (.25 sec) UV relays which trip the motor feeder breakers from the bus

EDG start under

LOP:


Degraded voltage: both incoming feeders <92% with a 20 sec TD


LOP: Both feeders are <92% and bus is <70%




LOCA: 1.68 psig OR -129 RPV level

If UV condition persists for >= 0.5 sec

LOP sequencing circuit initiates PSIS to prevent auto starting of selected loads until LOP timers cycle. The time delays for starting CS and RHR pumps are part of the pump starting circuits and not controlled by the LOP timer

EDG will not load when... (4160)

The flashing trip pushbutton acknowledge is on the 1E 4160 bus

4160 differential overcurrent initiates...

86R:


EDG regular lockout circuit


Normal and alternate feeds trip open and auto closure is blocked


USS transformer feeder breakers trip


All motor circuit breakers are tripped

4160 bus overcurrent initiates:

86T:


EDG regular lockout circuit


Normal and alternate feeds trip open and auto closure is blocked


USS transformer feeder breakers trip


All motor circuit breakers are tripped

With a bus over current and the supply breaker (norm or alt) does not trip...

After 0.2 sec TD then it trips the 13.6 kV xfmr supply breakers.


This will cause all of the 4160 busses supplied by the xfmr except the one tripped by the over current to transfer to the other xfmr


Will also cause a fast transfer of the 502 and 503 loads over to their opposite xfmrs

LOCA is sensed from x logic...

x= core spray



The EDGs are started


the LOCA sequencer is initiated


LOCA load shedding of selected non-1E loads occur


PSIS will prevent starting of selected equipment until the LOCA sequencing circuit timers cycle

Incoming feeder interlocks

AUTO CLOSE BLOCK must not be selected AND


Associated bus must be >94% of normal