Normal steam header pressure |
100-110 psi |
|
Steam header pressure lo alarm |
90psi |
|
Steam header pressure hi alarm |
125psi |
|
Feed pump normal pressure |
175-190psi |
|
Feed pump lo pressure shutdown |
135 psi |
|
Feed tank hi alarm |
95% |
|
Feed tank lo alarm |
30% |
|
Control air pressure lo |
80psi |
|
Condensate salinity hi |
8.o ųmhos |
|
Drain cooler salinity hi |
8.o ųmhos |
|
Low boiler level |
-5" |
|
Low low boiler water level |
-10" |
|
Hi boiler water level |
+5" |
|
Safety relief nr1 |
Lifts @ 145 psig Reseats @140 psig |
|
Safety relief nr 2 |
Lift @150psig Reseats @140 psig |
|
Dft level hi |
79 gals |
|
Dft level lo |
19 gals |
|
Dft relief valve |
30psig |
|
Whb steam output rating |
14648 lbs/hrs max |
|
Feed pump rating |
55gpm @190psid |
|
Circulating water pump rating |
150gpm @30psid |
|
Dft feed booster pump |
60gpm @70psig |