Where does each service water pump take suction?

After the "A", "B", and , "C" traveling screens

Which heat exchangers does Service water directly cool?

TBCCW


RBCCW

Find more!!

Which area room coolers is directly cooled by service water?

Turbine building 31'6", 4.160kv switchgear room.

Describe the heat reject path for the "A" DC switchgear room ventilation system during accident (SIAS) conditions?

"A" DC switchgear room general area to the Chill water system via x84A, "A" DC switchgear cooler. Chill water to tbccw via x196A, "A" vital chiller. Service water to long island sound via the seal well/quarry cut.

"SW PUMP A STNR TROUBLE" annunciator is in at the control room, due to a verified high D/p on the "A" service water strainer. What should be occuring?

The strainer should be backwashing and should continue to backwash for at least 5 min.

What component in the service water system is a power operated assembly to filter debris and prevent fouling of heat exchanger tubes and other small flow passages?

Service Water Strainers

What describes the design purpose of the Kirk Key interlock associated with the Service Water strainers

Prevents cross tying MCCs B51 & B61