What two Candela settings can be required in a sleeping room?

<24 inch from ceiling - 177 CD (ceiling mount)


>24 inch from ceiling - 110 CD (wall mount)

In a room over 14' x 16', what is the maximum distance from the pillow a visual alarm can be located.

16 feet

You are installing a system at camp anyname. Where would you install the smoke detectors.

Inside or outside the sleeping quarters and on each level including the basement.

What are the over current protection for batteries in a fire alarm minimum and maximums?

150% min and 250% max of the batteries operational range.




NFPA 1999 1-5.2.9.3

At what temperature must a water temperature sensing device operate?

40 Degrees

When are non-restorable heat detectors to be sent out for lab testing, and how many at each interval?

After 15 years 2 devices out of 100 should be sent for testing and then every 5 years thereafter.

Which detector will best sense invisible particles from a flaming fire?

Ionization Detector

How many non-restorable heat detectors out of 100 are the be sent for testing?

Two

On a ceiling that slopes 1' in 8', where are the smokes to be located?

Peaked or Shed type, those having a slope of 1.5" per foot or more must have a device within 3' of the peak then standard placement.




On ceilings with less that 1.5'' per foot slope standard placement.

A wall mounted detector must be placed where?

With the top edge more then 4 inches from the ceiling and not more than 12 inches from the ceiling.

What is the heat detector spacing listing of a heat detector and a combination smoke/heat detector?

Heat -50'


Smoke/Heat - 30'

On a system set up for positive alarm sequence the operator has how many seconds to initiate the investigation phase?

15 seconds

On a positive alarm sequence system how long can the investigation phase be.

180 seconds

How many years is the Seattle certification good for?

It must be renewed each year but only requires retesting every 3 years.

How many days does a new hire have to obtain a Seattle certification?

90 days

On a beam type ceiling, when is spacing reduced?

When a beam is more than 4" but less that 12" deep and 8' on centers, spacing is reduced 50%

In a corridor what is the maxim distance between visual devices, And where are they placed?

Maxim distance of 100 feet and they must be within 15 feet from the end of the corridor.

What is the reduction in spacing when one mirror is used with a beam detector?

2/3 spacing

Manual pull stations are required within how many feet of an exit, and with a maxim travel distance between units of what?

5 feet of an exit and with a travel distance of not more than 200 feet.

Completely discharged batteries must be recharged by the charging circuit within how many hours?

48 Hours

How many seconds from loss of primary power does a system have to generate a trouble?

30 seconds after main voltage falls below 85% of the rated voltage.

True or false. Replacement of fire alarm panel will require a fire department inspection?

True

What quantity of unaffected devices must be tested when a panel is replaced.

10%

What parts of a Seattle system certification must be completed prior to a final inspection?

Parts 1, 2, 4 -10.




Part 3 is completed after the operational test.

True or False. Prior to a final fire department inspection a system must be pre-tested.

True

What is the color code for a 350 degree heat detector?

175-249 degrees, white


250-324 degrees, Blue


350-399 degrees, Red


400-499 degrees, green


500-575 degrees, orange




This can be remembered using the phrase. White Boys Read Good Operas.

All holes around a duct detector must be sealed because?

The possibility of dilution or redirection of smoke with-in the duct.

Duct detectors can not be used to replace area detection because?

Dilution of smoke and the HVAC unit may not be active.

Duct detectors must be installed on HVAC systems over ___________ CFM

2000 CFM

Duct detects are to be installed in HVAC systems at what CFM levels.

Supply 2000 CFM


Exhaust 15000 CFM


Both 15000 CFM

HVAC systems over _________ CFM must be shut down to prevent the spread of smoke.

2000 CFM

A deluge system is tested by?

An Alarm test bypass switch.

A preaction system is tested by?

An alarm test bypass switch.

A wet sprinkler system is tested by?

An inspectors test valve

When must a tamper switch on a valve generate a supervisory condition?

Within 2 revolutions of the wheel or one-fifth of the stem travel. Which ever is less.

A tamper switch cannot?

Obscure the view of the PIV status window.


Impede the operation of the valve.

A high rise building is a building that rises more than how many feet from the ground?

75 Feet

Battery's must provide operation for________ stand by power and ______ Alarm operation.

24 hours stand by and 4 minutes Alarm activation.

Ambient temperature must be ________ Degrees below the rated operation of the heat detector installed.

20 Degrees

Transformers and generators that supply power to the FACP must be installed according to what?

NFPA 110 and NFPA 37

Testing requirements for a FACP are found where?

NFPA 72

Smoke detectors must be located farther away then ___________ from a supply air grill.

36 inches

Audible devices must be ________ above ambient noise level.

