What is "B" vent referred to in the vent sizing tables? What is the maximum temperature that b vent can handle?

Double wall


470 degrees Fahrenheit

What is C vent referred to in the sizing tables?

Single wall

When would you use A vent?

For high temperature and venting oil or solid fuel

What type of material is type B H venting made of? What are the temperature ratings of that material?

PVC up to 65 degrees C


CPVC up to 90 degrees C

What does LTVH refer to?

Least total vent height

Can a single fan assist Appliance be vented into a chimney

No

How much would you de-rate the values in the book when using a corrugated metallic chimney liner?

20%

When is a chimney considered to be exterior?

When one or more sides is exposed to the outside

What is the minimum vent height required if the vent size is reduced from the flue collar size?

10 ft

How many elbows are assumed when the vent connector lateral length is greater than 0?

2

May a fan assisted Appliance beat individually vented into a tile lined masonry chimney?

No

When common vented appliances are located on the same floor how is the total available height determined?

The height is measured from the highest draft Hood or the flue collar to the level of the cap or terminal

Is linear interpolation of table entries allowed when desired values are not listed?

Yes

Is extrapolation be on the table entries allowed when desired values are not listed?

No

When the Code table shows more than one vent size acceptable which is preferred?

The smallest

Installing an oversized venting system may result in condensation being produced by the products of combustion true or false

True

The products of combustion in a gas fired kitchen range are vented directly into the room true or false

True

Sealed, separated, or direct vent appliances get all of the required air for combustion from within the room or space that the appliances in true or false

False

Type c vent will require how much clearance from combustibles

6 in

A combustible material is protected by a piece of sheet metal spaced out 1in, using non combustible spacers. Based on this installation how much clearance is required from a single wall vent to a combustible?

2 inches

Type BW vent must terminate a minimum of how many feet above the floor?

12 feet

A vent from an appliance must not terminate within how many feet of a mechanical Air Supply to a building

6 feet

Flue gases will begin to condense at a temperature of approximately

127 degrees Fahrenheit

The minimum clearance from combustibles for a type A single wall chimney is

18 in