Single wall vent connector gage |
28 gage smaller than 6" |
|
If portions of vent connector have no dilution air min gage of |
24 |
|
Incinerator min gage |
20 gage for vent connector |
|
Aluminum vent connectors |
-22 B&SG (Brown and sharp gage) -3“-5“ |
|
Single wall vent connector min clearance from combustibles |
6" |
|
Type B vent min clearance from combustibles |
1" |
|
Can a single wall vent connector pass through floor or ceiling? |
No |
|
When is the ONLY time a single wall vent connector may pass through a wall? |
If protected with ventilated thimble |
|
Vent must be ___ higher than a roof, and ___ higher than any obstruction within ___? |
1) 2 ft 2) 2 ft 3) 10 ft |
|
Chimney must be ___ higher than a roof, and ___ higher than any obstruction within ___? |
1) 3 ft 2) 2 ft 3) 10 ft |
|
Vent terminating and passing through wall must be ___ above grade? |
1 ft |
|
What is BH vent |
Is CPVC mus be system s-636 certified Has positive vent pressure |
|
BH vent must be ___ higher than a roof, and ___ higher than any obstruction within ___? Aka special venting system |
1) 18" 2) 18" 3) 18" |
|
ROT for sizing single appliance vent |
Vent connector and vent, same size appliance flu collar or draft hood outlet |
|
ROT for sizing single appliance for chimney |
Vent connector same size as appliance flue collar or draft hood outlet. Chimney is one size larger |
|
ROT sizing for tro or more appliances for vent |
Vent connector for each appliance same size as appliance flue collar or draft hood outlet. Vent are sized by taking all the areas of largest vent then adding half the area of the rest |
|
ROT sizing for two or more appliances for chimneys |
Vent connector for each appliance same size as appliance flue collar or draft good outlet Chimney area sized by using area of largest vent than adding half the area of the rest |
|
Min size of vent |
-3" diameter -apply to catagory I apiances only other appliances are sized by manufacturers code |
|
Direct vent appliances uses what kind of vent pipe arrangement |
Coaxial pipe: vents products of. Combustion through a pipe inside another pipe that brings combustion air Ex. Decorative fire place |
|
Direct vent appliances below grade may use a ___ fitting |
Snorkel fitting |
|
How high above finished grade must vent be? |
12" |
|
Power assisted vents |
Vents that once been connected to B vent to vent though the roof. They have ben modified to vent through a wall. |
|
Only plastic pipe allowed for use today for venting |
S-636 *first 3ft of vent pipe must be vissible |
|
Only auto damper allowed to be added to appliance is ____, other whose it must come with it installed |
Thermal activated |
|
Are manual dampers permitted in a venting system? |
No |
|
Vents with psoitve vent pressure( catigorie III & IV) must run independently to outdoors |
True, may not be connected together |
|
Can a vent with positive vent pressure be connected to any natural draft vent (type B) or to a venting system for draft hood equipped appliances? |
No |
|
Drafthoods / draft control devices are used to maintain |
Steady negative pressure |
|
Draft control devices include |
Draft hoods and draft regulators smlike the barometric type |
|
What's a barometric draft regulator |
-Like draft hoods -Relife opening has floating plate or gate that constantly adjust amount of dilution air, maintain desired vent pressure |
|
Three basic draft hood designs |
-Verticle -horizontal -horizontal and verticle (angle) |
|
Single acting baromateic regulator: |
-gate swings inward only on negative pressure -used in solid fuel burning apications |
|
Double acting baromateic regulator |
- gate swings inwards AND outward depending on vent pressure -used in converted appliances |
|
Does a mid and high efficiency appliance have a draft control device? |
No |
|
Main function of draft hood |
-allows escape of flue gas under abnormal vent conditions -prevent back draft from enterinf combustion chamber -neutralizes excessive stack action -dilutes products of combustion -Helps room vent |
|
GSG stands for |
Galvanized steel gage |
|
When can vent connector be type B |
Where extreme vent connector cooling and condensation is a problem |
|
Vent grade |
1/4“ per ft |
|
Combustible surface temps max |
194 degrees F |
|
Vents passing through wall need ventilated thimble __ or larger in diameter than vent. |
-4" -needed when distance from appliance to pen point is less than 6 ft |
|
Vents passing through wall need ventilated thimble __ or larger in diameter than vent. |
-2" -needed when distance from appliance to pen point is 6 ft or greater |
|
Dampers in vent connectors may be |
Thermal operated type |
|
Manifold sizing/common vent |
Area all vents, add total than square root Round up for pipe size if need |
|
Can you use rule of thumb sizing method for sizing fan assist |
-no -only for natural draft appliances |
|
Where should the smallest sized vent connector be connected to a a vent or chimney |
At the top, above all larger vents. Same applies for fan assist. However if both fan must be lowest connection |
|
Can a B vent pass through wall |
Yes |
|
Air tight building refered to as |
Type A bldg |
|
Loose building reford to as |
Type B bldg |
|
Min size masonry chimney |
12“ sq |
|
Where can appliance in a commercial kitchen be vented to |
Exhaust canopy |
|
Catagory I appliance |
- operates with a non-positive vent pressure and is with a vent gas temperature of at least 140F above its dew point -all draft hood equipped appliances, all fan assist labelled as cat 1 and all appliances certified for venting into b vent |
|
Catagory II appliance |
-operates with a non-positive vent pressure and with a vent gas temperature less than 140 F above dew point -measured at entrance of venting system 300F Higher efficiency apiances than catagory I -still has slight negative pressure in the venting system |
|
Catagory III appliance |
-operates with positive vent pressure and with a vent gas temp Atleast 140F above dew point -measured at entrance to the vent systen -non condensing type appliance usually 3" plastic, 3" ss venting system -may have some condensation so vent needed |
|
Catagory IV |
-operates with positive vent pressure and vent gas temp less than 140F above dew point -measured at the entrance to venting system -condensing high efficient appliance usually have 2" plastic venting system and a drain |
|
Vent terminate |
-7ft from driveway / paved sidewalk public prop -6ft from mech air supply inlet to any building -above regulator: 3ft from center and 16 ft up |
|
Flue gass discharge opening for outdoor pool heater shall terminate no less than ___ ft from any building opening. |
10ft |