15 db

How many feet from a door is a smoke detector to be located when it is being used for closure activation?

5 feet and no closer than the depth of the header.

How many devices may be installed on a supervised loop?

64 devices of which only 42 can be smoke detectors.

How many devices can be installed on an unsupervised loop?

18 units of which only 12 can be smoke detectors.

What information is required on a service label?

1. Do not remove by order of the fire Marshall.


2. Name of service company.


3. Address of service company.


4. Phone number of service company.


5. Date of last service.


6. Signature of service tech.


7. Description of work preformed.

What levels will generate a supervisory condition on a water level monitoring system. Pressurized and non pressurized tanks.

3'' above or 3'' below on a pressurized tank.


12" below on a non pressurized tank.

What are the average ambient sound levels for business, Industrial, Institutional, and residential buildings?

Business 45 db


Industrial 80 db


Institutional 50 db


Residential 35 db

A room temperature supervisory signal shall signal at what temperature? And shall restore at what temperature?

Signal at 40 degrees.


Restore at 40 degrees.

Circuits capable of transmitting an alarm signal during a single open or a non-simultaneous single ground fault are designated as class_____

Class A

Circuits incapable of transmitting an alarm beyond the location of a single open or non-simultaneous single ground fault on a conductor shall be designated as class _____

Class B

The maximum number of water flow switches permitted on a single circuit is?

5 water flow switches

Where audible devices are provided to signal sleeping areas they shall have a sound level at least _______

15 bd above the average ambient sound level, or 5 db above the the expected maximum sound level lasting 60 seconds or more, or 70 db. Whichever is greater.

Wall mounted devices shall have there top edge mounted not less than _________ above floor level and not less than ________ from the ceilings.

90 inches above floor level


4 inches from but not more than 12" from the ceilings.




NFPA 2007 5.7.3.2.1

In the event of communications equipment failure a backup Chanel to a subsidiary station shall operate within________ and be repaired within _______

90 seconds


5 days

A complete record of testing shall be kept for?

Two years

Record of signals received at monitoring shall be kept for how long?

1 year

Trouble signals and there restoration shall be automatically transmitted to the monitoring station within ____________

200 seconds.

What voltage can a battery under load not fall below.

2.05 volts per cell

In Seattle what is the test frequency for high rise buildings?

Quarterly

In Seattle what is the cost of any subsequent Fire Marshal inspections.

$45 per hour

The installation of all wiring and equipment shall be in accordance with NFPA 70 and specifically what articles?

Articles 760, 770, 800

Initiation of an alarm signal shall occur within _____ seconds of a water flow.

90 seconds

True or false. Manual fire alarm boxes shall be located within 5 feet of an exit doorway on the first floor.

False, they must be located within 5 feet of an exit doorway and at each exit on each floor.

What does the acronym D.A.C.T. mean?

Digital alarm communicator transmitter

What is NFPA 70?

National electrical code

Activation of alarm notification devices or voice evac systems shall occur withing how many seconds of an initiating device activation?

20 seconds

Trouble signals and restoration for them shall be transmitted within how many seconds?

200 seconds

Smoke detects shall not be installed in places where any of these ambient conditions exist?

Temperatures below 32 degrees.


Temperatures above 100 degrees.


Relative humidity above 93%


air velocity above 300 ft/per minute.

Manual fire alarm boxes shall be mounted at what height?

3.5 feet to 4.5 feet above the floor.

The maximum time elapse from sensing a fire until it is reported to a monitoring station shall not exceed how long?

90 seconds

In a lead acid type battery, with the battery at full charge the voltage or each call shall be______

2.3 volts per cell at 77 degrees F

True or False. Where a two way telephone communications circuit is provided the wires shall be monitored for a short circuit fault.

True.

A rate of rise heat detector is defined as?

A device that responds when the temperature rises at a rate exceeding a predetermined temperature.

A sloped ceiling is a ceiling that slopes more than.

1 in 8

High or low pressure switches shall signal if the pressure changes more than_______

10 PSI

Batteries shall be protected from over-current by protection having a rating of_______________

150% to 250% of the maximum operating load.




NFPA 1999 1-5.2.9.3

Smoke detector sensitivity shall be tested at what interval?

One year after install and every other year thereafter.

Systems that require the operation of two automatic detectors are permitted under these conditions.

1.They do not use a verification function.


2.They are permitted by the AHJ


3.There are at least two devices in each protected space.

To test a water flow switch water shall be flown where and in what amount?

Through the inspectors test and in in amount equal or greater than a single sprinkler head.

In a dry sprinkler system water may be flown where to test the flow switch?

Through an alarm test bypass connection.

True or False. Fire alarms can share components with non fire alarm systems such as mass communication systems.

True they can share components.