When taking over a shift, preliminary safety checks allow the boiler operator to identify any possible problems.
|
True
|
|
A routine set of duties helps the operator to complete all assigned tasks.
|
True
|
|
In general, boilers should be blown down every 24 hr.
|
True
|
|
The main steam stop valve should be closed during normal plant start-up.
|
True
|
|
The boiler vent must be closed during warm-up to prevent pressure from escaping.
|
False
|
|
A bottom blowdown can be used to control chemical concentrations in the boiler.
|
True
|
|
The furnace brickwork should be cooled rapidly for energy efficiency.
|
False
|
|
There should be pressure in the boiler when dumping.
|
False
|
|
The boiler should be blown down when it is on a heavy load.
|
False
|
|
The operator's hand must always be kept on the blowdown valve during blowdown.
|
True
|
|
The blowdown valve should be kept open long enough for the water level in the gauge glass to drop out of sight.
|
False
|
|
The quick-opening valve is opened first and closed last during blowdown.
|
True
|
|
The low water fuel cutoff is checked for proper operation with the burner firing.
|
True
|
|
Try cocks can be used as a boiler water level indicator.
|
True
|
|
Steam discharged from the top try cock indicates a low water level.
|
False
|
|
An evaporation test is performed by blowing down the low water fuel cutoff.
|
False
|
|
Water added to a boiler with a low water level condition could cause a boiler explosion.
|
True
|
|
Furnace explosions are caused by steam in the fuel oil.
|
False
|
|
Any abnormal odor of gas should alert the boiler operator to a possible leak.
|
True
|
|
The boiler must be filled with water heated to 50°F before it is started for the first time.
|
False
|
|
Bottom blowdown is performed by opening the gauge glass blowdown valve.
|
False
|
|
Leaking fuel oil in the furnace could lead to a furnace explosion.
|
True
|
|
The boiler should be inspected to determine the cause of a low water level condition.
|
True
|
|
The furnace should not be purged after a flame failure.
|
False
|
|
A boiler must be taken off-line before it can be inspected.
|
True
|
|
Main steam stop valves must be tagged out during a boiler inspection.
|
True
|
|
After a boiler is dumped, it should dry completely before cleaning.
|
False
|
|
A hydrostatic test is a steam test used to check for boiler leaks.
|
False
|
|
A malfunctioning steam trap can result in a steambound feedwater pump.
|
True
|
|
Tools and equipment must be provided for the boiler inspector during boiler inspection.
|
True
|
|
During a hydrostatic test, the boiler is half filled with water.
|
False
|
|
Dry lay-up is recommended for boilers that will be out of service for an extended period.
|
True
|
|
Moisture left on metal surfaces during dry lay-up could cause scale buildup.
|
False
|
|
More pounds of silica gel than quicklime are required when laying up a boiler dry.
|
True
|
|
All valves are opened during dry lay-up.
|
False
|
|
A scratch on the inside of a gauge glass can cause it to break.
|
True
|
|
A clean gauge glass is necessary to accurately determine boiler water level.
|
True
|
|
A boiler inspection is commonly performed by the plant manager.
|
False
|
|
An evaporation test lowers the boiler water level rapidly.
|
False
|
|
Two people should be present during an evaporation test.
|
True
|
|
All plants maintain boiler room logs for an 8-hour period.
|
False
|
|
A boiler room log can be used to determine the cause of a boiler shutdown.
|
True
|
|
Boiler lay-up is required when the boiler is out of service between shifts.
|
False
|
|
When warming up the boiler, the low water fuel cutoff should be blown down before the steam pressure gauge records pressure.
|
False
|
|
When shutting down the boiler, the main steam valve should be closed immediately after the furnace is shut down.
|
False
|
|
The first thing a boiler operator should do when taking over a shift is ___.
|
check the boiler water level
|
|
When the low water fuel cutoff is blown down, ___.
|
the burner should shut off
|
|
The boiler pressure should always be ___ the header pressure when cutting a boiler in on the line.
|
slightly below
|
|
The boiler should be blown down when it is ___.
|
on a light load
|
|
ASME code states that on boilers having two bottom blowdown valves, the ___ valve should be closest to the boiler.
|
quick-opening
|
|
After blowing down the water column and gauge glass, the water should ___ the gauge glass.
|
quickly enter
|
|
If water cannot be seen in the gauge glass, ___.
|
the burner should be secured
|
|
A furnace explosion can be caused by ___.
|
a buildup of combustible gases or vapors, leaking gas or fuel oil, & improper furnace purge
|
|
The ___ blowdown valve is used to dump the boiler.
|
bottom
|
|
The best method for checking for leaks in gas lines is ___.
|
applying soapy water
|
|
A(n) ___ test is used to check for leaks in the boiler.
|
hydrostatic
|
|
All traces of coal, soot, and ash must be removed to prevent ___ from forming when mixed with water.
|
sulfuric acid
|
|
A steambound pump is caused by ___.
|
excessive water temperature
|
|
A(n) ___ test is used to test the low water fuel cutoff.
|
evaporation
|
|
A ___ is used to record information regarding operation of the boiler during a given period of time.
|
boiler room log
|
|
The boiler must be ___ when the low water fuel cutoff is blown down.
|
firing
|
|
The flame scanner is removed with the burner firing, the ___.
|
burner should shut off
|
|
To prevent damage to the furnace brickwork, the furnace ___.
|
should be cooled slowly
|
|
Boiler ___ is a condition when a boiler is operating at or above its maximum allowable working pressure.
|
overpressure
|
|
Before dumping the boiler, the boiler heating surface should be ___.
|
cool enough to touch
|
|
The water column whistle valve is ___ during the hydrostatic test.
|
removed
|
|
During the hydrostatic test, pressure on the boiler is brought up to ___ times the MAWP.
|
1½
|
|
Water used to fill the boiler during the hydrostatic test should be a minimum of ___°F.
|
70
|
|
___ is placed on the water side of the boiler when placing the boiler in dry lay-up.
|
Quicklime
|
|
Gauge glass nuts are tightened by hand and then turned ___ with a wrench.
|
1/4 of a turn
|
|
A ___ test is the most accurate method of testing the low water fuel cutoff.
|
evaporation
|
|
When testing a low water fuel cutoff, the burner should shut off when ___.
|
water is still visible in the gauge glass
|
|
The internal mechanism of a low water fuel cutoff should be periodically removed from the bowl to check and ___ the float ball.
|
clean
|
|
To correct a high water condition, a ___ is performed.
|
bottom blowdown
|
|
New ___ should be used when replacing a broken gauge glass.
|
packing nuts
|
|
A boiler is given a bottom blowdown to ___.
|
discharge sludge
|
|
A leak on gas lines and equipment must be repaired ___.
|
by authorized personnel
|
|
For maximum safety in operation of a low pressure boiler, the low water fuel cutoff should be tested ___.
|
daily
|
|
Boiler data that is commonly recorded on a boiler room log includes ___.
|
boilers on line, steam pressure, & condensate return temperature
|
|
All running auxiliaries (fuel oil pumps, fan, water pump, and burner) should be checked for proper ___.
|
temperature, pressure, & lubrication
|
|
The proper testing of boiler accessories is determined by procedures suggested by ___.
|
ASME Code
|
|
After testing the flame scanner, ___.
|
reset the programmer
|
|
During the evaporation test, the ___ is secured.
|
automatic city water makeup feeder
|
|
During a boiler inspection, the main steam stop valve is ___.
|
closed and tagged out
|
|
The ___ must be covered with water before water can be added safely.
|
heating surface
|